White Rodgers 11D82 Installation Instructions Download Page 2

2

All wiring should be done in accordance with local and national electrical codes and ordinances.

WIRING

11D06 .................... OPEN ON RISE

11D37 .................... CLOSE ON RISE

11D82 .................... S.P.D.T.

RED

WHITE

BLUE

COMMON

CLOSE ON RISE
OF TEMPERATURE

OPEN ON RISE
OF TEMPERATURE

SETTING THE CONTROL

CONTROLS WITH ADJUSTABLE DIFFERENTIAL

1.

Insert a screwdriver in the centre slot and turn the dial until
the right hand indicator “B” points to the lowest temperature
of the cycle.

2.

Turn the differential adjusting screw “C” until the left hand
indicator “D” points to the highest temperature of the cycle.

The left-hand indicator points to the temperature at which the
contacts open on high limit and low limit applications. On
circulator applications, 
 the left-hand indicator points to the
temperature at which the circulator will start.

On combination low limit and circulator applications,  the
left-hand indicator points to the temperature at which the low
limit stops the burner and permits the circulator to run.

CONTROLS WITH FIXED DIFFERENTIAL

Insert a screwdriver in centre slot “A” and turn the dial until the
fixed indicator “B” points to the highest desired temperature of
the cycle.

The fixed indicator points to the temperature at which the
contacts open on high limit  and  low limit applications. On
circulator applications, 
the fixed indicator points to the tem-
perature at which the circulator will start.

On combination low limit and circulator applications,  the
fixed indicator points to the temperature at which the low limit
stops the burner and permits the circulator to run.

“B” FIXED

INDICATOR

“A” ADJUSTING

SLOT

“B” FIXED INDICATOR

“C” DIFFERENTIAL

ADJUSTING SCREW

“D” MOVABLE INDICATOR

“A” ADJUSTING

SLOT

Well No.

Description

A

B

C

89-0211

1/2" Std. Shank

1-13/16"

3"

3-5/16"

89-0212

1/2" Std. Ext. Shank

3-5/16"

3"

3-5/16"

89-0213

3/4" Std. Shank

1-13/16"

3"

3-5/16"

89-0214

3/4" Std. Ext. Shank

3-5/16"

3"

3-5/16"

89-0215

3/4" Extra Ext. Shank

4-13/16"

3"

3-5/16"

 A 

 B 

 C 

Order wells and heat conductive grease No. 145-0163 separately.

SERVICING

RETAINER CLIP

IMMERSION WELL

CAPILLARY

RETAINER CLIP

Reviews: