Whirlpool 201553 Installation Instructions And Use & Care Manual Download Page 12

12  

Water System Piping

Piping, fittings, and valves should be installed according to 
the installation drawing (Figure 13). If the indoor installation 
area is subject to freezing temperatures, the water piping 
must be protected by insulation.
Water supply pressure should not exceed 80% of the 
working pressure of the water heater. The working 
pressure is stated on the water heater’s data plate. If this 
occurs, a pressure limiting valve with a bypass may need 
to be installed in the cold water inlet line. This should 
be placed on the supply to the entire house in order to 
maintain equal hot and cold water pressures.
IMPORTANT: 
• 

Heat cannot be applied to the water fittings on the 
heater as they may contain nonmetallic parts. If solder 
connections are used, solder the pipe to the adapter 
before attaching the adapter to the hot and cold water 
fittings.

• 

Always use a good grade of joint compound and be 
certain that all fittings are drawn up tight.

Piping Installation

1.  Install the water piping and fittings as shown in Figure 

13. Connect the cold water supply (3/4” NPT) to the 
fitting marked “C”. Connect the hot water supply (3/4” 
NPT) to the fitting marked “H”.

 

IMPORTANT: Some models may contain energy saving 
heat traps to prevent the circulation of hot water within 
the pipes. Do not remove the inserts within the heat 
traps.

2.  The installation of unions in both the hot and cold water 

supply lines is recommended for ease of removing the 
water heater for service or replacement.

3.  Some local codes may require, and the manufacturer 

of this water heater recommends, installing a tempering 
valve or an anti-scald device in the domestic hot water 
line as shown in Figure 14. These valves reduce the 
point-of-use temperature of the water by mixing cold 
and hot water and are readily available for use. 

4.  If installing the water heater in a closed water system, 

install an expansion tank in the cold water line as 
specified under “Closed System/Thermal Expansion” 
section.

5.  Install a shut-off valve in the cold water inlet line. It 

should be located close to the water heater and be 
easily accessible. Know the location of this valve and 
how to shut off the water to the heater.

6.  A temperature and pressure relief valve must be 

installed in the opening marked “Temperature and  
Pressure (T & P) Relief Valve” on the water heater. 
A discharge line must be added to the opening of 
the T&P Relief Valve. Follow the instructions under 
“Temperature and Pressure Relief Valve” section. 

7.  After piping has been properly connected to the water 

heater, remove the aerator at the nearest hot water 
faucet. Open the hot water faucet and allow the tank 
to completely fill with water. To purge the lines of 
any excess air, keep the hot water faucet open for 
3 minutes after a constant flow of water is obtained. 
Close the faucet and check all connections for leaks.

In a closed system use a

thermal expansion tank

Figure 13

Water Piping Installation

Main

Water

Supply

Cold Water

Inlet Valve

Cold Water

Supply to Fixtures

Hot Water

Outlet

Union

Temperature and

Pressure Relief Valve

Discharge line

6” maximum

above drain

Drain line

3/4” ID

minimum

Drain

Metal

Drain Pan

1 3/4” depth maximum

1”minimum

Massachusetts: 

Install a vacuum relief 

in cold water line per 

section 19 MGL 142.

Pressure reducing

valve with bypass

Figure 14
Typical Tempering
Valve Installation

Follow the tempering
valve manufacturer’s
instructions.

Cold

Water

Inlet

Hot

Water
Outlet

Tempered water
to fixtures

Tempering valve
(Set to 120°F)

Summary of Contents for 201553

Page 1: ...service agency or the gas supplier WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death INSTALLER AFFIX THESE INSTRUCTIONS TO OR ADJACENT TO THE WATER HEATER OWNER RETAIN THESE INSTRUCTIONS AND WARRANTY FOR FUTURE REFERENCE RETAIN THE ORIGINAL RECEIPT AS PROOF OF PURCHASE 6510415 W10123251 March 200...

Page 2: ... substances WARNING This product contains a chemical known to the State of California to cause cancer birth defects or other reproductive harm This appliance can cause low level exposure to some of the substances included in the Act Your safety and the safety of others are very important We have provided many important safety messages in this manual and on your appliance Always read and obey all s...

Page 3: ...users of this water heater will need it for future reference Service to the Flame Lock Safety System should only be performed by a qualified person Examples of a qualified person include licensed plumbers authorized gas company personnel and authorized service personnel IMPORTANT The manufacturer and seller of this water heater will not be liable for any damages injuries or deaths caused by failur...

Page 4: ... liquids or vapors have spilled or leaked in the area of the water heater leave the area immediately and call the fire department from a neighbor s home Do not attempt to clean the spill until all ignition sources have been extinguished Keep combustibles such as boxes magazines clothes etc away from the water heater area Site Location Select a location near the center of the water piping system Th...

Page 5: ...trols must be easily accessible for operation and service Maintain proper clearances as specified on the data plate Do not locate the water heater near an air moving device The operation of air moving devices such as exhaust fans ventilation systems clothes dryers fireplaces etc can affect the proper operation of the water heater Special attention must be given to conditions these devices may crea...

Page 6: ...ntrol valve thermostat 4 Turn the gas supply on and check for leaks Test all connections by brushing on an approved noncorrosive leak detection solution Bubbles will show a leak Correct any leak found Figure 3 Gas Piping Manual Gas Shut off Valve Ground Joint Union 3 minimum Check with local utility for minimum height Drip leg Gas Pressure IMPORTANT The gas supply pressure must not exceed the maxi...

Page 7: ...e is excluded from warranty coverage The following types of installation not limited to the following will require outdoor air for combustion due to chemical exposure and may reduce but not eliminate the presence of corrosive chemicals in the air beauty shops photo processing labs buildings with indoor pools water heaters installed in laundry hobby or craft rooms water heaters installed near chemi...

Page 8: ... be drawn from outside of the enclosure One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure as shown in Figure 4 The size of each opening free area is determined by the total BTUH input of all gas utilization equipment i e water heaters furnaces clothes dryers etc and the method by which the air is provided The BTUH input can be found on the wat...

Page 9: ...ipment so that they are opened automatically during equipment operation Keep louvers and grilles clean and free of debris or other obstructions Direct to outdoors Vertical ducts Horizontal ducts Figure 6 Figure 7 Figure 8 Table 3 Minimum Free Area of Permanent Openings for Ventilation and Combustion Air Supply All Air from Outdoors Only Based on the total BTUH input rating for all gas utilizing eq...

Page 10: ...isting water heater be sure to use the new draft hood supplied with the water heater Vent Pipe Size It is important that you follow the guidelines in these instructions for sizing a vent pipe system If a transition to a larger vent size is required the vent transition connection must be made at the draft hood outlet Vent Connectors 1 Type B Double Wall U L Listed Vent Pipe 2 Single Wall Vent Pipe ...

Page 11: ...terminate with a listed cap or other roof assembly and be installed according to their manufacturer s instructions Gas vents must be supported to prevent damage joint separation and maintain clearances to combustible materials Figures 11 and 12 IMPORTANT This gas vent must be terminated in a vertical position to facilitate the removal of the burnt gases An unused chimney flue or masonry enclosure ...

Page 12: ...r line as shown in Figure 14 These valves reduce the point of use temperature of the water by mixing cold and hot water and are readily available for use 4 If installing the water heater in a closed water system install an expansion tank in the cold water line as specified under Closed System Thermal Expansion section 5 Install a shut off valve in the cold water inlet line It should be located clo...

Page 13: ...ain a check valve backflow preventer or water pressure reducing valve This will create a closed water system During the heating cycle of the water heater the water expands causing pressure inside the water heater to increase This may cause the temperature and pressure relief valve to discharge small quantities of hot water To prevent this it is recommended that a diaphragm type expansion tank suit...

Page 14: ...t terminate a maximum of six inches above a floor drain or external to the building Must be capable of withstanding 250 F 121 C without distortion Must be installed to allow complete drainage of both the valve and discharge line T P Relief Valve and Pipe Insulation Some Models 1 Locate the T P Relief Valve on the water heater 2 Locate the slit running the length of the insulation 3 Spread this sli...

Page 15: ...m the system Otherwise these bubbles will be trapped in the air handler heat exchanger coil reducing the efficiency Do not connect the water heater to any system or components previously used with non potable water heating appliances when used to supply potable water Some jurisdictions may require a backflow preventer in the incoming cold water line This may cause the temperature and pressure reli...

Page 16: ...rized service provider Fresh air supply free of corrosive elements and flammable vapors Fresh air openings sized correctly with consideration given to the blocking effect of louvers and grilles Ductwork is the same cross sectional area as the openings Vent Pipe System Check for proper drafting at the water heater draft hood Refer to the Checking the Draft section of this manual for the test proced...

Page 17: ...ckwise to its lowest setting WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life LIGHTING INSTRUCTIONS 7 Depress the reset button all the way in and IMMEDIATELY depress the igniter button until you hear a loud click Observe the pilot through the view port Do not release the reset button Repeat immediately if...

Page 18: ...how a discoloration on the air intake grid and require replacement of the entire water heater Depress the gas control knob slightly and turn clockwise to OFF Do not use tools or force Turn the temperature dial clockwise to its lowest setting Turn gas control knob clockwise to PILOT WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage person...

Page 19: ...e edges After several minutes of operation the burner screen may glow red If large flames are observed at anytime shut off unit and call a qualified person Stacking Stacking occurs when a series of short draws of hot water 3 gallons or less are taken from the water heater tank This causes increased cycling of the burner and can result in increased water temperatures at the hot water outlet An anti...

Page 20: ...ilot flame is present and will shut off the gas supply to the main burner and the pilot burner if the flame is absent A high temperature limit switch or ECO Energy Cut Off in the tank is used to shut off the unit if the water temperature exceeds 180 F 83 C The ECO is a single use switch which if activated requires complete replacement of the entire gas control valve thermostat If the ECO should ac...

Page 21: ...n air supplies are not obstructed Build up of soot and carbon on the main burner and pilot burner Check for a soft blue flame Leaking or damaged water and gas piping Presence of flammable or corrosive materials in the installation area Presence of combustible materials near the water heater After servicing this water heater check to make sure it is working properly See Operating Your Water Heater ...

Page 22: ... Replacing the Pilot Assembly 1 Follow the instructions in Removing the Burner Door Assembly section to remove the assembly 2 Remove the retainer clip securing the two piece wire connector to the burner door assembly Note the orientation of the retainer clip Insert the tip of a large flat head screwdriver between the clip and the top of the two piece wire connector Carefully rotate the screwdriver...

Page 23: ...y section 2 Use a vacuum cleaner shop vac to remove all loose debris in the combustion chamber Figure 28 Use compressed air to clear any dust or debris that may have accumulated in the flame trap 3 Reassemble following the procedure under the Replacing the Burner Door Assembly section External Inspection Cleaning of the Flame trap Although not likely to occur if debris collects on the flame trap u...

Page 24: ...spect the viewport for damage and replace as required 3 Insert the burner door assembly into the combustion chamber and slide it completely forward Note When inserting the burner door assembly tip the burner end up slightly to ensure it engages with the burner bracket 4 Inspect the door gasket and make sure there is no fiberglass insulation between the door gasket and the combustion chamber See Fi...

Page 25: ...rder When replacing the gas valve thread a correctly sized pipe into the inlet and use it to turn the gas valve clockwise DO NOT OVER TIGHTEN damage may result Be sure to use approved Teflon tape or pipe joint compound on the gas piping connections and fitting on the back of the gas control valve that screws into tank Be sure to remove the pilot ferrule nut from the new gas control valve thermosta...

Page 26: ...h gas utility company SLOW HOT WATER RECOVERY 1 Insufficient air 2 Flue clogged 3 Low gas pressure 4 Improper calibration 5 Thermostat set too low 6 Water heater too small 7 Wrong piping connections 8 Wasted hot water 1 Provide ventilation to water heater Check flue way flue baffle and burner 2 Clean flue locate source and correct 3 Check with gas utility company 4 Replace thermostat 5 Turn temper...

Page 27: ...nd orifice Is the pilot free from dirt and debris NO YES Follow the Cleaning the Pilot Assembly instructions found in this manual Is the pilot protected from cold drafts that could prevent it from lighting NO YES Eliminate any drafts See the Site Location instructions found in this manual Check the water heater for a Flammable Vapor FV event If the flame trap show signs of discoloration shut off t...

Page 28: ... PIECE WIRE CONNECTOR WITH RETAINER CLIP 15 BURNER DOOR GASKET 16 VIEWPORT ASSEMBLY 17 THERMOCOUPLE 18 PIEZOELECTRIC IGNITER BUTTON 19 FLEXIBLE MANIFOLD TUBE REPAIR PARTS ILLUSTRATION When ordering repair parts always give the following information 1 Model serial and product number 2 Type of gas 3 Item number 4 Parts description Repair Parts List LEGEND Special anode rod see Anode Rod Water Odor s...

Page 29: ...ntains two piece wire connector and retainer clip Item 15 Contains burner door gasket Item 16 Contains viewport Item 17 Contains thermocouple Item 18 Contains piezoelectric igniter button Item 19 Contains flexible manifold tube Item 15 Item 14 Item 16 Item 13 Item 12 Item 18 Item 17 Item 19 Alternate Igniter WHIRLPOOL FLAME LOCK DESIGN and FLAME LOCK are trademarks of Whirlpool U S A 2007 Whirlpoo...

Reviews: