OPERATING INSTRUCTIONS:
Figure 3.
1. The green LED indicates there are no faults in the SAFEPATH system. The amber LED indicates there are 1 or more faults in
the system (see SAFEPATH manual for troubleshooting procedures). The red LEDs indicate that the zone is in an alarm
condition.
2. Switching the AUTO/MANUAL switch to the MANUAL position initiates a tone alarm.
3. Pressing the microphone press-to-talk button initiates a live audible announcement.
4. Each alarm has its own priority. The actions of the Remote Microphone might override or be overridden by other actions. See
Table 1 for a list of all alarm conditions.
5. Switching a ZONE DISCONNECT switch removes that zone from an alarm condition.
6. Switching the ALL CALL switch to the ALL CALL position overrides all zone disconnects.
NOTE
: Some models may have “Words” indicating the type of message instead of numbers above the Tone/Message activation
buttons.
Table 1: Alarm Conditions and the Respective Resulting Actions (in order of priority)
1. Panel mic push-to-talk button is depressed.
a. Panel live voice broadcast enabled
b. Strobes not enabled
2. AUTO/MANUAL switch in manual position.
a. Selected tone broadcasts
b. Strobes enabled
3. Remote mic push-to-talk button depressed.
a. Remote mic live voice broadcast enabled
b. Strobes enabled
4. Remote mic AUTO/MANUAL switch in
manual position.
a. Selected tone broadcasts
b. Strobes enabled
5. Channel play contacts close.
a. Selected tone broadcasts
b. Strobes enabled
c. If DV option is attached, then:
1) Recorded message plays
2) Strobes enabled
See SAFEPATH Manual for additional information.