background image

P84501 B 

Sheet 2 of 8 

 

WARNING:  CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY 

BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE 
THE APPLIED VOLTAGE TO THE STROBES.

 

 

SPECIFICATIONS (AMPLIFIER): 
 

Table 1A:  Sound Output Level 

Sound Level 

Rated Reverberant dBA at 

10 ft per UL 1480 for 0.5-V and 25-V Settings 

6 82 
5 81 
4 76 
3 74 
2 70 
1 68 

 

NOTE:

  See Table 5 

Sound Output Level Selection

 for use of settings “A” and “B”. 

 

 

Power 

Input 

Voltage:       16.0 

to 

33.0 

VDC, 

regulated 

Current 

Consumption:      120 

mA 

RMS 

maximum 

Appliance Input Level:            0.5 V RMS or 25 V RMS (Switch selectable) 
Appliance Input Impedance: 

  0.5-V Setting: 
     Greater than 400 Ohms, or equivalent to less than 
     1/1000 W (0.001 W or 1 mW) load 

 

25-V Setting: 

     Greater than 20 kOhms, or equivalent to less than 
     1/32 W (0.03125 W or 31.25 mW) load 
 

Sound pressure level measurements were made at 16 VDC with audio inputs of 0.5 V RMS in the 0.5-V setting and with 25 V RMS 
in the 25-V setting. Current measurements were made at 33 VDC with audio inputs of 0.5 V RMS in the 0.5-V setting and with 
25 V RMS in the 25-V setting. 
 
Reverberant dBA is a minimum UL rating based on sound measurements in a reverberant test room. 
 

Table 1B:  Strobe

 

Regulated Voltage 

VDC/FWR 

Voltage Range 

VDC/VRMS 

Candela Mounting 

Options 

24 16.0-33.0 

15/30/75/110 

A,B 

 

NOTES: 

1.

 

The strobe will produce 1 flash per second over the "Regulated Voltage" range. 

2.

 

The SA Series

 

is UL Listed for indoor use with a temperature range of +32

°

F  to +120

°

F  (0

°

C to +49

°

C) and maximum 

humidity of 85% RH. 

 
 

WARNING:  CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT. 

 
 

Table 2:  UL Current Ratings (AMPS)  

Maximum RMS Current  

UL Voltage 

15cd 

30cd 

75cd 

110cd 

DC 16-33.VDC  0.060 

0.092 

0.165 

0.220 

FWR 16-33.VRMS  0.102 0.155 0.253 

0.347 

Summary of Contents for SA-S70-24MCW-FR

Page 1: ...vide a synchronized strobe appliance when used in conjunction with a Sync Module SM Dual Sync Module DSM or Wheelock s Power Supplies listed for synchronization The Strobe uses a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum visibility and reliability for effective visible signaling The SA Series is listed for indoor use wall mount only with the back...

Page 2: ...to less than 1 32 W 0 03125 W or 31 25 mW load Sound pressure level measurements were made at 16 VDC with audio inputs of 0 5 V RMS in the 0 5 V setting and with 25 V RMS in the 25 V setting Current measurements were made at 33 VDC with audio inputs of 0 5 V RMS in the 0 5 V setting and with 25 V RMS in the 25 V setting Reverberant dBA is a minimum UL rating based on sound measurements in a reverb...

Page 3: ... current exceeds the power supplies peak capacity the output voltage provided by the power supplies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies For example an auxiliary power supply that lacks filtering at its output stage either via lack of capacitance and or lack of battery backup across the out...

Page 4: ...5 1 7 10 2 12 25 5 33 37 4 44 50 4 1 6 8 1 11 20 3 29 29 7 41 55 3 3 6 6 6 11 16 5 28 24 2 38 60 2 7 5 5 4 10 13 5 27 19 8 37 65 2 4 5 4 8 10 12 0 27 17 6 37 70 2 3 6 4 5 10 11 3 27 16 5 37 75 2 0 5 3 9 10 9 8 26 14 3 36 80 1 8 5 3 6 9 9 0 25 13 2 33 85 1 8 5 3 6 9 9 0 24 13 2 33 90 1 8 2 3 6 5 9 0 12 13 2 17 SETTINGS The switch on the PCB SW1 is used to select the input voltage and sound output l...

Page 5: ...ith respect to the reference level Sound Output Level 6 0 dB and are included only to assist the user in choosing a setting during installation However use the values in Table 1 not these values for the actual sound output levels WARNING DOUBLE CHECK SWITCH SW1 SETTINGS TO MAKE SURE THEY ARE CORRECT IMPROPER SETTINGS CAN DAMAGE THE UNIT OR RESULT IN A DISTORTED OUTPUT OR A dBA SOUND OUTPUT LEVEL T...

Page 6: ...provide sufficient wiring clearance for the installed product 7 Do not pass additional wires used for other than the signaling appliance through the backbox Such additional wires could result in insufficient wiring space for the signaling appliance 8 Mounting hardware for each mounting option is supplied 9 The SA Series can be flush mounted to a 4 square by 1 1 2 deep backbox with a 4 square 1 1 2...

Page 7: ...PA Standards and the Authority Having Jurisdiction WARNING IF SYNCHRONIZED STROBES ARE NOT USED THEN A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON S FIELD OF VIEW UNDER CERTAIN CIRCUMSTANCES MIGHT INDUCE A PHOTO SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY STROBE REFLECTIONS IN A GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE TO MINIMIZE THIS POSSIBLE HAZA...

Page 8: ...RODUCT THE FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT WHEELOCK MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND EXPRESS IMPLIED OR STATUTORY WHETHER AS TO MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR THE USER S PURPOSE...