White Rodgers 50A55 Troubleshooting Manual Download Page 2

Place

thermostat

fan switch in

the ON

position.

Return fan

switch to

AUTO position.

Indoor Blower

Check

Does indoor

blower run at

HEAT speed?

YES

YES

NO

NO

YES

NO

YES

NO

YES

NO

Indoor blower

fault. Repair or

replace. Check

operation.

Is 24V

present at

control

terminals

G & C?

Is 120V

present at

control terminals

COOL & CIR

NEUTRAL?

Is 24V

present at

control

terminals

R & C?

Does LED

flash 1 time

when disconnect

is turned

ON?

Is 120V

present across

primary of control

transformer?

Is 24V

present across

secondary of

transformer?

Is 24V

present

across 12-pin

connector pins TH

& TR on the

control?

Is 120V

present at

control terminals

XFMR & XFMR

NEUTRAL?

Is 120V

present across

control terminals

LINE & LINE

NEUTRAL?

Repair wiring

from control to

thermostat. Check

operation.

Repair wiring

and/or plug

connection. Check

operation.

Replace

transformer. Check

operation.

Repair wiring to

transformer. Check

operation.

Correct 120V

power supply. Check

operation.

Replace control.

Check operation.

Replace control.

Check operation.

1A

1B

1E

1D

1C

1F

1I

1H

1G

1J

1K

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

CHART 1

WARNING

!

If diagnostic indicator (LED) 

shows continuous flashing, turn 

off gas supply at source before 

disconnecting electrical power!

INTEGRATED FURNACE

CONTROL MODULE

TROUBLESHOOTING

GUIDE

www.white-rodgers.com

190

TECHNICAL

 HELP