WARNING:
CONTACT WHEELOCK FOR THE CURRENT “INSTALLATION INSTRUCTIONS” SERIES RSSR (P83884)
“GENERAL INFORMATION” SHEET (P82380) ON THESE PRODUCTS. THESE DOCUMENTS UNDERGO PERIODIC
CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE
PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING
OR INSTALLING THESE PRODUCTS, INCLUDING:
•
TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES.
•
FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON THOSE
CIRCUITS.
•
COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON’S FIELD OF VIEW.
•
ADDING, REPLACING OR CHANGING APPLIANCES COULD EFFECT CURRENT DRAW.
RECALCULATE CURRENT DRAW TO INSURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK REQUIRED BY ALL
APPLIANCES DO NOT EXCEED THE RATED CAPACITY OF THE POWER SOURCES OR FUSES.
•
THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR “REGULATED VOLTAGE RANGE”.
•
USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBES ON CODED
OR INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBES MAY NOT FLASH.
•
FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN
IMPROPER INSTALLATION, APPLICATION, AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH
COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
•
CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND
INSTALLATION OF THESE PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS.
Wiring Diagrams
#
# For detail using SM or DSM Sync Module refer to Data Sheet S3000 or Installation Instructions (P83123 for SM and P83177 for DSM).
For wiring information on the PS-12/24-8CP and PS-12/24-8MP Power Supplies refer to Installation Instructions P84515 and P84333.
Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and
operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with
local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by
qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters’ Laboratories (UL),
National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable
building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the
local authority having jurisdiction (AHJ).
+
-
+
-
+
-
FROM
PRECEDING
APPLIANCE, SYNC
MODULE, POWER
SUPPLY OR FACP
TO NEXT
APPLIANCE
OR EOLR
SERIES RSSR APPLIANCE
SERIES RSSR APPLIANCE SYNCHRONIZED WITH SM
MODULE SINGLE CLASS “B” NAC CIRCUIT
EOLR
+
-
SM
F
A
C
P
STROBE
Audible
STROBE
+
- Audible
Strobe
NAC
Circuit
RSSR
RSSR
DSM
+ OUT 2
+OUT 1
+ IN 1
+ IN 2
MINUS 1
MINUS 2
+
-
-
+
SYNC
AUDIBLE
STROBE
NAC
CIRCUIT
OUT
STROBE
NAC
CIRCUIT
RETURN
FACP
RSSR
RSSR
RSSR
RSSR
RSSR
RSSR
SERIES RSSR APPLIANCES SYNCHRONIZED WITH DSM
MODULE SINGLE CLASS “A” NAC CIRCUIT
F
A
C
P
DSM #3
Strobe NAC Cir.
DSM #2
DSM #1
Strobe NAC Cir.
Strobe NAC Cir.
Sync
Sync
Sync
+
-
+
+
-
-
DSM Interconnecting wiring shown. Maximum of
twenty (20)
RSSR
RSSR
RSSR
RSSR
RSSR
RSSR
SERIES RSSR APPLIANCES SYNCHRONIZED WITH
MULTIPLE DSM MODULES
Series PS-12/24-8CP
or PS-12/24-8MP
Series PS-12/24-8
EOLR
F
A
C
P
OUTPUTS
1-4
4-CLASS
"B"
OR
2-CLASS
"A"
AS
AS
AS
RSSR
RSSR
RSSR
SERIES RSSR APPLIANCES SYNCHRONIZED
WITH PS-12/24-8CP or PS-12/24-8MP