White Rodgers 1F90W-71 Installation Instructions Manual Download Page 6

6

ATTACH THERMOSTAT TO SUBBASE

IT IS RECOMMENDED THAT YOU SET OPTION
SWITCHES TO DESIRED POSITION BEFORE ATTACH-
ING ON SUBBASE  
(see OPERATION).  IT IS ALSO
RECOMMENDED THAT YOU PROGRAM THE
THERMOSTAT WITH BATTERIES INSTALLED BE-
FORE ATTACHING ON SUBBASE 
(see OPERATION
GUIDE
 for programming instructions).

POWER TO THERMOSTAT MUST BE OFF BE-
FORE ATTACHING THERMOSTAT TO WALL.
FAILURE TO TURN OFF POWER BEFORE AT-
TACHING THERMOSTAT MAY CAUSE EQUIP-
MENT DAMAGE DUE TO RAPID COMPRESSOR
CYCLING.

To attach thermostat to subbase, line up the plastic snap
guides at the bottom of the thermostat and the three
connector pins on the thermostat with the connectors
near the bottom left section of the subbase (when viewed
from the front).  Gently pivot the thermostat up until the six

pin connectors and the plastic snaps lock into place (see
Fig. 12).  Be gentle when attaching thermostat.  If the
thermostat does not seem to be attaching to the subbase
easily, make sure that the connector pins and plastic
snaps are properly aligned, and that excess wire is
pushed into the wall.  Damage to the thermostat may
occur if force is used.

CAUTION

!

ENGAGE TWO LOWER GUIDES;

PIVOT UP

Figure 13.  Attaching thermostat to subbase

SYSTEM CONFIGURATION

A.  SET GROUP A OPTION SWITCHES

ANY TIME GROUP B OPTION SWITCHES  ARE
CHANGED, THE "AA" BATTERIES MUST BE REMOVED
FOR A MINIMUM OF 2 MINUTES.  DO NOT REMOVE
THE BATTERIES WHEN CHANGING GROUP A OP-
TION SWITCHES.

1.

Total Keypad Activity

2.

Total Keypad Lockout — All thermostat buttons are
disabled.

3.

Limited Temperature Range — Temperature may
be raised or lowered within programmed temperature
limits (temperature adjustment cannot exceed the
lowest cooling or highest heating program tempera-
tures).

OPERATION

B.  SET GROUP B OPTION SWITCHES

ANY TIME GROUP B OPTION SWITCHES  ARE
CHANGED, THE "AA" BATTERIES MUST BE REMOVED
FOR A MINIMUM OF 2 MINUTES.  DO NOT REMOVE
THE BATTERIES WHEN CHANGING GROUP A OP-
TION SWITCHES.

1.

Automatic Changeover (Heating/Cooling Systems
Only)
 — enables thermostat to automatically switch
between heating and cooling programs to maintain
desired room temperature.

NOTE

ON

1

2

Switch #1 OFF
Switch #2 OFF

ON

1

2

Switch #1 ON
Switch #2 OFF

ON

1

2

Switch #1 OFF
Switch #2 ON

Figure 13.  Back of Thermostat

Option Switches

3-pin Connector

6-pin Connector

Batteries

W14

W22

(Group A)

(Group B)

NOTE

ON

1

2

3

Switch #1 ON
Switch #2 OFF
Switch #3 (see step B5)

Summary of Contents for 1F90W-71

Page 1: ...illivolt line orlow voltage have it inspected by a qualified heating and air conditioning contractor electrician or someone familiar with basic electricity and wiring R WHITE RODGERS Do not exceed the...

Page 2: ...un fireplaces or any temperature radiating equip ment 4 Avoid locations close to windows adjoining outside walls or doors that lead outside 5 Avoid locations close to air registers or in the direct pa...

Page 3: ...erminal identification Discard any unused labels PULL AT LEAST SIX INCHES OF WIRE OUT OF THE WALL WHEN YOU DISCONNECT IT DO NOT ALLOW THE WIRES TO FALL BACK INTO THE WALL ATTACH SUBBASE TO WALL 1 Remo...

Page 4: ...vAC 120vAC Hot Neutral THERMOSTAT SYSTEM G W Figure 6 Typical Wiring Diagram for Cool Only 3 Wire Single Transformer Systems 6 Fan Relay Cooling System RH TRANSFORMER G RC 6 MV Y W RH Thermostat Termi...

Page 5: ...MV 24vAC 120vAC Hot Neutral THERMOSTAT SYSTEM G W HEATING TRANSFORMER 6 24vAC 120vAC Hot Neutral COOLING TRANSFORMER Cooling System Fan Relay Heating System RC G RC 6 MV Y W RH Thermostat Terminal Con...

Page 6: ...stat may occur if force is used CAUTION ENGAGE TWO LOWER GUIDES PIVOT UP Figure 13 Attaching thermostat to subbase SYSTEM CONFIGURATION A SET GROUP A OPTION SWITCHES ANY TIME GROUP B OPTION SWITCHES A...

Page 7: ...h 2 OFF Switch 3 see step B5 ON 1 2 3 Switch 1 OFF Switch 2 ON Switch 3 see step B5 ON 1 2 3 Switch 1 ON Switch 2 ON Switch 3 see step B5 2 Press FAN ON AUTO until FAN ON is displayed The blower shoul...

Page 8: ...e Product F O B Seller sfactory orSeller sissuanceofacreditintheamount of the purchase price of such Product for resale as described below Seller shall have the option of requiring the return of any d...