Whirlpool 6510374 Installation Instructions And Use And Care Manual Download Page 19

19

Operational Conditions

Condensation

Moisture from the products of combustion condenses on 
the tank surface and the outside jacket of the water heater 
and forms drops of water which may fall onto the burner or 
other hot surfaces. This will produce a “sizzling” or “frying” 
noise. NOTE: This condensation is normal and should not be 
confused with a leaking tank. Condensation may increase or 
decrease at different times of the year.

High efficient energy saver water heaters will produce 
larger amounts of condensation on initial start-up or when 
a large amount of hot water is being used. NOTE: Do not 
confuse this with a “tank leak”. Once the water reaches a 
temperature of 120°F and the tank warms up (usually 1-2 
hours), the condensation will stop.

IMPORTANT: It is always recommended that a suitable drain 
pan be installed under the water heater to protect the area 
from water damage resulting from normal condensation 
production, a leaking tank or piping connections. Refer to 
“Location Requirements” on page 4. Under no circumstances 
is the manufacturer to be held responsible for any water 
damage in connection with this water heater.

Water Heater Sounds

During the normal operation of the water heater, sounds or 
noises may be heard. These noises are common and may 
result from the following:

1.  Normal expansion and contraction of metal parts during 

periods of heat-up and cool-down.

2.  Condensation causes sizzling and popping within the 

burner area and should be considered normal.

3.  Sediment buildup in the tank bottom will create varying 

amounts of noise and may cause premature tank failure. 
Drain and flush the tank as directed under “Draining and 
Flushing”.

Smoke/Odor

The water heater may give off a small amount of smoke 
and odor during the initial start-up of the unit. This is due to 
the burning off of oil from metal parts of a new unit and will 
disappear after a few minutes of operation. 

Safety Shut-off

This water heater is designed to automatically shut-off in the 
event of the following:

1.  The pilot flame is extinguished for any reason.
2.  The water temperature exceeds 180°F (83°C).
3.  Excessive combustion chamber temperatures.
4.  The ignition of flammable vapors.

A thermopile is used to determine if a pilot flame is present, 
and will shut off the gas supply to the main burner and the 
pilot if the flame is absent. This unit is also equipped with a 
thermal switch, designed to shut off the gas supply in the 
event the water heater has been exposed to flammable 
vapors (eg, spilled gasoline), poor combustion caused by a 
blocked vent or insufficient combustion air. If the 
thermal switch opens: 
1.  Check the flame-trap for signs of high temperature 

(blue or black discoloration) See Figure 28A.

2.   If there are signs of high temperature, correct any 

issues before you reset the thermal switch. Contact the 
Product Service and Support Department for service 
information at: 

1-877-817-6750

3.   Inspect your installation for any problems with venting 

or combustion air. 

4.   Reset the thermal switch by depressing the small 

button in the center of the thermal switch.

A high temperature limit switch or ECO (Energy Cut Off) in 
the tank is used to shut off the unit if the water temperature 
exceeds 180°F (83°C). The ECO is a single use switch and 
requires complete replacement of the entire gas control 
valve/thermostat. If the ECO should function, the water 
heater cannot be used until the gas control valve/thermostat 
is replaced by a qualified person. Contact your local dealer 
for service information.

Anode Rod/Water Odor

Each water heater contains at least one anode rod, which 
will slowly deplete while protecting the glass-lined tank 
from corrosion and prolonging the life of the water heater. 
Once the anode is depleted, the tank will start to corrode, 
eventually developing a leak. Certain water conditions will 
cause a reaction between this rod and the water.  The most 
common complaint associated with the anode rod is a “rotten 
egg smell” produced from the presence of hydrogen sulfide 
gas dissolved in the water. IMPORTANT: Do not remove 
this rod permanently as it will void any warranties.

 

The parts 

list includes a special anode that can be ordered if water 
odor or discoloration occurs. NOTE: This rod may reduce 
but not eliminate water odor problems. The water supply 
system may require special filtration equipment from a water 
conditioning company to successfully eliminate all water odor 
problems. 

Artificially softened water is exceedingly corrosive because 
the process substitutes sodium ions for magnesium and 
calcium ions. The use of a water softener may decrease the 
life of the water heater tank. 

The anode rod should be removed from the water heater 
tank every 3 years for inspection. The following are typical 
(but not all) signs of a depleted anode rod:
• 

The majority of the rods diameter is less than 3/8”.

• Signifi cant sections of the support wire (approx. 1/3 or 

more of the anode rod’s length) are visible.

If the anode rod show signs of either or both it should be 
replaced. NOTE: Whether re-installing  or replacing the 
anode rod, check for any leaks and 
immediately correct if found.
In replacing the anode:
1.  Turn off gas supply to the water 

heater.

2.  Shut off the water supply and 

open a nearby hot water faucet to 
depressurize the water tank.

3.  Drain approximately 5 gallons 

of water from tank (Refer to 
“Draining and Flushing” for proper 
procedures). Close drain valve.

4.  Remove old anode rod.
5. Use 

Teflon

®

 tape or approved pipe 

sealant on threads and install new 
anode rod.

6.  Turn on water supply and open 

nearby hot water faucet to purge 
air from water system. Check for 
any leaks and immediately correct 
any if found.

7.  Restart the water heater as directed under “Operating 

Your Water Heater.” See the “Repair Parts Illustration” 
for anode rod location on page 27.

TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.

Summary of Contents for 6510374

Page 1: ...sion may result causing property damage personal injury or death INSTALLER AFFIX THESE INSTRUCTIONS TO OR ADJACENT TO THE WATER HEATER OWNER RETAIN THESE INSTRUCTIONS AND WARRANTY FOR FUTURE REFERENCE RETAIN THE ORIGINAL RECEIPT AS PROOF OF PURCHASE Table of Contents 2 6510374 W10100870 February 2006 Energy Smart Gas Water Heater with the Flame Lock Safety System To obtain technical warranty or se...

Page 2: ...if any part has been under water Immediately call a qualified service technician Water heaters subjected to flood conditions or any time the gas controls main burner or pilot have been submerged in water require replacement of the entire water heater Hydrogen gas can be produced in a hot water system that has not been used for a long period of time generally two weeks or more Hydrogen gas is extre...

Page 3: ...the Flame Lock Safety System should only be performed by a qualified person Examples of a qualified person include licensed plumbers authorized gas company personnel and authorized service personnel IMPORTANT This water heater has a resettable thermal switch installed as part of the Flame Lock Safety System DO NOT attempt to disable or modify this feature in any way IMPORTANT The manufacturer and ...

Page 4: ...y and call the fire department from a neighbor s home Do not attempt to clean the spill until all ignition sources have been extinguished Do not store combustible materials boxes magazines clothes etc on or in close proximity to the water heater Site Location Select a location near the center of the water piping system The water heater must be installed indoors and in a vertical position on a leve...

Page 5: ...ble materials are stated on the data plate adjacent to the gas control valve thermostat of the water heater The water heater is certified for installation on a combustible floor IMPORTANT If installing over carpeting the carpeting must be protected by a metal or wood panel beneath the water heater The protective panel must extend beyond the full width and depth of the water heater by at least thre...

Page 6: ... gas supply pressure must not exceed the maximum supply pressure as stated on the water heater s data plate The minimum supply pressure is for the purpose of input adjustment Gas Pressure Testing IMPORTANT This water heater and its gas connection must be leak tested before placing the appliance in operation If the code requires the gas lines to be tested at a pressure exceeding 14 W C the water he...

Page 7: ...e is excluded from warranty coverage The following types of installation not limited to the following will require outdoor air for combustion due to chemical exposure and may reduce but not eliminate the presence of corrosive chemicals in the air beauty shops photo processing labs buildings with indoor pools water heaters installed in laundry hobby or craft rooms water heaters installed near chemi...

Page 8: ...can be drawn from outside of the enclosure One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure as shown in Figure 4 The size of each opening free area is determined by the total BTUH input of all gas utilization equipment i e water heaters furnaces clothes dryers etc and the method by which the air is provided The BTUH input can be found on the ...

Page 9: ...r supply openings consideration must be given to the blocking effect of protection louvers grilles and screens These devices can reduce airflow which in turn may require larger openings to achieve the required minimum free area Screens must not be smaller than 1 4 mesh If the free area through a particular design of louver or grille is known it should be used in calculating the specified free area...

Page 10: ...ng water heater be sure to use the new drafthood supplied with the water heater Figure 9 Drafthood Installation Sheet Metal Screws four provided Drafthood Jacket top Install the drafthood with the four screws provided Legs Slots Slots Legs Vent Pipe Size It is important that you follow the guidelines in these instructions for sizing a vent pipe system If a transition to a larger vent size is requi...

Page 11: ...erminate with a listed cap or other roof assembly and be installed according to their manufacturer s instructions Gas vents must be supported to prevent damage joint separation and maintain clearances to combustible materials Figures 11 and 12 IMPORTANT This gas vent must be terminated in a vertical position to facilitate the removal of the burnt gases An unused chimney flue or masonry enclosure m...

Page 12: ...t line It should be located close to the water heater and be easily accessible Know the location of this valve and how to shut off the water to the heater 6 A temperature and pressure relief valve must be installed in the opening marked Temperature and Pressure T P Relief Valve on the water heater A discharge line must be added to the opening of the T P Relief Valve Follow the instructions under T...

Page 13: ... the requirements for Relief Valves and Automatic Shut off Devices for Hot Water Supply Systems ANSI Z21 22 The function of the temperature and pressure relief valve is to discharge water in large quantities in the event of excessive temperature or pressure developing in the water heater The valve s relief pressure must not exceed the working pressure of the water heater as stated on the data plat...

Page 14: ... water outlet pipe Special Applications Combination Space Heating Potable Water System Some water heater models are equipped with inlet outlet tappings for use with space heating applications If this water heater is to be used to supply both space heating and domestic potable drinking water the instructions listed below must be followed The unit must be set to standard mode See Operating the Tempe...

Page 15: ...s for possible gas leaks Correct any leak found Important Information About Your Water Heater This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a flammable vapor ignition incident New technology used in meeting these standards makes this product less tolerant of installation errors or improper installation environments Please review the following info...

Page 16: ...s completely filled with water before lighting the pilot Check the data plate near the gas control valve thermostat for the correct gas Do not use this water heater with any gas other than the one listed on the data plate If you have any questions or doubts consult your gas supplier or gas utility company Explosion Hazard Replace viewport if glass is missing or damaged Failure to do so can result ...

Page 17: ...rson Figure 17 Match Relief Opening Drafthood Figure 18 Flame Characteristics Tips may have a yellow tint Yellow inner cones are satisfactory Correct flame soft blue Water Temperature Regulation The thermostat is adjusted to the pilot position when it is shipped from the factory Water temperature can be regulated by moving the temperature dial to the preferred setting The preferred starting point ...

Page 18: ...Failure 6 Flashes Indicates Upper Sensor Failure 7 Flashes Indicates Electronic Control Failure 8 Flashes Indicates Valve Failure Continuous Solid Flash indicates system shutdown NOTE If the pilot lights but will only stay lit with the knob depressed in the pilot position look for the following status light codes 6 Second Solid Light followed by 4 Flashes The unit will not relight because it detec...

Page 19: ...vice and Support Department for service information at 1 877 817 6750 3 Inspect your installation for any problems with venting or combustion air 4 Reset the thermal switch by depressing the small button in the center of the thermal switch A high temperature limit switch or ECO Energy Cut Off in the tank is used to shut off the unit if the water temperature exceeds 180 F 83 C The ECO is a single u...

Page 20: ...supplies are not obstructed Build up of soot and carbon on the main burner and pilot burner Check for a soft blue flame Leaking or damaged water and gas piping Presence of flammable or corrosive materials in the installation area Presence of combustible materials near the water heater After servicing this water heater check to make sure it is working properly See Operating Your Water Heater sectio...

Page 21: ...d manifold tube at the gas control valve thermostat Figures 22 23 6 Grasp the manifold tube and push down slightly to free the manifold tube pilot tube and thermopile 7 Carefully remove the manifold assembly from the combustion chamber NOTE Be sure not to damage internal parts Removing the Burner from the Manifold Assembly Natural Gas Burner Low Nox 1 Take off the burner by removing the two 2 scre...

Page 22: ...Assembly Page 23 Figure 25 Two Piece Wire Connector Assembly Thermopile Connector Two Piece Wire Connector Pilot Tube Igniter Wire Retainer Clip Burner and other fittings not show for clarity Manifold Door Figure 26 Pilot Assembly Pilot Assembly Thermopile Connector Igniter Connector Thermal Switch Connectors Pilot Thermopile External Inspection Cleaning of the Flame trap Inspect the wrap around f...

Page 23: ...re 28B 4 Inspect the door gasket and make sure there is no fiberglass insulation between the door gasket and the combustion chamber 5 Replace the two screws which secure the manifold assembly door to the combustion chamber Tighten securely There should be no space between the gasket part of the manifold door and combustion chamber IMPORTANT Do not operate the water heater if the door gasket does n...

Page 24: ...ions Bubbles forming indicate a leak Correct any leak found If additional information is required contact the Service Department at 1 877 817 6750 TEFLON is a registered trademark of E I Du Pont De Nemours and Company 5 No leaks at pilot and manifold connection 6 Manifold door screws securely tightened 7 Depress the button on the thermal switch 1 Manifold door gasket properly sealed 2 Viewport not...

Page 25: ...iping dip tube must be in cold inlet 8 Advise customer DRIP FROM RELIEF VALVE 1 Excessive water pressure 2 Heater stacking 3 Closed water system 1 Use a pressure reducing valve and relief valve 2 Lower the thermostat setting 3 See Closed System Thermal Expansion THERMOSTAT FAILS TO SHUT OFF 1 Thermostat not functioning properly 2 Improper calibration 1 Replace thermostat 2 Replace thermostat COMBU...

Page 26: ...ng Refrigeration authorized service provider to correct the combustion air supply ventilation issue Correct size of openings to allow sufficient air NO YES YES YES NO Check the vent system for restrictions obstructions and check the vent termination height Refer to the Installation Instructions section of this manual for specific requirements NO Section C Pilot light will not remain lit Contact Cu...

Page 27: ... PILOT ASSEMBLY KIT Natural Gas 13 BURNER Natural Gas Low Nox 14 MANIFOLD DOOR ASSEMBLY Natural Gas Low Nox 15 TWO PIECE WIRE CONNECTOR WITH RETAINER CLIP 16 MANIFOLD DOOR GASKET 17 VIEWPORT ASSEMBLY 18 THERMISTORS Pictured on next page When ordering repair parts always give the following information 1 Model serial and product number 2 Type of gas 3 Item number 4 Parts description Repair Parts Lis...

Page 28: ...opile two piece wire connector with retainer clip thermal switch and pilot assembly Natural Gas Low Nox Item 15 Contains two piece wire connector and retainer clip Item 16 Contains manifold door gasket Item 17 Contains viewport Item 18 Contains replacement thermistors Item 18 WHIRLPOOL FLAME LOCK DESIGN and FLAME LOCK are trademarks of Whirlpool U S A 2006 Whirlpool Corporation All rights reserved...

Reviews: