background image

6

ELECTRIC DRYER POWER HOOKUP 

Electrical Requirements - U.S.A. Only

It is your responsi

b

ility

To contact a qualified electrical installer.

To be sure that the electrical connection is adequate and in 
conformance with the National Electrical Code, ANSI/NFPA 70-
latest edition and all local codes and ordinances. 

The National Electrical Code requires a 4-wire power supply 
connection for homes built after 1996, dryer circuits involved in 
remodeling after 1996, and all mobile home installations.

A copy of the above code standards can be obtained from: 
National Fire Protection Association, One Batterymarch Park, 
Quincy, MA 02269.

To supply the required 3 or 4 wire, single phase, 120/240 volt, 
60 Hz., AC only electrical supply (or 3 or 4 wire, 120/208 volt 
electrical supply, if specified on the serial/rating plate) on a 
separate 30-amp circuit, fused on both sides of the line. A time-
delay fuse or circuit breaker is recommended. Connect to an 
individual branch circuit. Do not have a fuse in the neutral or 
grounding circuit. 

Do not use an extension cord.

If codes permit and a separate ground wire is used, it is 
recommended that a qualified electrician determine that the 
ground path is adequate.

Electrical Connection

To properly install your dryer, you must determine the type of 
electrical connection you will be using and follow the instructions 
provided for it here.

This dryer is manufactured ready to install with a 3-wire electrical 
supply connection. The neutral ground conductor is 
permanently connected to the neutral conductor (white wire) 
within the dryer. If the dryer is installed with a 4-wire electrical 
supply connection, the neutral ground conductor must be 
removed from the external ground connector (green screw), and 
secured under the neutral terminal (center or white wire) of the 
terminal block. When the neutral ground conductor is secured 
under the neutral terminal (center or white wire) of the terminal 
block, the dryer cabinet is isolated from the neutral conductor.

If local codes do not permit the connection of a neutral ground 
wire to the neutral wire, see “Optional 3-wire connection” 
section. 

A 4-wire power supply connection must be used when the 
appliance is installed in a location where grounding through the 
neutral conductor is prohibited. 

G

rounding through the neutral is 

prohibited for (1) new branch-circuit installations, (2) mobile 
homes, (3) recreational vehicles, and (4) areas where local codes 
prohibit grounding through the neutral conductors.

If using a power supply cor

d

:

Use a UL listed power supply cord kit marked for use with clothes 
dryers. The kit should contain:

A UL listed 30-amp power supply cord, rated 120/240 volt 
minimum. The cord should be type SRD or SRDT and be at least 
4 ft (1.22 m) long. The wires that connect to the dryer must end 
in ring terminals or spade terminals with upturned ends.

A UL listed strain relief.

If your outlet looks like this:

4-wire receptacle 

 

(14-30R)

Then choose a 4-wire power supply cord 

 

with ring or spade terminals and UL listed strain 
relief. The 4-wire power supply cord, at least 4 ft 
(1.22 m) long, must have four 10-gauge copper 
wires and match a 4-wire receptacle of NEMA 
Type 14-30R. The ground wire (ground 
conductor) may be either green or bare. 

 

The neutral conductor must be identified 

 

by a white cover.

If your outlet looks like this:

3-wire receptacle 

 

(10-30R)

Then choose a 3-wire power supply cord with ring 
or spade terminals and UL listed strain relief. The 
3-wire power supply cord, at least 4 ft (1.22 m) 
long, must have three 10-gauge copper wires and 
match a 3-wire receptacle of NEMA Type 10-30R.

If connecting 

b

d

irect wire:

Power supply cable must match power supply (4-wire or 3-wire) 

 

and be:

Flexible armored cable or nonmetallic sheathed copper cable 
(with ground wire), protected with flexible metallic conduit. All 
current-carrying wires must be insulated.  

10-gauge solid copper wire (do not use aluminum) at least 

 

5 ft (1.52 m) long.

Summary of Contents for W10224585A

Page 1: ...24585A DRYER SAFETY You You can be killed or seriously injured if you don t immediately can be killed or seriously injured if you don t follow All safety messages will tell you what the potential hazard is tell you how to reduce the chance of injury and tell you what can happen if the instructions are not followed Your safety and the safety of others are very important We have provided many import...

Page 2: ... B C D E A Leveling legs 4 B Y connector C Short inlet hose D Inlet hose with right angle connector E Rubber washer Remove parts package from dryer drum Check that all parts are included NOTE Do not use leveling legs supplied with dryer if installing on a pedestal Parts needed Check local codes Check existing electrical supply and venting See Electrical Requirements and Venting Requirements before...

Page 3: ...imes The dryer must not be installed or stored in an area where it will be exposed to water and or weather Check code requirements Some codes limit or do not permit installation of the dryer in garages closets mobile homes or sleeping quarters Contact your local building inspector Installation clearances The location must be large enough to allow the dryer door to open fully Dryer Dimensions A B C...

Page 4: ... Electric or Gas Non Steam Electric or Gas A 1 25 mm 1 25 mm B 32 9 16 686 mm 31 1 2 800 mm C 5 127 mm 5 127 mm Required spacing For side or bottom venting 0 0 mm spacing is allowed Recessed or closet installation Dryer on pedesta A B C D E F 460 mm l Steam Electric or Gas Non Steam Electric or Gas A 1 25 mm 1 25 mm B 27 686 mm 27 686 mm C 1 25 mm 1 25 mm D 1 25 mm 1 25 mm E 32 9 16 686 mm 31 1 2 ...

Page 5: ... 2 310 cm2 3 76 mm 3 76 mm 1 25 mm 24 in 2 155 cm2 6 152 mm 76 1930 mm 27 686 mm A 1 25 mm 1 25 mm Steam Electric or Gas Non Steam Electric or Gas A 5 140 mm 5 127 mm Required spacing NOTE Some models are not recommended for stacked recessed or closet installation Mobile home Additional installation requirements This dryer is suitable for mobile home installations The installation must conform to ...

Page 6: ...nder the neutral terminal center or white wire of the terminal block the dryer cabinet is isolated from the neutral conductor If local codes do not permit the connection of a neutral ground wire to the neutral wire see Optional 3 wire connection section A 4 wire power supply connection must be used when the appliance is installed in a location where grounding through the neutral conductor is prohi...

Page 7: ...rain relief tab pointing up B Hole below terminal block opening C Clamp section D Strain relief tab pointing down Put power supply cord through the strain relief Be sure that the wire insulation on the power supply cord is inside the strain relief The strain relief should have a tight fit with the dryer cabinet and be in a horizontal position Do not further tighten strain relief screws at this poi...

Page 8: ...re connections A B C D E F G A 4 wire receptacle NEMA type 14 30R B 4 prong plug C Ground prong D Neutral prong E Spade terminals with upturned ends F 19 mm UL listed strain relief G Ring terminals 1 Remove center silver colored terminal block screw 2 Remove neutral ground wire from external ground conductor screw Connect neutral ground wire and the neutral wire white or center wire of power suppl...

Page 9: ...nter silver colored terminal block screw B Center silver colored terminal block screw C Neutral ground wire D Neutral wire white or center wire E 19 mm UL listed strain relief 3 Connect ground wire green or bare of direct wire cable to external ground conductor screw Tighten screw A B C D E F A External ground conductor screw B Ground wire green or bare of power supply cable C 19 mm UL listed stra...

Page 10: ...minal block screw 2 Place the hooked end of the neutral wire white or center wire of direct wire cable under the center screw of terminal block hook facing right Squeeze hooked end together Tighten screw A C D B E A External ground conductor screw B Neutral ground wire C Center silver colored terminal block screw D Neutral wire white or center wire E 19 mm UL listed strain relief 3 Place the hooke...

Page 11: ...drying performance If this is a new vent system Vent material Use a heavy metal vent Do not use plastic or metal foil vent 4 102 mm heavy metal exhaust vent and clamps must be used 4 102 mm heavy metal exhaust vent 4 102 mm Vent products can be purchased from your dealer or by calling Whirlpool Service For more information see the Assistance or Service section Rigid metal vent For best drying perf...

Page 12: ...ional exhaust installations This dryer can be converted to exhaust out the right side left side or through the bottom If you prefer you may contact your local dealer to have the dryer converted WARNING Fire Hazard Use a heavy metal vent Do not use a plastic vent Do not use a metal foil vent Failure to follow these instructions can result in death or fire A B C A Standard rear offset exhaust instal...

Page 13: ...Use caulking compound to seal exterior wall opening around exhaust hood 2 Connect vent to exhaust hood Vent must fit inside exhaust hood Secure vent to exhaust hood with 4 102 mm clamp 3 Run vent to dryer location Use the straightest path possible See Determine vent path in Plan Vent System Avoid 90º turns Use clamps to seal all joints Do not use duct tape screws or other fastening devices that ex...

Page 14: ...eck again for levelness COMPLETE INSTALLATION 1 Check that all parts are now installed If there is an extra part go back through the steps to see which step was skipped 2 Check that you have all of your tools 3 Dispose of recycle all packaging materials 4 Check the dryer s final location Be sure the vent is not crushed or kinked 5 Check that the dryer is level See Level Dryer 6 Remove the blue pro...

Page 15: ...akers Replace the fuse or reset the circuit breaker Confirm the power cord is properly installed Refer to Electrical Connection for details Select a Timed Dry heated cycle and restart the dryer If the message persists consult a qualified electrician AF low airflow condition The dryer will continue to run when this diagnostic code is present Press any key to clear the code from the display and retu...

Page 16: ...al Is the dryer located in a room with temperature below 45ºF 7ºC Proper operation of dryer cycles requires temperatures above 45ºF 7ºC Is the dryer located in a closet Closet doors must have ventilation openings at the top and bottom of the door The front of the dryer requires a minimum of 1 25 mm of airspace and for most installations the rear of the dryer requires 5 127 mm See the Installation ...

Reviews: