TROUBLESHOOTING GUIDE

Unit has ice forming on the evaporator 

Possible cause

Solution

Evaporator coil is dirty

Clean the coil with a vacuum. If coil is very dirty, use a spray bottle 
with a small amount of liquid dish detergent or coil cleaner. Spray coil, 

There is something blocking the supply and/or return air

Remove blockage

The evaporator fan is not turning on

Call a service tech to troubleshoot

The unit has not gone through an Anti-Frost Cycle yet

Check the coil for surface ice. Melt with blow drier until coil is warm to 
the touch. Soak up water with a towel.

The unit continues to ice

Observe ice formation pattern. If only part way up the coil face, unit 
could be low on refrigerant. If all the way up, the coil may be dirty or 

Unit does not run/power up 

Possible cause

Solution

Unit is not plugged in

Make sure the unit is plugged into an outlet

Power switch not on

Turn unit on by pressing the power button on the control

Line voltage is incorrect rating for unit

Check line voltage to make sure there is 110V-120V

Bottle at setpoint

Lower setpoint

Thermostat not calling for cooling

Lower setpoint

Power select switch in wrong position

See page 11 for correct switch position

Faulty thermostat or wiring

Call Customer Service at 1-800-343-9463

Cellar temperature is too warm

Possible cause

Solution

The temperature of the room to which the unit  
exhausts exceeds 110°F

Intake temperature needs to drop below 110°F

The unit is undersized for the cellar

Order correct size unit

There is something blocking the supply and/or return air on 
evaporator or condenser side of the unit
Unit is mounted too low in the cellar

Relocate unit so the distance from the ceiling and top of the unit or 
cold air supply duct is no more than 18”

One or more of the fans is not turning on

Call Customer Service at 1-800-343-9463

Compressor is not turning on

Call Customer Service at 1-800-343-9463

Compressor keeps cycling on overload
Poor seal around door

Make sure there are no air gaps around the door. If door seal is 
damaged, replace it.

Setpoint too high

Lower the setpoint

Evaporator coil is frosted or iced up

Observe ice formation pattern. If only part way up the coil face, unit could 
be low on refrigerant. If so, call Customer Service at 1-800-343-9463.

System runs constantly

Possible cause

Solution

Leaky door seal or poorly insulated cellar

Fix leaky door seal and insulate cellar in accordance with this manual 
(page 9)