MODEL NUMBERS: 

SA-S70-24MCW-FR     Supervised Self-Amplified Speaker with Multi-Candela 
SA-S70-24MCW-FW     Sync/Non-Sync Strobe, Wall Mount 
 

GENERAL: 

The Multi-Candela Supervised Self-Amplified Speaker Strobe is UL Listed under Standards UL 1971 (Standard for Signaling 
Devices for the Hearing Impaired) and UL 1480 (Standard for Speakers for Fire Alarm, Emergency, and Commercial and 
Professional Use)  for indoor fire protection service and provides a choice of 6 different sound output levels and operates with audio 
input levels of 0.5 V RMS (e.g., from Wheelock’s SALL-15S or any other 0.5V-RMS audio output source Listed for Fire Protective 
Signaling Service) and 25 V RMS, all by means of selectable switch settings.  The Low Profile design incorporates a high efficiency 
speaker for maximum output at minimum power across a frequency range of 400Hz to 4000Hz, and features a sealed back 
construction for extra protection and improved audibility.  The appliance mounts onto a 4” square deep backbox with an extension 
ring. (See Mounting Options.) All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring 
via a Control Panel. 
 
The SA Series

 

Multi-Candela Speaker Strobe provides four selectable light output intensities in one unit and can provide a 

non-synchronized strobe appliance when connected directly to a Fire Alarm Control Panel (FACP), or provide a synchronized strobe 
appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or Wheelock’s Power Supplies listed for 
synchronization.  The Strobe uses a Xenon flashtube with solid-state circuitry enclosed in a rugged Lexan

 lens to provide maximum 

visibility and reliability for effective visible signaling.  The SA Series

 

is listed for 

indoor use, wall mount only

 with the backboxes 

specified in these instructions (see Mounting Options). 

 

The SA Series

 

is UL Listed for 

indoor use only

 over a temperature range of +32

°

F  to +120

°

F  (0

°

C to +49

°

C) and maximum 

humidity of 85% RH, with the backboxes specified in these instructions (see Mounting Options). 

 

NOTE

:  “Lexan” is a registered trademark of General Electric Company. 

 

NOTE:

  All 

CAUTIONS

 and 

WARNINGS

 are identified by the symbol 

.  All warnings are printed in bold capital letters. 

 

WARNING:  THE SPEAKER STROBE APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT." 

 

WARNING:  PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT.  THE 

SUPERVISED SELF-AMPLIFIED SPEAKER STROBE MUST BE FIELD SET TO THE DESIRED SOUND OUTPUT 
LEVEL BEFORE IT IS INSTALLED.  THIS IS DONE BY PROPERLY ADJUSTING A FOUR-POSITION SWITCH IN 
ACCORDANCE WITH THESE INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER 
PERFORMANCE AND MAY DAMAGE THE PRODUCT, WHICH COULD RESULT IN PROPERTY DAMAGE AND 
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

NOTE:  THE MAXIMUM WIRE IMPEDENCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.  THE 
MAXIMUM NUMBER OF STROBES ON A SINGLE NOTIFICATION APPLIANCE CIRCUIT SHALL NOT EXCEED 47. 
 

WARNING:  THIS APPLIANCE WAS TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS USING 

FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR) POWER FOR THE STROBE. THE AMPLIFIER 
WAS TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS REGULATED POWER. DO NOT APPLY 
80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION. 

 

Copyright 2004 Wheelock, Inc.  All rights reserved.

 

Summary of Contents for SA-S70-24MCW-FR

Page 1: ...vide a synchronized strobe appliance when used in conjunction with a Sync Module SM Dual Sync Module DSM or Wheelock s Power Supplies listed for synchronization The Strobe uses a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum visibility and reliability for effective visible signaling The SA Series is listed for indoor use wall mount only with the back...

Page 2: ...to less than 1 32 W 0 03125 W or 31 25 mW load Sound pressure level measurements were made at 16 VDC with audio inputs of 0 5 V RMS in the 0 5 V setting and with 25 V RMS in the 25 V setting Current measurements were made at 33 VDC with audio inputs of 0 5 V RMS in the 0 5 V setting and with 25 V RMS in the 25 V setting Reverberant dBA is a minimum UL rating based on sound measurements in a reverb...

Page 3: ... current exceeds the power supplies peak capacity the output voltage provided by the power supplies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies For example an auxiliary power supply that lacks filtering at its output stage either via lack of capacitance and or lack of battery backup across the out...

Page 4: ...5 1 7 10 2 12 25 5 33 37 4 44 50 4 1 6 8 1 11 20 3 29 29 7 41 55 3 3 6 6 6 11 16 5 28 24 2 38 60 2 7 5 5 4 10 13 5 27 19 8 37 65 2 4 5 4 8 10 12 0 27 17 6 37 70 2 3 6 4 5 10 11 3 27 16 5 37 75 2 0 5 3 9 10 9 8 26 14 3 36 80 1 8 5 3 6 9 9 0 25 13 2 33 85 1 8 5 3 6 9 9 0 24 13 2 33 90 1 8 2 3 6 5 9 0 12 13 2 17 SETTINGS The switch on the PCB SW1 is used to select the input voltage and sound output l...

Page 5: ...ith respect to the reference level Sound Output Level 6 0 dB and are included only to assist the user in choosing a setting during installation However use the values in Table 1 not these values for the actual sound output levels WARNING DOUBLE CHECK SWITCH SW1 SETTINGS TO MAKE SURE THEY ARE CORRECT IMPROPER SETTINGS CAN DAMAGE THE UNIT OR RESULT IN A DISTORTED OUTPUT OR A dBA SOUND OUTPUT LEVEL T...

Page 6: ...provide sufficient wiring clearance for the installed product 7 Do not pass additional wires used for other than the signaling appliance through the backbox Such additional wires could result in insufficient wiring space for the signaling appliance 8 Mounting hardware for each mounting option is supplied 9 The SA Series can be flush mounted to a 4 square by 1 1 2 deep backbox with a 4 square 1 1 2...

Page 7: ...PA Standards and the Authority Having Jurisdiction WARNING IF SYNCHRONIZED STROBES ARE NOT USED THEN A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON S FIELD OF VIEW UNDER CERTAIN CIRCUMSTANCES MIGHT INDUCE A PHOTO SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY STROBE REFLECTIONS IN A GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE TO MINIMIZE THIS POSSIBLE HAZA...

Page 8: ...RODUCT THE FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT WHEELOCK MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND EXPRESS IMPLIED OR STATUTORY WHETHER AS TO MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR THE USER S PURPOSE...