background image

TECH SHEET - DO NOT DISCARD

PAGE 3

FOR SERVICE TECHNICIAN’S USE ONLY

PART NO. W10156037A

DISPLAY

DESCRIPTION

EXPLANATION / RECOMMENDED PROCEDURE

PF

Power
Failure

PF

flashes to indicate that a power failure

occurred while the dryer was running. Press Start
to continue the cycle, or press Pause/Cancel to
clear the display.

L2

Low/No Line

Voltage

L2

flashes if low line voltage (less than 50V) is

detected at installation.

Check to see if a household fuse has blown or
a circuit breaker has tripped.

Confirm the power cord is properly installed
and plugged into the power outlet.

Check the relay connections on the machine
control electronics. See TEST #4, page 6.

AF

Restricted

Air Flow

Condition

AF

flashes if a restricted air flow condition exists.

Check to make sure the lint screen is clean, the
door seal is in place and the vent is not
obstructed.

F-0

1

Primary

Control

Failure

F-01

flashes when there is a primary control

failure. Replace the machine control electronics.
See Accessing & Removing the Electronic
Assemblies, page 9.

F-02

Keypad/

User Interface

Failure

F-02

flashes when there is a stuck button or user

interface mismatch. This fault code will ONLY
appear when in the diagnostic test mode. See
TEST #6, page 8.

F-22

Exhaust

Thermistor

Open

F-22

flashes if the exhaust thermistor is open.

See TEST #4a, page 6.

F-23

Exhaust

Thermistor

Shorted

F-23

flashes if the exhaust thermistor has

shorted. See TEST #4a, page 6.

F-24

Inlet

Thermistor

Open

F-24

flashes if the inlet thermistor is open.

This fault code will ONLY appear when in the
diagnostic test mode. See TEST #4a, page 6.

F-25

Inlet

Thermistor

Shorted

F-25

flashes if the inlet thermistor is shorted.

This fault code will ONLY appear when in the
diagnostic test mode. See TEST #4a, page 6.

F-26

Motor Drive

System Failure

F-26

flashes if there is a motor drive system

failure. See TEST #3, page 5.

F-28

Moisture

Sensor Open

F-28

flashes if the moisture sensor strip is open.

This fault code will ONLY appear when in the
diagnostic test mode. See TEST #5, page 7.

F-29

Moisture

Sensor

Shorted

F-29

flashes if the moisture sensor strip has

shorted. This fault code will ONLY appear when in
the diagnostic test mode. See TEST #5, page 7.

DISPLAY FAULT CODES

The fault codes below would be indicated when attempting to start a drying cycle
or after activating the diagnostic test mode.

PROBLEM

POSSIBLE CAUSE / TEST

NOTE:

Possible Cause/Tests MUST be performed

in the sequence shown for each problem.

WON’T POWER UP.

(No response when
buttons are pressed.)

1. Supply connections. See TEST #1, page 4.
2. Check harness connections.
3. User interface assembly. See TEST #6, page 8.

WON’T START CYCLE
WHEN START BUTTON
IS PRESSED.

1. If number display flashes, check to be sure the

door is completely shut, and press and hold down
Start for about 1 second.

2. See TEST #3, page 5.
3. See TEST #7, page 8.

WON’T SHUT OFF
WHEN EXPECTED.

1. Check Pause/Cancel button. See TEST #6,

page 8.

2. User interface assembly. See TEST #6, page 8.
3. Moisture sensor. See TEST #5, page 7.

CONTROL WON’T
ACCEPT SELECTIONS.

User interface assembly. See TEST #6, page 8.

WON’T HEAT.

1. Heater. See TEST #4, page 6.
2. Check harness connections.
3. Check installation.

HEATS IN AIR CYCLE.

Heater. See TEST #4, page 6.

SHUTS OFF BEFORE
CLOTHES ARE DRY.

1. Check the dryness setting for Automatic Cycles.
2. Check for full lint screen.
3. Check for clogged vent.
4. Moisture sensor. See TEST #5, page 7.
5. Dryness adjust. See Adjusting Customer-Focused

Drying Modes, page 8.

TROUBLESHOOTING GUIDE

Some tests will require accessing components. See figure 2, page 4 for component
locations.

Steam Model

2. Motor +  water valve.

Flash “Delicate” LED.

3.

Motor +  water valve + drum
light.

Flash “Drum Light” LED.

4.

No loads on (motor +  water
valve).

Flash “Normal” LED.

5. Repeat using same button.

Start sequence again at 1.

DEACTIVATING THE MANUAL LOAD TEST

Press the Pause/Cancel button to exit this mode.

DISPLAY

DESCRIPTION

EXPLANATION / RECOMMENDED PROCEDURE

F-30

Restricted

Air Flow

Condition

F-30

flashes if a restricted air flow condition

exists. This fault code will ONLY appear when in
the diagnostic test mode. Check to make sure the
lint screen is clean, the door seal is in place and
the vent is not obstructed.

F-50

Water Valve

Failure

F-50

flashes if no voltage is detected at the water

valve relay. Check that the wires are plugged in on
the valve and at the relay on the machine control
electronics. See TEST #8, page 8. This fault code
appears ONLY when in the diagnostic test mode.

Summary of Contents for WED6600VU0

Page 1: ...or 5 seconds with 88 showing in the Estimated Time Remaining two digit display DIAGNOSTIC Unsuccessful Entry If entry into diagnostic mode is unsuccessful press the Pause Cancel button twice then press the Power button If indicators come on try to use a different button than was used to activate the diagnostic test mode If that button fails to enter the diagnostic mode something is faulty and it i...

Page 2: ...lay the line voltage currently being measured by the machine control After all saved fault codes have been displayed press the End of Cycle Signal button The last 2 digits of the voltage value will be displayed on the dual 7 segment display A Dryness modifier LED will also be illuminated to indicate the voltage range corresponding to the number displayed The Dryness LEDs relate to specific voltage...

Page 3: ...LY appear when in the diagnostic test mode See TEST 5 page 7 DISPLAY FAULT CODES The fault codes below would be indicated when attempting to start a drying cycle or after activating the diagnostic test mode PROBLEM POSSIBLE CAUSE TEST NOTE Possible Cause Tests MUST be performed in the sequence shown for each problem WON T POWER UP No response when buttons are pressed 1 Supply connections See TEST ...

Page 4: ... at the machine control Go to TEST 6 page 8 If the drum light fails to illuminate do not assume the machine control electronics needs replacement Several conditions may cause the drum light not to illuminate including a bad bulb If the drum light does not illuminate go to TEST 1 at left See Removing the Back Panel page 11 to access Thermal Cut off Drum Light Assembly Water Nozzle Steam Models Inle...

Page 5: ...DING RESISTANCE Ω CONTACT POINTS OF MEASUREMENT MAIN 1 4 2 6 Blue wire in back at pin 4 and bare copper wire terminal removed from pin 5 of black drive motor switch START 1 4 2 8 Blue wire in back at pin 4 and bare copper wire terminal on pin 3 of black drive motor switch If the resistance at the motor is correct there is an open circuit between the motor and machine control electronics Check for ...

Page 6: ... resistance is greater than 20 kΩ replace the exhaust thermistor TEST 4a Thermistors EXHAUST THERMISTOR The machine control electronics monitors the exhaust temperature using the exhaust thermistor and cycles the heater relay on and off to maintain the desired temperature Begin with an empty dryer and a clean lint screen 1 Plug in dryer or reconnect power 2 Start the Timed Dry cycle 3 If after 60 ...

Page 7: ...isture Sensor NOTE This test is started with the machine completely assembled This test is performed when an automatic cycle stops too soon or runs much longer than expected NOTE Dryer will shut down automatically after 2 hours The following items are part of this system Harness connection Metal sensor strips Machine control electronics See ESD information page 1 1 Activate the diagnostic test mod...

Page 8: ...g dryer or disconnect power Check that the wires between the door switch and machine control electronics are connected See figure 11 for switch location and see Removing the Front Panel Drum Assembly page 9 If the connections are OK replace the door switch assembly and retest If the door switch assembly has been replaced and dryer still does not start replace the machine control electronics TEST 8...

Page 9: ...disconnect power 2 Remove the lint screen 3 Remove the two screws holding the lint screen duct to the top 4 Open the door 5 Push on the retaining clips located under top of dryer on the right and left side using a flat object such as a putty knife See figure 13 6 Slowly rotate top backwards and lean against wall or support with a prop rod 7 Disconnect the door switch wire harness located on the ri...

Page 10: ...ert NOTE When reconnecting wire connections be sure to route the user interface wires beneath the retainer clips on the user interface back cover REMOVING THE BACK PANEL 1 Unplug dryer or disconnect power 2 Remove the cover plate screw and cover plate See figure 18 3 Remove the nine rear screws from the back panel for steam models remove the additional screw near the valve opening at the bottom 4 ...

Page 11: ...SENSOR MOVS Y R Y R BK NEUTRAL TERMINAL LINKED TO CABINET W MACHINE CONTROL ELECTRONICS P4 2 P4 1 R R INLET THERMISTOR 50 kΩ INLET TEMP INLET TEMP RTN BU P8 1 LAMP LOAD NC NO R W SINGLE ELEMENT MODEL R N O COM R W BK NC HIGH LIMIT THERMOSTAT 180 F 82 C HEATER 2700 W COM BK HEATER 2700 W R V P8 2 GND CENTRIFUGAL SWITCH 2M 1M 5M 6M 3M R LINE L2 W DOOR SWITCH W NEUTRAL N T BU BU W W P8 4 P8 3 NEUTRAL...

Page 12: ...BK N O R COM N O COM R VALVE RELAY L1 WIDE HEATER RELAY 1 HEATER V HEATER RTN BU NEUTRAL DOOR GND MOTOR MTR CS MOIST P8 4 T W P8 2 G Y P9 1 P8 5 BK W P4 4 P4 5 P4 3 R P4 6 P4 2 P4 1 R R R R W VALVE NC BU NO W 4M W 5M 3M 6M CENTRIFUGAL SWITCH 2M 1M GM G Y BK W R NC W R DRIVE MOTOR 1 3 H P NEUTRAL TERMINAL LINKED TO CABINET SENSOR Y R P13 1 P13 2 G Y SENSOR MOVS Y R Y R BK HIGH LIMIT THERMOSTAT 260 ...

Reviews: