background image

10

SEQUENCE OF OPERATION

Cooling (cooling only or heat pump)

When the thermostat calls for cooling, the circuit between R and 
G is completed, and the blower relay is energized. The Normally 
Open contacts close, causing the indoor blower motor to 
operate. The circuit between R and Y is also completed; this 
circuit closes the contactor in the outdoor unit starting the 
compressor and outdoor fan motor. Circuit R and O energizes 
the reversing valve, switching it to the cooling position. (The 
reversing valve remains energized as long as selector switch is 
in the COOL position.)

Heating (electric heat only)

When the thermostat calls for heat, the circuit between R and W 
is completed, and the heat sequencer relay is energized. A time 
delay follows before the heating elements and the indoor blower 
motor come on. Units with a second heat sequencer relay can be 
connected with the first sequencer to W on the thermostat 
subbase or connected to a second stage on the subbase.

Heating (heat pump)

When the thermostat calls for heat, the circuits between R and Y 
and R and G are completed. Circuit R-Y energizes the contactor 
starting the outdoor fan motor and the compressor. Circuit R 
and G energizes the blower relay starting the indoor blower 
motor.

If the room temperature should continue to fall, the circuit 
between R and W 1 is completed by the second stage heat room 
thermostat. Circuit R-W 1 energizes a heat sequencer relay. The 
completed circuit will energize supplemental electric heat (if 
available). Units with a second heat sequencer relay can be 
connected with the first sequencer to W 1 on the thermostat or 
connected to a second heating stage W 2 on the thermostat 
subbase.

Variable Speed Features

Some WMB air handlers are equipped with a variable speed 
motor and will deliver a constant airflow within a wide range of 
external static pressures. The variable speed blower offers the 
following comfort features:

Start

When called into operation, the variable speed motor will slowly 
ramp up to normal operating speed. This eliminates the noise 
and discomfort that results caused by the initial blast of air 
encountered with standard air handlers. It can take up to 
7.5 minutes to reach normal operating speed.

Continuous Blower Operation

The comfort level of the living space can be enhanced when 
using this feature by allowing continuous circulation of air in 
between calls for cooling or heating. The circulation of air 
between calls for cooling or heating occurs at 50% of the 
normal airflow rate (350 CFM minimum).

Reduced Airflow Operation

For situations where humidity control is a problem, the variable 
speed motor can be enabled to operate at a 10% reduction in 
the normal airflow rate under the control of a humidistat. This 
can be achieved by connecting to a standard humidity control 
that is normally closed and opens on humidity rise.

The Control Board

The control board regulates airflow selection and features LED 
indicators that display operating mode, humidity control, and 
airflow CFM. The red LED flashes once for each 100 CFM. For 
example, if the operating CFM is 1200, the CFM LED will flash 
12 times, then pause before repeating the 12-flash pattern.

Thermostat signals for emergency heat (EM), optional auxiliary 
heat (W1), reversing valve (O), compressor (Y1), and blower (G) 
are all indicated by lit LED’s on this board.

This model is designed for use with heat pumps as well as air 
conditioning systems. The control board needs to sense a signal 
on the “O” thermostat wire in order to use cooling delay timing. 
For a straight air conditioning system, connect the “O” wire to the 
thermostat “R” wire.

AIR HANDLER MAINTENANCE

IMPORTANT: Do not operate system without a filter. A filter is 
required to protect the coil, blower, and internal parts from 
excessive dirt and dust. See “Installation Configurations” for the 
location of the filter in the unit cabinet and the service panel 
giving access to unit filter. The filter is placed in the supply air 
return duct by the installer.

Inspect air filters at least once a month and replace or clean 
as required. Dirty filters are the most common cause of 
inadequate heating or cooling performance.

Replace disposable filters. Cleanable filters can be cleaned 
by soaking in mild detergent and rinsing with cold water.

Install new/clean filters with the arrows on the side pointing in 
the direction of airflow.

Do not replace a cleanable (high velocity) filter with a 
disposable (low velocity) filter unless return air system is 
properly sized for it.

If water should start coming from the secondary drain line, a 
problem exists which should be investigated and corrected. 
Contact a qualified person.

ASSISTANCE OR SERVICE

If you need further assistance, you can write to the below 
address with any questions or concerns: 

Whirlpool

®

 Home Cooling and Heating

14610 Breakers Drive
Jacksonville, FL  32258

Please include a daytime phone number in your correspondence.

Accessories

To order accessories, contact your Whirlpool

©

 Home Cooling and 

Heating dealer.

Electric Heat Kits 

Refer to the accessory kit label on the front panel of the air 
handler for electric heat kit accessory options and applications.

Summary of Contents for WMB

Page 1: ...ANDLER SAFETY 1 INSTALLATION REQUIREMENTS 1 Tools and Parts 2 Location Requirements 2 Installation Configurations 3 Electrical Requirements 3 Ductwork Requirements 4 INSTALLATION INSTRUCTIONS 4 Inspect Shipment 4 Install Ductwork 4 Install Filter 4 Make Electrical Connections 5 Complete Installation 7 SEQUENCE OF OPERATION 10 AIR HANDLER MAINTENANCE 10 ASSISTANCE OR SERVICE 10 Accessories 10 WARRA...

Page 2: ... very humid space If installed in an unconditioned space sealant should be applied around the electrical wires refrigerant tubing and condensate lines where they enter the cabinet Electrical wires should be sealed on the inside where they exit the conduit opening Sealant is required to prevent air leakage into and condensate from forming inside the air handler control box and on electrical control...

Page 3: ...of major components such as the blower assembly Provide enough clearance between the suspension rods and the air handler to allow removal of the blower access panel Installation Configuration Options NOTE Typical installations with optional WEM modular evaporator coil are shown ElectricalRequirements NOTES Use copper conductors only All field wiring must be done in accordance with National Electri...

Page 4: ...o not install the unit as your claim may be denied InstallDuctwork IMPORTANT Install ductwork in accordance with NFPA 90B Standard for the Installation of Warm Air eating and Air Conditioning Sytems latest edition and any local codes Connect supply air duct to the flange on top of the unit If an isolation connector is used it must be non flammable A return air duct system is recommended If the uni...

Page 5: ... transformer to the 208 Volt terminal on the transformer See the appropriate wiring diagram for your model WARNING Electrical Shock Hazard Disconnect all power supplies before servicing Replace all parts and panels before operating Failure to do so can result in death or electrical shock WARNING Electrical Shock Hazard Electrically ground air handler Connect ground wire to ground terminal marked G...

Page 6: ...t N E C Class 2 Plug Pin Location Amp 350781 1 6 Pin Cap TD Time Delay Optional TR Transformer BWR Blower Relay MTR Blower Motor CAP Motor Capacitor GND Ground Connection BK Black W White R Red G Green BU Blue Y Yellow BWR 3 6 4 1 5 2 18 BK 12 BK 12 BK 12 BK 12 BK 12 BK 12 BK 12 BK 12 BK 12 Y 12 Y LS3 LS4 12 Y 12 Y SEQ2 2nd Stage 1st Stage LS1 LS2 SEQ1 CB2 L1B L2B L2A L1A GND CB1 GND 14 BK 14 Y 14...

Page 7: ...an outdoor condensing unit or heat pump that matches the maximum cooling capacity rating of the air handler If the outdoor condensing unit is smaller than the maximum cooling capacity rating for the air handler the cooling blower speed may need to be changed Refer to Blower Performance Chart PSC Motor IMPORTANT The cooling blower speed must be set to provide a minimum of 350 CFM airflow per ton 12...

Page 8: ...nce Chart Variable Speed Motor NOTE If using a humidistat the dehumidify resistor located on the bottom right of the control board must be removed to enable it See Control Board Taps and Dehumidify Resistor The HUM terminal on the board must be connected to the Normally Closed contact of the humidistat so that the board senses an open circuit on high humidity If a humidistat is used the dehumidify...

Page 9: ...556 551 562 545 523 517 C 514 502 490 484 465 458 437 426 D 466 445 437 412 403 392 386 382 WMB48VB 1A Y1 A 1 134 1 123 1 123 1 113 1 102 1 091 1 079 1 074 B 991 972 956 949 937 923 909 909 C 847 826 807 793 778 753 736 712 D 687 664 646 619 612 581 557 531 Y1 Y2 A 1 676 1 656 1 635 1 624 1 613 1 608 1 608 1 598 B 1 435 1 404 1 398 1 398 1 392 1 380 1 375 1 362 C 1 234 1 220 1 212 1 205 1 197 1 18...

Page 10: ...occurs at 50 of the normal airflow rate 350 CFM minimum Reduced Airflow Operation For situations where humidity control is a problem the variable speed motor can be enabled to operate at a 10 reduction in the normal airflow rate under the control of a humidistat This can be achieved by connecting to a standard humidity control that is normally closed and opens on humidity rise The Control Board Th...

Page 11: ...11 ...

Page 12: ...late Dealer name____________________________________________________ Address ________________________________________________________ Phone number__________________________________________________ Model number __________________________________________________ Serial number __________________________________________________ Installation date ________________________________________________ 0650329...

Reviews: