![White Knight Heateflex Aquarius Owner'S Manual Download Page 7](http://html.mh-extra.com/html/white-knight/heateflex-aquarius/heateflex-aquarius_owners-manual_976071007.webp)
Copyright © 2020 White Knight Fluid Handling | A Graco company
P: 626.599.8566 |
|
https://wkfluidhandling.com
Aquarius DIW Heaters Owner’s Manual
Ver. 1.0.0 | 29 Apr 2020 | P. 5
Subject to change without notice
5. Aquarius
®
systems are tested at “
Process Temperature Set Point
” parameter set
below the maximum temperature possible and 1 gpm DIW flow. This will test the
performance of the controller.
a. The unit is allowed to operate with the controller “
Process Temperature Set Point
”
set to a value below the maximum temperature possible and flow set to 1 GPM.
b. If the temperature is not stable, confirm that the controller’s parameters are set to
factory settings shown in the user’s manual. If further controller tuning is required,
see the TROUBLESHOOTING GUIDE.
6. Aquarius
®
systems pass operational tests of the following safety interlocks or alarms:
a.
Components
: Aquarius
®
components are thoroughly checked for functionality,
which includes the Safety Relay(CON2), Door Interlock, EMO (Emergency Off), SCR
(Silicon Controlled Rectifier), Safety PLC, High Limit T/C Monitoring, Liquid Level,
Thermal Cut-Off Sensor, Leak Sensors (Optional), GFCI, and Current Transformer.
b.
Flow Sensor
: The system flow rate is indicated by the FLOW RATE value readout on
the
System Status
screen.
i) Modify the current “
Low Flow Alarm Set Point
” located on the
System Set Up ►
Alarm Set Points
screen.
ii) Set the
Low Flow Alarm Set Point
” value to just above the
FLOW RATE
reading
on the
System Status
screen. The Low Flow Alarm will trigger and the controller
will disable the heaters and send the unit into STANDBY mode.
iii) Return the Low Flow Alarm Set Point” to the original setting.
c.
Pressure Sensor
: The system pressure is indicated by the PRESSURE value
readout on the System Status screen.
i) Modify the current “
High Pressure Alarm Set Point
” located on the
System Set
Up ► Alarm Set Points
screen.
ii) Set the “
High Pressure Alarm Set Point
” value to just below the
PRESSURE
reading on the System Status screen. The
High Pressure Alarm
will trigger and
the controller should disable the heaters and send the unit into
STANDBY
mode.
iii) Return the “
High Pressure Alarm Set Point
” to the original setting.
d.
Output Thermocouple
: The process (output) temperature is indicated by the
PROCESS TEMPERATURE
value readout on the System Status screen.
i) Modify the current “
High Temperature Alarm Set Point
” located on the
System
Set Up ► Alarm Set Points
screen.
ii) Set the “
High Temperature Alarm Set Point
” value to just below the
PROCESS
TEMPERATURE
reading on the
System Status
screen. The
High Temperature
Alarm
will trigger and the controller will disable the heaters and send the unit into
STANDBY
mode.
iii) Return the “
High Temperature Alarm Set Point
” to the original setting.