EtherNet/IP gateway
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
79
Other connections supported by the SP-COP2-ENI module are listed in the following table. You can
find information on these assembly instances in the table "
Overview of assembly databytes [ch. 8.5.1,
Table 39: Class 1 connections supported by the SP-COP2-ENI module
Name of the connection
Assembly for data
from the PLC to SP-
COP (O
→
T)
Assembly for data
from SP-COP to the
PLC (T
→
O)
Logic output (1 to 400) and logic/physical input
37
57
Logic output (1 to 400) and logic/state/system mode
assembly
37
167
Logic output (81 to 400) and logic/physical input
138
57
Logic output (81 to 400) and logic/state/system
mode assembly
138
167
Logic output (161 to 400) and logic/physical input
139
57
Logic output (161 to 400) and logic/state/system
mode assembly
139
167
Logic output (241 to 400) and logic/physical input
140
57
Logic output (241 to 400) and logic/state/system
mode assembly
140
167
Logic output (321 to 400) and logic/physical input
141
57
Logic output (321 to 400) and logic/state/system
mode assembly
141
167
Logic/physical input (“Listen only”)
199
57
Logic/state/system mode assembly (“Listen only”)
199
167
Logic/physical input (“Input only”)
198
57
Logic/state/system mode assembly (“Input only”)
198
167
Connection point 199 (= 0xc7) is used for
Listen Only
and connection point 198 (= 0xc6) for
Input
Only
. Both possess a data size of zero. This means that the PLC does not make any data available for
the SP-COP2-ENI module.
If the PLC only requires process data from the SP-COP module, the user is recommended to use a
connection with
Input Only
.
Basic configuration of the controller module
79825419
The integrated gateway SP-EN-IP (EtherNet/IP gateway) is a constituent part of the SP-COP2-ENI
module.
Activating the gateway
You can activate the integrated gateway in the configuration dialog of the SP-COP2-ENI module in
the
Properties
docking window:
8.3.2