Deployment
Wieland Electric GmbH | BA001269 | 09/2021 (Rev. A)
39
6.3
Setting the IP address
Setting possibilities
•
Setting the IP address via web page
•
Setting the IP address via address switch
•
With the
ricos
FLEX BC MODBUS you should always use a static IP address.
•
If the
ricos
FLEX BC MODBUS is configured via DHCP, this must provide a valid gateway address,
otherwise the IP address is not accepted!
•
When using a DHCP server, make sure that the IP address assignment (lease) in the DHCP server is
not changed. Otherwise, after a restart, the
ricos
FLEX BC MODBUS cannot be found by the master.
Setting the IP address via web page
On delivery the
ricos
FLEX BC MODBUS has the following settings:
•
Password and module parameter are deleted.
•
On delivery, the switches pos. 2 ... 7 of the address switch are set to
‘0’
Subnet mask:
255.255.255.0
IP Address:
10.0.0.1
If the systems are in the same IP circle, you can use this address to access the web page IP address
allows you to access the web page of the integrated web server, see 6.4.1 Web server on page 40,
and change the IP address data accordingly via tab
‘IP’
.
Setting the IP address via address switch
Ranking for the IP address configuration
•
The switch for DHCP activation pos. 1 has the highest priority.
•
If there is no DHCP server, the IP address (192.168.1.x) set at the switches pos. 2 ... 7 is used.
•
If no address is set, i.e. all switches pos. 2 ... 7 are set to '0', the stored IP address (default
10.0.0.1) is used.
If your systems are in the same IP circle, you can access the
ricos
FLEX BC MODBUS via the IP ad-
dress.
NOTICE