White Rodgers 1F95-71 Installation Instructions Manual Download Page 3

3

TABLE 1. TERMINAL REFERENCE

LABEL

NUMBER

1F95

TERMINAL

DESIGNATION

FUNCTION

OLD THERMOSTAT

TERMINAL

DESIGNATION

(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)

(10)
(11)
(12)
(13)

G
C

R
O
B

Y1

Y2

W1
W2
W3

Fan Output
Transformer 24 VAC Common

Transformer 24 VAC Hot
Changeover Output (Cooling)
Changeover Output (Heating)

Stage 1 Cool
Stage 2 Cool
Stage 1 Heat
Stage 2 Heat
Stage 3 Heat

REPLACEMENT INSTALLATION

Remove Old Thermostat

1.

Shut off electricity at the main fuse box until installa-
tion is complete. Verify power is off with a voltmeter.

2.

Remove the front cover of the old thermostat. With
wires still attached, 
remove wall plate from the wall.

3.

If the old thermostat has a wall mounting plate,
remove the thermostat and the wall mounting plate as
an assembly.

4.

Use the Cross Reference Guide to find the thermostat
type you are replacing.

5.

Identify each wire attached to the old thermostat
using the labels enclosed with the new thermo-
stat. Record the identification of the wire on the
corresponding blank in Table 1.

6.

Disconnect the wires from old thermostat one at a
time. Pull at least 6 inches of wire out of the wall. DO
NOT LET WIRES FALL BACK INTO THE WALL.

7.

Install new thermostat using the following proce-
dures.

Attach Subbase To Wall

1.

Remove the packing material from the thermostat.
Place the fingers of one hand on the center top and
bottom portion of the thermostat. Grasp the subbase
in the other hand on the top and bottom center, and
gently pull straight out (see fig. 2). The thermostat has
pin and socket connectors. Forcing or prying on the
thermostat will cause damage to the unit.

THIS THERMOSTAT REQUIRES BOTH THE HOT
AND COMMON SIDES OF THE 24 VAC TRANS-
FORMER TO BE PRESENT TO THE THERMOSTAT
FOR OPERATION.

2.

Connect wires beneath terminal screws on subbase
using wiring schematic for your particular application
(see figs. 3 through 6).

3.

Place subbase over hole in wall and mark mounting
hole locations on wall using subbase as a template.

4.

Move subbase out of the way. Drill mounting holes.

5.

Fasten subbase loosely to wall, as shown in fig. 3,
using two mounting screws. Place a level against
bottom of subbase, adjust until level, and then tighten
screws. (Leveling is for appearance only and will not

PULL STRAIGHT OUT

Figure 2. Removing thermostat from subbase

NOTE

Mounting

hole

Pull wires through

this opening

Connect wires under

terminal screws

Mounting

hole

4-pin connector

9-pin connector

O

B

Y1
Y2

C
G

W1

R

W2
W3

Screw

anchors

Figure 3. Subbase

S1 S2 S3

Summary of Contents for 1F95-71

Page 1: ...ermostat to Subbase Operation 6 System Configuration Set Option Switches Check Thermostat Operation Fan Operation Heating System Operation Cooling System Operation Troubleshooting PRECAUTIONS Ifindoub...

Page 2: ...building temperature Observe the following general rules when selecting a location 1 Locate thermostat about 5 ft above the floor 2 Install thermostat on a partitioning wall not on an outside wall 3 N...

Page 3: ...THE WALL 7 Install new thermostat using the following proce dures Attach Subbase To Wall 1 Remove the packing material from the thermostat Place the fingers of one hand on the center top and bottom po...

Page 4: ...RSONALINJURY AND OR EQUIPMENT DAMAGE COULD RESULT NOTE TABLE 2 WIRE IDENTIFICATION LABELS 1 G G 1 9 Y1 Y1 9 2 C C 2 3 L L 3 4 R R 4 5 O O 5 6 B B 6 7 E1 E1 7 8 E2 E2 8 10 Y2 Y2 10 11 W1 W1 11 12 W2 W2...

Page 5: ...HOT side of the second transformer is jumpered to the COMMON side of the first transformer a short will be made Damage to equipment will occur when power is restored IF SAFETY CIRCUITS ARE IN ONLY ONE...

Page 6: ...the top of the thermostat and the 4 connector pins on the thermostat with the connectors near the top right section of the subbase when viewed from the front Gently pivot the thermostat down until th...

Page 7: ...lure if the battery is not installed When power is restored the thermostat will automatically maintain a temperature of 64 F or a cooling temperatureof82 F factorypreprogrammed asneeded CHECK THERMOST...

Page 8: ...If you need further information about this product please write to White Rodgers Division Emerson Electric Co 9797 Reavis Road St Louis MO 63123 5398 Attention Technical Service Department...