White Rodgers 668-451 Installation Instructions Manual Download Page 3

3

TESTING (cont’d)

Rotate Cell Assembly counter-
clockwise to remove it. To replace
it, insert end through notched open-
ing in bracket and rotate clock-
wise. NOTE: If bracket is ever re-
moved from burner, Cell Assembly
will not fit if bracket is reinstalled
backwards.

TYPE 956 FLAME DETECTORS

OLD STYLE

NEW STYLE

CELL ASSEMBLY

SOCKET

ASSEMBLY

CELL

BRACKET

F063-0485

F063-2006

Cell only (Old Style)

Cell assembly (New Style)

PART No. OF REPLACEMENT PARTS

4.

If safety lockout problem is of an occasional
nature the following additional check may be
made to insure that flame detector location is not
a marginal one:

a.

Disconnect flame detector leads from “F” terminals.

b.

Attach a jumper wire to one “F” terminal. Start burner.
Then immediately connect jumper wire to the other
“F” terminal. Burner should  continue to run.

c.

With burner running, attach flame detector leads to an
accurate  ohmmeter. Reading of ohmmeter should
be below 1000 ohms, and preferably as low as 500
ohms.

If indicator of ohmmeter remains steady, read-
ings up to 2000 ohms should also be acceptable.
Generally, the lower the reading, the better the
application, and less likely the chance of burner
flame variation causing a safety lock-out.

d.

If resistance of flame detector is over 1000 ohms, it
may not be able to see the burner flame properly.
Check alignment of the flame detector through the
hole in the static pressure disc. Clean this hole if it is
blocked by foreign matter. Check for broken “F” wires.

e.

If flame detector alignment is good but resistance is
still high, readjustment of burner flame and/or nozzle
replacement may be necessary (according to burner
manufacturer’s instructions).

Be sure to remove wire jumper after finishing this
flame detector check.

NOTE

WARNING

!

Summary of Contents for 668-451

Page 1: ...national electrical codes and ordinances This control is a precision instrument and should be handled carefully Rough handling or distorting compo nents could cause the control to malfunction To prevent electrical shock and or equipment damage disconnect electric power to system at mainfuseorcircuitbreakerbox untilinstallation is complete Do not use on circuits exceeding specified volt ages Higher...

Page 2: ...ing has elapsed the control should lock out on safety stopping the burner 2 Open the line switch 3 Replace Flame Detector lead removed in step 1 4 Wait3minutes Thenoperatethemanualresetbutton on top of control C HIGH LIMIT AND THERMOSTAT CHECK 1 Close the line switch to start the burner 2 Lower the setting of the high limit control to its lowest setting This should stop the burner unless furnace o...

Page 3: ... other F terminal Burner should continue to run c Withburnerrunning attachflamedetectorleadstoan accurate ohmmeter Reading of ohmmeter should be below 1000 ohms and preferably as low as 500 ohms If indicator of ohmmeter remains steady read ings up to 2000 ohms should also be acceptable Generally the lower the reading the better the application and less likely the chance of burner flame variation c...

Page 4: ...tre conforme aux codes et règlements locaux et nationaux qui régissent les installations électriques Votre commande est un appareil de précision qui doit être manipulé avec soin Elle peut se détraquer si elle est manipulée defaçonnégligenteousidescomposantessontendommagées Pour prévenir les risques d électrocution et de dommages matériels coupez l alimentation du système au panneau de distribution...

Page 5: ...de sécurité s est écoulé la commande devrait engager le blocage de sécurité et arrêter le brûleur 2 Ouvrez l interrupteur principal 3 Rebranchez le fil du détecteur de flamme que vous avez débranché à l étape 1 4 Attendez 3 minutes puis appuyez sur le bouton de remise en route manuel qui est situé sur le dessus de la commande C VÉRIFICATION DU LIMITEUR À MAXIMUM ET DU THER MOSTAT 1 Fermez l interr...

Page 6: ...continuer à fonctionner c Avec le brûleur en marche branchez les fils du détecteur à un ohmmètre juste La lecture devrait être inférieure à 1 000 ohms et se situer de préférence dans les alentours de 500 ohms Si l indicateur de l ohmmètre est stable une lecture allantjusqu à2000 ohmsdevraitêtreacceptable Règle générale cependant une faible résistance entraîne une meilleure installation et diminue ...

Reviews: