WIKA operating instructions model A2G-85
When using long connection wires it may be necessary to use
a separate GND wire for voltage output current to prevent
measurement distortion. The need for an extra GND wire
depends on the cross section and length of the used
connection wires. If long and/or small cross section wires are
used, supply current and wire resistance may generate a
voltage drop in the common GND wire resulting in a distorted
output measurement.
6. Menu navigation
6.1 Standard version
1. Selecting the instrument menu
Keep the selection button “SELECT” pressed for at least 2 seconds to
access the menu.
▶
MENU is displayed
2. Selecting and adjusting the parameters
Press the “DOWN” button once
▶
Next menu item is displayed
Supply voltage U
B
Output DC 0/2 … 5/10 V
Output DC 0/2 … 5/10 V
V
V
Extra GND wire
XXXXXXXX
XXXX
5. Commissioning, operation / 6. Menu navigation