White Rodgers 50A55-285 Installation Instructions Manual Download Page 7

7

SYSTEM LOCKOUT AND

DIAGNOSTIC FEATURES

SYSTEM LOCKOUT FEATURES

When system lockout occurs, the gas valve is de-energized, the
circulator blower is energized at heat speed, and, if flame is
sensed, the inducer blower is energized. The diagnostic indica-
tor light will flash or glow continuously to indicate system status.
(System lockout will never override the precautionary fea-
tures.)

To reset the control after system lockout, do one of the
following:

1.

Interrupt the call for heat or cool at the thermostat for at least
one second but less than 20 seconds (if flame is sensed
with the gas valve de-energized, interrupting the call for
heat at the thermostat will not reset the control).

2.

Interrupt the 24 VAC power at the control for at least one
second. You may also need to reset the flame rollout sensor
switch.

3.

After one hour in lockout, the control will automatically reset
itself.

DIAGNOSTIC FEATURES

The 50A55 control continuously monitors its own operation and
the operation of the system. If a failure occurs, the LED will
indicate a failure code as shown below. If the failure is internal
to the control, the light will stay on continuously. In this
case, the entire control should be replaced, as the control
is not field-repairable
.

If the sensed failure is in the system (external to the control), the
LED will flash in the following flash-pause sequences to indicate
failure status (each flash will last approximately 0.25 seconds,
and each pause will last approximately 2 seconds).

1 flash, then pause

System lockout

2 flashes, then pause

Pressure switch stuck closed

3 flashes, then pause

Pressure switch stuck open

4 flashes, then pause

Open limit switch

5 flashes, then pause

Open rollout switch

6 flashes, then pause

115 Volt AC power reversed/Im-
proper ground

7 flashes, then pause

Low flame sense signal

Continuous flashing

Flame sensed with gas valve

(no pause)

off

The LED will also flash once at power-up.

Summary of Contents for 50A55-285

Page 1: ...er and fan Signals interpreted during continual surveillance of the thermo stat and flame sensing element initiate automatic ignition of the burner sensing of the flame and system shut off during norm...

Page 2: ...Establishing Time 0 8 sec Flame Failure Response Time 2 0 sec At 50 Hz all timing specifications should be increased by 20 Gases Approved Natural Manufactured Mixed Liquified Petroleum and LP Gas Air...

Page 3: ...rminals to mate with those on the control UL approved 105 C rated 16 gauge min stranded 4 64 thick insulation wire is recommended for all line voltage connections Refer to 50A55 specification sheet fo...

Page 4: ...N C ROLLOUT N C AUX HIGH LIMIT N C PRESSURE SWITCH N O FLAME SENSOR PROBE COMPRESSOR CONTACTOR ELECTRONIC AIR CLEANER HUMIDIFIER INDUCER CIRCULATOR BLOWER 50A55 24 VAC 120 VAC 24 VAC CLASS II TRANSFOR...

Page 5: ...al or equivalent low voltage thermostat Y terminal or equivalent 2nd wire from Y terminal goes to 24 VAC HOT side of compressor contactor coil 24 VAC COMMON side of compressor contactor coil gas valve...

Page 6: ...ed the ignitor is turned off and the 50A55 control goes into the retry se quence The retry sequence provides a 60 second wait follow ing an unsuccessful ignition attempt flame not detected After this...

Page 7: ...tomatically reset itself DIAGNOSTIC FEATURES The 50A55 control continuously monitors its own operation and the operation of the system If a failure occurs the LED will indicate a failure code as shown...

Page 8: ...MOUNTING HOLE TEMPLATE FOR MOUNTING HOLE LOCATIONS 4 172 007 2 plcs 6 402 010 2 plcs Refer to page 3 of the installation instructions for proper installation MOUNTING HOLE TEMPLATE...

Reviews: