MOUNTING PROCEDURES: 
 
 

CAUTION:  

Check that the installed product  will have sufficient clearance and wiring room prior to installing backboxes and 

conduit, especially if sheathed multiconductor cable or 3/4" conduit fittings are used. 

 
 

1. 

Multitone Strobe models can be flush mounted to a standard 4 inch square by 2-1/8 inch deep electrical box (Figure A) or a 

standard 2-gang by 3-1/2" inch minimum deep electrical box (Figure B).   

 
2. 

All models can also be surface mounted to Wheelock's model IOB backbox (Figure C or D) or to a 4" square backbox (model 

DBB or BB) with Wheelock's model ISP extender (Figure F and G). 

 
3. 

Multitone Strobe models can also be retrofitted to an existing FSB backbox to replace Wheelock's model 7001 Strobe Horn 

when used with Wheelock adaptor plate model RP (Figure E). 

 
4. 

All models are supplied with four snap-in covers to hide the mounting holes and provide an attractive installation.  The snap-in 

covers are interchangeable and have slots on each end so they can be removed if necessary (by prying them up with a thin blade 
screwdriver).  To insert snap-in cover, slide the outside edge of the cover (furthest edge from the strobe lens) partially into the 
mounting hole recess; then align the cover so it is parallel to the grille (not tilted) and snap cover into place. 

 
5. 

The IOB surface backbox has 1/2 inch conduit knockouts on two sides.  It has a variety of knockouts on the back for mounting 

it to recessed electrical boxes and for wire entrances (Figure D).  It can also be mounted to a surface with the two mounting 
ears that are supplied.  The ears slide into slots on the back of the box (Figure C).  Use appropriate anchors for the wood screws 
that are supplied with the box (if necessary). 

 
6. 

The IOB includes a prefastened gasket and four hole plugs.  Make sure the condensation drain holes on the box face down and 

that the box is vertical to permit drainage of any moisture.  Use the mounting ears to secure the box (do not use the back 
knockouts).  Use the hole plugs to seal the unused mounting holes on the Multitone grille (press them in securely from the back 
side of the grille).  Mount the unit to the IOB with the four #8-18 screws supplied with the box. 

 
7. 

Mounting hardware for each mounting option is supplied. 

 
8. 

Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product.  When 

extension rings are required, conduit should enter through the backbox, not the extension ring.  Use Steel City #53151 (1-1/2" 
deep) or #53171 (2-1/8" deep) extension rings (as noted in the mounting options) or equal with the same cut-out area. 

 
9. 

When terminating field wires, do not use more lead length than required.  Excess lead length could result in insufficient wiring 

space for the signaling device. 

 
10.  Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce 

minimum stress on the product.  This is especially important for stiff, heavy gauge wires and wires with thick insulation or 
sheathing. 

 
11.  Do not pass additional wires (used for other than the signaling device) through the backbox.  Such additional wires could result 

in insufficient wiring space for the signaling device. 

 
12.  All models are UL Listed for indoor outdoor use with a temperature range of:  32oF to 120oF (0oC to +49oC) and maximum 

humidity of 85% RH for indoor use and -31oF to 150oF (-35oC to +66oC) and maximum humidity of 95% RH for outdoor use.  

 
 
 
 
 
 

Summary of Contents for MT-12-WH

Page 1: ...l Panel FACP NOTE All CAUTIONS and WARNINGS are identified by the symbol All warnings are printed in bold capital letters WARNING PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION INSTALLATION AND OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION WHICH COULD R...

Page 2: ... the strobe and audible are wired to operate in unison on a single circuit Table 3 dBA Multitone With Strobe Anechoic Reverberant dBA 10 dBA 10 Per UL 464 Tone Nominal Minimum Maximum Voltage Voltage Voltage HI STD HI STD HI STD Horn 99 93 85 79 88 82 Bell 92 87 79 75 82 75 March Time Horn 99 93 82 75 85 79 Code 3 Horn 99 93 79 75 82 75 Code 3 Tone 95 90 75 70 79 73 Slow Whoop 99 94 82 75 85 79 Si...

Page 3: ...TO HANDLE THE MAXIMUM INRUSH OR PEAK CURRENT FROM ALL DEVICES ON THOSE CIRCUITS FAILURE TO DO THIS MAY RESULT IN LOSS OF POWER TO THE SIGNALING CIRCUIT AND THE FAILURE OF ALL DEVICES ON THAT CIRCUIT TO OPERATE When calculating the maximum inrush use Figure 1 to determine the highest value of Rated Inrush Current for an individual strobe across the expected operating voltage range of the strobe the...

Page 4: ...ut level as follows Refer to Figure 3 Multitone Strobe Appliances cannot be field set for input voltage Multitone Strobe Appliances are field set for dBA sound output level by adjusting a four position Switch SW1 as shown in Table 5 and Figure 3 Use SW1 Position 1 to select the desired dBA sound output level Table 5 dBA Sound Output Level Settings HIGH dBA Set SW1 POS 1 1 Factory Setting STANDARD ...

Page 5: ...on signaling and not for any other purpose The Horn and Bell Tones can be used on coded systems with a minimum On Time of 1 4 second if the audible and strobe are wired to operate independently All other tones are recommended for use only on continuous non coded systems WIRING INFORMATION Audible appliance and strobe operate independently Audible appliance and strobe operate in unison Red and blac...

Page 6: ...cient space in the backbox to accommodate the field wires and stresses from the wires could damage the product Although the limits shown for each mounting option comply with the National Electrical Code NEC Wheelock recommends use of the largest backbox option shown and the use of approved stranded field wires whenever possible to provide additional wiring room for easy installation and minimum st...

Page 7: ... of the box Figure C Use appropriate anchors for the wood screws that are supplied with the box if necessary 6 The IOB includes a prefastened gasket and four hole plugs Make sure the condensation drain holes on the box face down and that the box is vertical to permit drainage of any moisture Use the mounting ears to secure the box do not use the back knockouts Use the hole plugs to seal the unused...

Page 8: ...FPA 72 1993 Edition NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the inst...

Page 9: ...ER SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQU...

Reviews: