Figure 13. 

Hang Up Tone Frequency Detector 

 
When shipped from the factory, the frequency is set to minimum (200Hz), and is adjustable up to 950Hz.  The adjustment 
procedure is as follows: 
 
1. 

Initiate a page to TPI-100. 

 

2. 

Hang up phone. 

 

3. 

When the Hang Up Tone comes on, adjust the potentiometer until the TPI-100 disconnects. 

 

4. 

Initiate a page to TPI-100 

 

5. 

Hang up phone. 

 

6. 

The TPI-100 should disconnect immediately upon detecting the Hang Up Tone.  If the TPI-100 does not disconnect 
immediately, repeat adjustment procedures. 

 
 

The Page Duration Timer

 potentiometer is shown in Figure 14.  It is used with telephone  systems with a delayed Hang Up 

Tone that cannot be detected by the frequency detector, or with systems that do not generate a Hang Up Tone (remain silent).  
For telephone systems with Hang Up Tones that can be detected by the frequency detector, the Page Duration Timer (set at 51 
seconds with its Timer Control Jumper in the "VOX" position) also serves as a back-up disconnect device in one-way paging 
applications if the paging party inadvertently does not hang up. 
 

 

 

Figure 14. 

Page Duration Timer 

 
 
 
When shipped from the factory the timer is set to 51 seconds (maximum).  If the Timer Control Jumper is set for "VOX" control, 
then the timer begins to time out when audio is no longer detected on Tip and Ring.  If the Timer Control Jumper is set for 

Summary of Contents for TPI-100

Page 1: ...blem has been corrected Should the equipment cause harm to the telephone network the telephone company shall if possible notify the customer that temporary discontinuance of service may be required ho...

Page 2: ...ems that generate a delayed or immediate Hang Up Tone the TPI 100 is equipped with a variable Frequency Detector 200 to 950Hz which is adjusted during installation to detect the telephone system s spe...

Page 3: ...he TPI 100 will disconnect the paging system when the preset time has elapsed NOTE Voice signals of the same frequency as the Hang Up Tone may cause the TPI 100 to disconnect If the TPI 100 disconnect...

Page 4: ...ne system consisting of a single TPI 100 and a single TBM 101 talkback speaker system or TBH 104 talkback horn system One TBM 101 or TBH 104 may be used with a TPI 100 Depending upon the telephone sys...

Page 5: ...ed speakers horns The Timer Control Jumper should be placed in the VOX position Figure 4 Single Line Multi Zone Paging Figure 4 depicts a multi zone system consisting of a single TPI 100 and an FZC 3...

Page 6: ...n tone TO ACCESS ALL ZONES SIMULTANEOUSLY dial the number of the line connected to the TPI 100 controlling All Call If individual zone paging is in progress when an All Call page is initiated then an...

Page 7: ...igned to each page group and to All Call The paging devices connected to the TPI 100 s can be any of the configurations shown in Figures 1 thru 4 The TPI 100 s controlling the individual zones should...

Page 8: ...phone as a confirmation tone If individual zone paging or group paging is in progress when an All Call page is initiated then an alert tone will be signaled back to the zone and or group paging telep...

Page 9: ...dance 600 OHMS Hang Up Tone Detect Frequency Range 200hz to 950Hz Hang Up Tone Detect Time 250m Seconds Page Duration Timer Range 3 to 51 Seconds Operating Temperature Range 0 to 55 Degrees C Operatin...

Page 10: ...ll individual zone TPI 100 s B Connect TB1 terminal 6 from the All Call TPI 100 to TB1 terminal 4 of all individual zone TPI 100 s 7 In multiple line applications with Group Page and All Call A Connec...

Page 11: ...P82030 K Sheet 11 of 17 Figure 9 Installation Programming and Tone Volume Adjustment Diagram...

Page 12: ...Talk Battery TPI 100 selector switch to the TPI 100 position 2 If TPI 100 and FZC 3 use separate power supplies then install wire between GND TB1 terminal 5 on TPI 100 and GND TB1 terminal 4 on FZC 3...

Page 13: ...MAN pins for preset time out of the Page Duration Timer The Tone Detect Jumper is shown in Figure 12 Figure 12 Tone Detect Jumper When shipped from the factory the two position jumper is placed over t...

Page 14: ...shown in Figure 14 It is used with telephone systems with a delayed Hang Up Tone that cannot be detected by the frequency detector or with systems that do not generate a Hang Up Tone remain silent For...

Page 15: ...y times how long it takes for the telephone system to generate its Hang Up Dial or Reorder tone D Set the Page Duration Timer for just under the amount of time it takes the telephone system to generat...

Page 16: ...nput ACI All Call Output ACO and Zone Control Output ZCO wiring 4 Verify unit has released from last page 2 No sound or low page volume 1 Check presence and level of audio input at Tip and Ring termin...

Page 17: ...WARE WILL MEET THE USER S REQUIREMENTS WHEELOCK SHALL NOT BE LIABLE FOR ANY DELAYS BREAKDOWNS INTERRUPTIONS LOSS DESTRUCTION ALTERATION OR OTHER PROBLEMS IN THE USE OF A PRODUCT ARISING OUT OF OR CAUS...

Reviews: