AC output cable:
Pull the AC output cable through the cable gland and connect it
to the AC output connector. Connections are marked as “L1”-line,
“L2”-line, “N”-neutral and “Pe”-earth. Make sure it is tightly
screwed. Choose the proper output terminals according to the table
found on the connector PCB inside the connection compartment.
connection 230V output
connection 110V
single phase output
connection 110V
dual phase output
WARNING:
Check the AC input and AC output
after connection. Wrong or loose connections will
damage the WP-GI permanently.
tprotective earth
Depending on local regulations and usage of the safety isolation
transformer, connect the output Pe to output N using the wire
jumper 2.5mm2 to polarize the system. This can be done on the
location above the AC output connector.
If the secondary Pe may not float (e.g. when the boat is in dry-
dock or on a land based vehicle), the INPUT side Pe can be con-
nected to the oUTPUT side Pe using the 2.5mm2 wire jumper.
In the standard configuration, the shielding of the transformer is
connected to the secondary AC side (output) of the WP-GI and
the casing. Upon request, the shielding can be connected to the
primary AC (input) side without connection to the casing. This is
not standard and requires opening of the casing.
optional GFcI or circuit breaker in front cover
If the optional front cover for holding a two or four pole DIN rail
mounted device is installed, the appropriate wiring must be con-
nected to the device and the device to the AC input or AC output
terminal of the WP-GI. Connect according to local regulations! To
mount the option:
1. Put breaker devices on DIN rail
2. Connect wiring
3. Use bolts to mount the DIN rail to the cover.
4. Place the cover
2.6 operation
The WP-GI has no buttons to operate. When the AC input voltage
is connected to grid or shore power, the softstart will energize the
transformer (PRoTeCT LeD will light up) and then the AC output is
switched on. The red PRoTeCT LeD will switch off and the green
PoWeR LeD will light up.
The green oPeRATIoN LeD will remain on as long as there is AC
output power. If any failure is detected during operation, the output
will be switched off and the red PRoTeCT LeD will be lit.
2.7 trouble shooting
2.8 ce declaration of conformity
Product: WP-GI Whisper Power Galvanic Isolation Transformer.
WhisperPower guarantees that the unit complies with the relevant
standards.
2.9 specification
[ zelfde tabel als in de datasheet]
20120920UserManual WP-GI
Problem
Possible cause
Solution
No output voltage
No input voltage
Check all input
connections and
breakers upstream
Wrong input voltage
Check voltage and
settings
The PROTECT
LED burns
Over temperature
Check ambient
temperature
Check if ventilation
is blocked
Wrong input voltage
Check that continuous
load is <3600W
Check if fans are working
Check input voltage and
settings
When AC input
is connected,
the input circuit
breaker trips
Load on output too high
Check current rating
of circuit breaker on
input and adapt load
accordingly.
Softstart does not work
Fuses F1A are blown.
Repair by skilled
technician (requires
opening of the casing)
AC Connector
sparks or has
blackened
Wire ends in terminals
not properly tightened
Replace wiring,
verify connector,
tighten correctly
article nr. 60110100
Wp-GI 3600 Galvanic Isolation-transformer
Application
Galvanic Isolation Transformer for safety and protection of galvanic corrosion
Transformer type
2 winding toroidal isolation transformer
Construction method
Special vibration isolated mounting of transformer
Cooling method
Temperature controlled gradually regulated forced air cooling above 60° transformer core
Winding Data
Rated power
3.6kVA
Rated voltage
230V / 110V
Rated frequency
50hz / 60hz
Nominal current
16A / 32A
Inrush current
Softstart included <4A
Tappings
Prim/sec. mid-point (110vac)
Material winding
Copper
Temperature rise class
Class F 100 K
Insulation class
Class h 180 C
Insulation level
Class AC3
Impedance
Secundary less than 3.0% at 3,6kVA
General
No load consumption
21 W
Full load efficiency
>95%
Ambient operating temperature
-10°C .. +45°C, derating to 80°C
Storage temperature
-25°C to 85°C
operating humidity
95% max, non-condensing
Audible noise
<40.0 dB(A); <50dB(A) with forced cooling
Local user interface
None
Protections
overcurrent, short circuit
Not included, external breaker(s) required according to local regulations
Temperature protection
Automatic switch off if transformer core > 120°C
overvoltage protection
Softstart is protected for overvoltage using fuse
earthscreen between windings
Compliant to AByC, can carry full fault current
Safety
Standards IeC 60079, IeC 60726
Mechanical
Protection degree
IP21
Connections input/output
6mm
2
max.
Cable gland entry
22mm
Dimensions (hxWxD)
510x330x150
Mounting holes
M10
Weight
25.0 kg
enclosure construction
Steel sheet metal
Surface finishing
RAL9003 structure powder coating
Optional:
It is recommended to install a GFCI/RCD in the AC input line.
article nr. 000000000
Replacement cover WP-GI with DIN-rail mount
article nr. 000000000
Ground fault circuit interrupter (GFCI/RCD) and circuit breaker 20A
article nr. 000000000
Ground fault circuit interrupter (GFCI/RCD) and circuit breaker 40A
C
2
3
1
4
B
A
D
E
Material <not specified>
Material:
NAME
11-7-2012
J.R.
FINISH:
DRAWING:
TOLERANCE PRINCIPE ISO 8015
21-9-2012
Weight: 8.17 gram
-
SHEET 1 OF 1
SCALE:1:1
ARTICLE NO.
TITLE:
REVISION
DO NOT SCALE DRAWING
STATUS:
DATE
SIGNATURE
UNLESS OTHERWISE SPECIFIED:
CHAMFER SHARP EDGES
GENERAL TOLERANCE
NEN ISO 2768-m
FORM AND PLACE TOLERANCES
NEN-ISO 1101
WELDING SYMBOL NEN EN 22553
ROUGHNESS ACC. to NEN3634
CHK'D
DRAWN
Phoenix
PRINTED
21-9-2012
M.B.
SHEET FORMAT:
PROJECTION : THIRD ANGLE UNITS : mm
A4
C
2
3
1
4
B
A
D
E
Material <not specified>
Material:
NAME
11-7-2012
J.R.
FINISH:
DRAWING:
TOLERANCE PRINCIPE ISO 8015
21-9-2012
Weight: 8.17 gram
-
SHEET 1 OF 1
SCALE:1:1
ARTICLE NO.
TITLE:
REVISION
DO NOT SCALE DRAWING
STATUS:
DATE
SIGNATURE
UNLESS OTHERWISE SPECIFIED:
CHAMFER SHARP EDGES
GENERAL TOLERANCE
NEN ISO 2768-m
FORM AND PLACE TOLERANCES
NEN-ISO 1101
WELDING SYMBOL NEN EN 22553
ROUGHNESS ACC. to NEN3634
CHK'D
DRAWN
Phoenix
PRINTED
21-9-2012
M.B.
SHEET FORMAT:
PROJECTION : THIRD ANGLE UNITS : mm
A4
n
pe
l1
C
2
3
1
4
B
A
D
E
Material <not specified>
Material:
NAME
11-7-2012
J.R.
FINISH:
DRAWING:
TOLERANCE PRINCIPE ISO 8015
21-9-2012
Weight: 8.17 gram
-
SHEET 1 OF 1
SCALE:1:1
ARTICLE NO.
TITLE:
REVISION
DO NOT SCALE DRAWING
STATUS:
DATE
SIGNATURE
UNLESS OTHERWISE SPECIFIED:
CHAMFER SHARP EDGES
GENERAL TOLERANCE
NEN ISO 2768-m
FORM AND PLACE TOLERANCES
NEN-ISO 1101
WELDING SYMBOL NEN EN 22553
ROUGHNESS ACC. to NEN3634
CHK'D
DRAWN
Phoenix
PRINTED
21-9-2012
M.B.
SHEET FORMAT:
PROJECTION : THIRD ANGLE UNITS : mm
A4
C
2
3
1
4
B
A
D
E
Material <not specified>
Material:
NAME
11-7-2012
J.R.
FINISH:
DRAWING:
TOLERANCE PRINCIPE ISO 8015
21-9-2012
Weight: 8.17 gram
-
SHEET 1 OF 1
SCALE:1:1
ARTICLE NO.
TITLE:
REVISION
DO NOT SCALE DRAWING
STATUS:
DATE
SIGNATURE
UNLESS OTHERWISE SPECIFIED:
CHAMFER SHARP EDGES
GENERAL TOLERANCE
NEN ISO 2768-m
FORM AND PLACE TOLERANCES
NEN-ISO 1101
WELDING SYMBOL NEN EN 22553
ROUGHNESS ACC. to NEN3634
CHK'D
DRAWN
Phoenix
PRINTED
21-9-2012
M.B.
SHEET FORMAT:
PROJECTION : THIRD ANGLE UNITS : mm
A4
n
pe
l2
C
2
3
1
4
B
A
D
E
Material <not specified>
Material:
NAME
11-7-2012
J.R.
FINISH:
DRAWING:
TOLERANCE PRINCIPE ISO 8015
21-9-2012
Weight: 8.17 gram
-
SHEET 1 OF 1
SCALE:1:1
ARTICLE NO.
TITLE:
REVISION
DO NOT SCALE DRAWING
STATUS:
DATE
SIGNATURE
UNLESS OTHERWISE SPECIFIED:
CHAMFER SHARP EDGES
GENERAL TOLERANCE
NEN ISO 2768-m
FORM AND PLACE TOLERANCES
NEN-ISO 1101
WELDING SYMBOL NEN EN 22553
ROUGHNESS ACC. to NEN3634
CHK'D
DRAWN
Phoenix
PRINTED
21-9-2012
M.B.
SHEET FORMAT:
PROJECTION : THIRD ANGLE UNITS : mm
A4
C
2
3
1
4
B
A
D
E
Material <not specified>
Material:
NAME
11-7-2012
J.R.
FINISH:
DRAWING:
TOLERANCE PRINCIPE ISO 8015
21-9-2012
Weight: 8.17 gram
-
SHEET 1 OF 1
SCALE:1:1
ARTICLE NO.
TITLE:
REVISION
DO NOT SCALE DRAWING
STATUS:
DATE
SIGNATURE
UNLESS OTHERWISE SPECIFIED:
CHAMFER SHARP EDGES
GENERAL TOLERANCE
NEN ISO 2768-m
FORM AND PLACE TOLERANCES
NEN-ISO 1101
WELDING SYMBOL NEN EN 22553
ROUGHNESS ACC. to NEN3634
CHK'D
DRAWN
Phoenix
PRINTED
21-9-2012
M.B.
SHEET FORMAT:
PROJECTION : THIRD ANGLE UNITS : mm
A4
n
l2
pe
l1
Galvanic Isolation-transformer
WP-GI
Whisper Power Galvanic
Isolation-transformer
Transformer for safety and hull protection to prevent corrosion
115
230VAC
230VAC
SHORE
PE
N
L
PE
N
L
SHIP
115
115
115
Power
Protect