background image

11

ELECTRIC DRYER ELECTRICAL REQUIREMENTS

Electric Dryer Grounding

It is your responsibility:

 

To contact a qualified electrical installer.

 

 To be sure that the electrical connection is adequate and in 

conformance with the National Electrical Code, ANSI/NFPA 

70-latest edition and all local codes and ordinances.

 

 The National Electrical Code requires a 4-wire power 

supply connection for homes built after 1996, dryer circuits 

involved in remodeling after 1996, and all mobile home 

installations.

 

 A copy of the above code standards can be obtained from: 

National Fire Protection Association, One Batterymarch 

Park, Quincy, MA 02269.

 

 To supply the required 3 or 4 wire, single phase, 120/240 

volt, 60 Hz., AC only electrical supply (or 3 or 4 wire, 

120/208 volt electrical supply, if specified on the serial/

rating plate) on a separate 30-amp circuit, fused on both 

sides of the line. A time delay fuse or circuit breaker is 

recommended. Connect to an individual branch circuit.  

Do not have a fuse in the neutral or grounding circuit.

 

Do not use an extension cord.

 

 If codes permit and a separate ground wire is used, it is 

recommended that a qualified electrician determine that 

the ground path is adequate.

Electrical Connection
To properly install your dryer, you must determine the type 

of electrical connection you will be using and follow the 

instructions provided for it here.

 

 This dryer is manufactured ready to install with a 3-wire 

electrical supply connection. The neutral ground conductor 

is permanently connected to the neutral conductor (white 

wire) within the dryer. If the dryer is installed with a 4-wire 

electrical supply connection, the neutral ground conductor 

must be removed from the external ground connector 

(green screw), and secured under the neutral terminal 

(center or white wire) of the terminal block. When the 

neutral ground conductor is secured under the neutral 

terminal (center or white wire) of the terminal block, the 

dryer cabinet is isolated from the neutral conductor.

 

 If local codes do not permit the connection of a neutral 

ground wire to the neutral wire, see “Optional 3-wire 

connection” section.

 

A 4-wire power supply connection must be used when the 

appliance is installed in a location where grounding through 

the neutral conductor is prohibited. Grounding through the 

neutral is prohibited for (1) new branch-circuit installations 

and (2) areas where local codes prohibit grounding through 

the neutral conductor.

Summary of Contents for Commercial Dryer

Page 1: ...es 6 Location Requirements 8 Gas Dryer Electrical Requirements 9 Gas Requirements 10 Electric Dryer Electrical Requirements 11 Dryer Venting Requirements 13 Gas Supply Connection 15 Installing Leveling Legs Coin Slide and Coin Box 17 Electric Dryer Electrical Connections 18 Leveling 22 Complete Installation 23 Changing to a 30 or 60 Minute Timing Cam 24 Maintenance Instructions 25 If You Need Assi...

Page 2: ...ded that the owner post in a prominent location instructions for the customer s use in the event the customer smells gas This information should be obtained from your gas supplier Post the following warning in a prominent location ...

Page 3: ...3 DRYER SAFETY IMPORTANT When discarding or storing your old clothes dryer remove the door ...

Page 4: ...ction for grounding instructions IMPORTANT SAFETY INSTRUCTIONS WARNING To reduce the risk of fire electric shock or injury to persons when using the dryer follow basic precautions including the following SAVE THESE INSTRUCTIONS Read all instructions before using the dryer This dryer is intended only for drying clothes and textiles that have been washed in water Do not use for any other purpose WAR...

Page 5: ...ch 19 16 39 mm level utility knife 1 4 6 mm nut driver 27 686 mm wood block caulk gun and caulk vent clamps pipe joint compound putty knife for installing new exhaust vent suitable for gas type flashlight optional 1 25 mm ruler or measuring tape open end wrenches TOOLS PARTS TORX is a registered trademark of Saturn Fasteners Inc Parts Supplied leveling legs 4 security cone 5 16 hex head 18 x 21 2 ...

Page 6: ...xhaust 35 889 mm Non coin operated models 71 8 181 mm Coin operated models 77 8 200 mm 1 25 mm 251 2 648 mm 31 4 83 mm 101 4 260 mm 29 737 mm 427 8 1089 mm 1 25 mm Back View 43 4 121 mm 141 4 362 mm Electric Gas 29 737 mm 11 4 32 mm 315 8 803 mm 4 dia 102 mm 20 508 mm 143 4 375 mm ...

Page 7: ...in operated models 71 8 181 mm Coin operated models 77 8 200 mm 1 25 mm 261 2 673 mm 31 4 83 mm 101 4 260 mm 27 737 mm 427 8 1089 mm 1 25 mm 15 381 mm 0 0 mm 0 0 mm 14 356 mm 1 25 mm 0 0 mm Back View 11 4 32 mm 53 8 137 mm 16 406 mm 37 940 mm gas models 131 2 343 mm Electric Gas 27 686 mm 31 4 83 mm 4 dia 102 mm 13 330 mm 315 8 803 mm electric models ...

Page 8: ...ck code requirements Some codes limit or do not permit installation of clothes dryers in garages closets or sleeping quarters Contact your local building inspector Make sure that lower edges of the cabinet plus the back and bottom sides of the dryer are free of obstructions to permit adequate clearance of air openings for combustion air See Recessed Area and Closet Installation Instructions below ...

Page 9: ... A 120 volt 60 Hz AC only 15 or 20 amp fused electrical circuit is required A time delay fuse or circuit breaker is also recommended It is recommended that a separate circuit serving only this dryer be provided This dryer is equipped with a power supply cord having a 3 prong grounding plug To minimize the possibility of shock the cord must be plugged into a mating 3 prong grounding type outlet gro...

Page 10: ... Cleveland Ohio 44131 5575 The design of this dryer has been certified by CSA International for use at altitudes up to 10 000 feet 3048 m above sea level at the B T U rating indicated on the model serial plate Burner input adjustments are not required when the dryer is operated up to this elevation When installed above 10 000 feet 3048 m a four percent 4 reduction of the burner B T U rating shown ...

Page 11: ...nded that a qualified electrician determine that the ground path is adequate Electrical Connection To properly install your dryer you must determine the type of electrical connection you will be using and follow the instructions provided for it here This dryer is manufactured ready to install with a 3 wire electrical supply connection The neutral ground conductor is permanently connected to the ne...

Page 12: ...ong must have four 10 gauge copper wires and match a 4 wire receptacle of NEMA Type 14 30R The ground wire ground conductor may be either green or bare The neutral conductor must be identified by a white cover Then choose a 3 wire power supply cord with ring or spade terminals and UL listed strain relief The 3 wire power supply cord at least 4 ft 1 22 m long must have three 10 gauge copper wires a...

Page 13: ...ow and poor performance Do not install in enclosed walls ceilings or floors The total length should not exceed 73 4 ft 2 4 m NOTE If using an existing vent system clean lint from entire length of the system and make sure exhaust hood is not plugged with lint Replace plastic or metal foil vents with rigid metal or flexible metal vents Review Vent System Chart and if necessary modify existing vent s...

Page 14: ... chart see your parts distributor Provision must be made for enough air for combustion and ventilation Check governing codes and ordinances See Recessed Area and Closet Installation Instructions in the Location Requirements sections A 4 102 mm outlet hood is preferred However a 21 2 64 mm outlet exhaust hood may be used A 21 2 64 mm outlet creates greater back pressure than other hood types For pe...

Page 15: ...A main vent can be used for venting a group of dryers The main vent should be sized to remove 5663 l min 200 CFM of air per dryer Large capacity lint screens of proper design may be used in main vent if checked and cleaned frequently The room where the dryers are located should have make up air equal to or greater than CFM of all the dryers in the room Back draft Damper Kit Part No 3391910 is avai...

Page 16: ... also be connected using 3 8 10 mm approved copper or aluminum tubing If the total length of the supply line is more than 20 ft 6 1 m larger tubing will be required If using natural gas do not use copper tubing Pipe joint compounds that resist action of type of gas supplied must be used Shut off valve required The supply line must be equipped with a manual shut off valve installed within 6 ft 1 8 ...

Page 17: ...for proper installation For dryers using coin slides use the adapter kit supplied with the dryer Replace the meter case service door Put the coin vault with lock and key in the meter case opening Remove cardboard or hardboard from under dryer Adjust the legs of the dryer up or down until the dryer is level 4 Install added security device Check that power is not supplied to the dryer Open and remov...

Page 18: ...rain relief 2 Insert power cord into strain relief Remove Terminal Block Cover Strain Relief ELECTRIC DRYER ELECTRICAL CONNECTIONS Direct Wire Strain Relief 1 Insert strain relief 2 Insert conduit into strain relief and tighten clamp Strain Relief ...

Page 19: ...ve center terminal block screw and the ground wire by removing the external ground connector screw 2 Connect ground and neutral wire to center terminal block Connecting 4 Wire Connection Power Supply Cord IMPORTANT A 4 wire connection is required for mobile homes and where local codes do not permit the use of 3 wire connections Connecting Direct Wire Ground 3 Connect ground wire green or bare with...

Page 20: ...re connections Direct wire cable must have 5 ft 1 52 m of extra length so dryer can be moved if needed Strip 5 127 mm of outer covering from end of cable leaving bare ground wire at 5 127 mm Cut 11 2 38 mm from 3 remaining wires Strip insulation back 1 25 mm Shape ends of wires into a hook shape Connecting 3 Wire Connection Power Supply Cord Connecting 4 Wire Connection Direct Wire ELECTRIC DRYER ...

Page 21: ...to neutral wire Direct wire cable must have 5 ft 1 52 m of extra length so dryer can be moved if needed Strip 31 2 89 mm of outer covering from end of cable Strip insulation back 1 25 mm If using 3 wire cable with ground wire cut bare wire even with outer covering Shape ends of wires into a hook shape Connecting Neutral Wire 1 Loosen or remove center terminal block screw Connecting Remaining Wires...

Page 22: ...Remove center terminal block screw Also remove neutral ground wire by removing external ground conductor screw 2 Connect neutral wire and neutral wire of power supply cord cable to center terminal block Connecting 3 Wire Connection Optional 1 Remove cardboard from beneath dryer Place a level on top edges of dryer checking each side and front If not level tip dryer and adjust legs up or down as sho...

Page 23: ...rect electrical supply and the recommended grounding method See Electrical Requirements 2 Check that all parts are now installed If there is an extra part go back through the steps 3 Check that you have all of your tools 4 Dispose of recycle all packaging materials 5 Plug into a grounded outlet or connect power 6 Check dryer operation Close dryer door Insert coins and press slide in slowly Operati...

Page 24: ...aight up and off shaft making sure that the V shaped notch clears the ratchet tooth WARNING Electrical Shock Hazard Disconnect power before making cam changes Failure to follow these instructions can result in death or electrical shock 5 Place new cam hub side down over clock shaft Line up flat side of shaft with flat side of cam hole Check that drive lug is in place 6 Turn cam until V shaped notc...

Page 25: ...int screen before and after each cycle Removing accumulated lint From inside the dryer cabinet Lint should be removed every 2 years or more often depending on dryer usage Cleaning should be done by a qualified person From the exhaust vent Lint should be removed every 2 years or more often depending on dryer usage Keep area around dryer clear and free from combustible materials gasoline and other f...

Page 26: ...26 NOTES ...

Page 27: ...27 NOTES ...

Page 28: ...8563800D 2011 All rights reserved 12 2011 Printed in U S A ...

Reviews: