Table 4:  Speaker Voltage and Wattage Connection Chart

 

Position 25V  70V 

A 2 

------ 

B 1 

------ 

C 1/2 

------ 

D 1/4 2 

E 1/8 1 
F ------ 

1/2 

G ------ 

1/4 

H ------ 

1/8 

            

              Figure 5: 

30

 CANDELA

 POINTER

INSERT 

SCREWDRIVER 

95

15

75

 

      NOTE:  

The Series E70-24MCC and E90-24MCC comes pre-set at 15cd. 

WARNING:  THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION.  

WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT “CLICKS” IN PLACE.  AFTER CHANGING 
THE CANDELA SETTING, THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION.  IMPROPER SETTING OF THE CANDELA 
SELECT SWITCH, MAY RESULT IN OPERATION AT THE WRONG CANDELA, WHICH COULD RESULT IN PROPERTY DAMAGE AND 
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 
 
MOUNTING PROCEDURES: 
 

1.

 

The E70/E90-24MCC can be flush mounted to a 4” square by 2-1/8” deep backbox with a 4” square 1-1/2” extension ring (Figure A) or surface mounted to a 
surface backbox (Figure B).  Mounting hardware for each mounting option is supplied. 

2.

 

Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product.  Do not pass additional wires (used for other 
than the signaling appliance) through the backbox.  Such additional wires could result in insufficient wiring space for the signaling appliance.  

3.

 

When terminating field wires, do not use more lead length than required.  Excess lead length could result in insufficient wiring space for the signaling appliance. 

4.

 

Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product.  This is 
especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing. 

5.

 

E70/E90-24MCC model has an integrated speaker mounting plate which must be oriented correctly when it is mounted to the backbox.  Turn the speaker 
mounting plate so that the arrow above the words “Horizontal Strobe” points to the top side of the speaker mounting plate. 

6.

 

To move selector switch, insert screwdriver into slot shown on the bottom side of the strobe.  The setting is indicated by a pointer and can be seen on the bottom 
side of the lens.  See Figure 5. 

7.

 

Mount the speaker mounting plate to the backbox.  Next slide the grille over the speaker mounting plate strobe and attach with (2) screws. 

 

WARNING:  WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING 

OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT 
CAN BE SEEN BY ALL INTENDED VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE 
THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION, REGARDLESS OF THE VIEWER'S ORIENTATION.  FAILURE TO 
DO SO COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

 

 

WARNING:  A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW, UNDER 

CERTAIN CIRCUMSTANCES, MIGHT INDUCE A PHOTO-SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY.  STROBE REFLECTIONS IN A 
GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE.  TO MINIMIZE THIS POSSIBLE HAZARD, WHEELOCK 
STRONGLY RECOMMENDS THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW 
WHICH EXCEEDS FIVE (5) Hz AT THE OPERATING VOLTAGE OF THE STROBES.  WHEELOCK ALSO STRONGLY RECOMMENDS THAT THE 
INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS, 
STANDARDS, REGULATIONS, CODES AND GUIDELINES. 
 

If this appliance is required to produce a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, the 
appliance must be used with a fire alarm control unit that can generate the temporal pattern signal.  Refer to manufacturer’s installation manual for details. 

 
NOTE:  

NFPA 72/ANSI 117.1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer, higher intensity strobes within the same protected area. 

 
 
 

CAUTION:  

Check the installation instructions of the manufacturers of other equipment used in the system for any guidelines or restrictions on wiring and/or 

locating Notification Appliance Circuits (NAC) and notification appliances.  Some system communication circuits and/or audio circuits, for example, may require 
special precautions to assure electrical noise immunity (e.g. audio crosstalk). 