21759-6-0608
Page 17
MAXIMUM HORIZONTAL
RUN WITH NO VERTICAL
RISE AND 90° ELBOW
MAXIMUM HORIZONTAL
RUN WITH MINIMUM
VERTICAL RISE AND
90° ELBOW
minimum
Figure 25
Figure 24
MINIMUM HOLE LOCATION DIMENSIONS FOR
THROUGH THE WALL HORIZONTAL INSTALLATIONS
WITH 90 DEGREE ELBOW OFF TOP OF FIREPLACE
Positioning the Fireplace
Determine the exact position of the appliance so the direct vent
termination will be centered (if possible) between two (2) studs. This
will avoid any extra framing. All vent kit pipes should be assembled
on the unit after the unit is moved into the final position.
Cutting the Hole (Figures 23)
After the fireplace has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This hole
must be 12" (305mm) high x 10" (254mm) wide with its center line
determined by the amount of vertical rise and horizontal run of the
termination.
See Figure 23.
When locating the hole it must be noted
that the bottom of the cap must be 12" (305mm) above the ground
level, and top of the cap must be no less than 18" (457mm) below
a combustible projection, and no closer than 9" (229mm) to any
wall running parallel to vent termination.
See Figure 24.
A
CENTER OF
ELBOW
STRAIGHT
OUT
(MINIMUM)
2
30
FIREPLACE
SERIES
HARD ELBOW DIMENSIONS
"A"
"B"
"C"
DVP42FP
43-1/2"
(1105mm)
5"
(127mm)
7"
(178mm)
DVP48FP
43-1/2"
(1105mm)
5"
(127mm)
7"
(178mm)
FIREPLACE
SERIES
FLEX PIPE 90 DEGREE BEND
"A"
"B"
"C"
DVP42FP
46"
(1143mm)
5"
(127mm)
7"
(178mm)
DVP48FP
46"
(1143mm)
5"
(127mm)
7"
(178mm)
Figure 23