White Rodgers 1F95W-71 Installation Instructions Manual Download Page 2

2

Approximately

5 feet from floor

1

2

” hole for

thermostat wire

Stout cord with 6”

chain attached

Baseboard

strip moulding

1

4

” guide hole

for sighting

Quarter round

removed

3

4

” hole in floor of partition

Hooked wire for snagging chain

Figure 1. Routing thermostat wires

SPECIFICATIONS

THIS CONTROL IS DESIGNED FOR USE WHERE BOTH SIDES OF THE TRANSFORMER ARE PRESENT TO
THE THERMOSTAT
 (both the hot and common sides of the 24 VAC end of the transformer.)

ELECTRICAL DATA
Electrical Rating

20 to 30 VAC 50/60 Hz.
0.01 to 1.5 Amps (Load per terminal)
2.5 Amps Maximum Total Load (All terminals com-
bined)

Anticipation:

Heating 4 to 40
Cooling 4 to 40

STAGING DATA
Up to 3 heating stages
Up to 2 cooling stages

THERMAL DATA
Setpoint Temperature Range:

40

°

F to 99

°

F (4

°

C to 37

°

 C)

Operating Ambient Temperature Range:

32

°

F to 105

°

F

Operating Humidity Range:

0 to 90% RH (non-condensing)

Shipping Temperature Range:

-40

°

F to 150

°

F

ACCESSORIES

Remote Sense Kit W.R. Part No. F145-1049
Thermostat Guard W.R. Part No. F29-0198 (clear) or

F29-0238 (opaque)

}

Reference Values

INSTALLATION

NEW INSTALLATION

IT IS RECOMMENDED THAT YOU PROGRAM THE
THERMOSTAT WITH BATTERY INSTALLED BEFORE
ATTACHING ON SUBBASE. SEE OPERATION GUIDE
FOR PROGRAMMING INSTRUCTIONS.

Select Thermostat Location

Proper location insures that the thermostat will provide a
comfortable building temperature. Observe the following
general rules when selecting a location:

1.

Locate thermostat about 5 ft. above the floor.

2.

Install thermostat on a partitioning wall, not on an
outside wall.

3.

Never expose thermostat to direct light from lamps,
sun, fireplaces or any temperature radiating equip-
ment.

4.

Avoid locations close to windows, adjoining outside
walls, or doors that lead outside.

5.

Avoid locations close to air registers or in the direct
path of air from them.

6.

Make sure there are no pipes or duct work in that part
of the wall chosen for the thermostat location.

7.

Never locate thermostat in a room that is normally
warmer or cooler than the rest of the building.

8.

Avoid locations with poor air circulation, such as
behind doors or in alcoves.

Route Wires To Location

All wiring must conform with local and national electrical
codes and ordinances.

1.

Probe for obstructions in partition before drilling 

1

2

hole in wall at selected location. Take up quarter
round and drill a small guide hole for sighting (see fig.
1). From basement, drill 

3

4

” hole in partition floor next

to guide hole. In houses without basements, drill 

1

2

hole through ceiling and into partition from above (see
fig. 1).

2.

Through this hole drop a light chain, or 6” chain
attached to a strong cord. Snag cord in basement with
hooked wire. In houses without basements, drop cord
through hole in ceiling and down partitioning; snag
cord at the thermostat location.

3.

Attach thermostat wire to cord and pull wire through
hole in wall so that 6” of wire protrudes.

NOTE

Summary of Contents for 1F95W-71

Page 1: ...acement Installation Remove Old Thermostat Attach Subbase to Wall Attach Thermostat to Subbase Operation 6 System Configuration Set Option Switches Check Thermostat Operation Fan Operation Heating Sys...

Page 2: ...building temperature Observe the following general rules when selecting a location 1 Locate thermostat about 5 ft above the floor 2 Install thermostat on a partitioning wall not on an outside wall 3 N...

Page 3: ...THE WALL 7 Install new thermostat using the following proce dures Attach Subbase To Wall 1 Remove the packing material from the thermostat Place the fingers of one hand on the center top and bottom po...

Page 4: ...RSONALINJURY AND OR EQUIPMENT DAMAGE COULD RESULT NOTE TABLE 2 WIRE IDENTIFICATION LABELS 1 G G 1 9 Y1 Y1 9 2 C C 2 3 L L 3 4 R R 4 5 O O 5 6 B B 6 7 E1 E1 7 8 E2 E2 8 10 Y2 Y2 10 11 W1 W1 11 12 W2 W2...

Page 5: ...HOT side of the second transformer is jumpered to the COMMON side of the first transformer a short will be made Damage to equipment will occur when power is restored IF SAFETY CIRCUITS ARE IN ONLY ONE...

Page 6: ...the top of the thermostat and the 4 connector pins on the thermostat with the connectors near the top right section of the subbase when viewed from the front Gently pivot the thermostat down until the...

Page 7: ...interruption or failure if the battery is not installed When power is restored the thermostat will automatically maintain a temperature of 64 F or a cooling temperatureof82 F factorypreprogrammed asne...

Page 8: ...If you need further information about this product please write to White Rodgers Division Emerson Electric Co 9797 Reavis Road St Louis MO 63123 5398 Attention Technical Service Department...

Reviews: