EtherNet/IP gateway
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
80
Illustration 17: Activation of EtherNet/IP in samosPLAN
6
NOTICE
Selection of the SP-EN-IP gateway is possible for modules of type SP-COP2-ENI from version D-
01.01.
Adapting the IPv4 data
The IPv4 data of the SP-COP2-ENI module can be adapted to the PLC settings in samosPLAN
6.
Requirement
During transmission of the IPv4 data, the device must not be in
Run
(Execute)
mode. The command
bar must be displayed on the left above the
Start
command, as shown in the following illustrations.
If this is not the case, stop the device via the
Stop
button.
Required window layout
Illustration 18: Setting of the IPv4 device data in samosPLAN
6
Configuring the data to PLC
79846795
The data transferred to the PLC and thus from the target device to the sender (Target to Originator,
T
→
O) can be adapted in the "samosPRO COMPACT
→
SP-EN-IP[0]" tab of the gateway configuration
in samosPLAN
6. By default, the first three bytes contain data for the input terminals I1 to I16 (and
IQ1 to IQ4 in the appropriate configuration as an input). Byte 4 comprises data of the output termi-
nals Q1 to A4 (and IQ1 to IQ4 in the appropriate configuration as an output).
8.3.3