
LINE SET PIPING DIAGRAMS
These are two
suggested
examples
for running the line set from the coil
to the condensing unit.
Example
1
is specifically applicable when
the system is installed with the
condensing unit below or leveled to
the coil.
Example
2 is applicable
when the system is installed with
the condensing unit at a
higher elevation than the
coil.
Reverse oil
return bend
Oil saving bend
Suction
Line
Evaporator
Coil
Within 16' of height
Downward slope
pitched toward
compressor
1
/
2
" / 10'
Liquid
Line
Maximum height difference
betwen condenser and
evaporator should not
exceed 50'
Cassette Unit
Suction
line
Liquid
Line
Oil return bend
Oil saving bend
Evaporator coil
50'
Example
1
Example
2
Cassette Unit
Page 30
08/04/21