Copyright 2005 Wheelock, Inc.  All rights reserved. 

 

 

 

 

 

 

 

   

P84398F 

Sheet 1 of 4 

                    

Thank you for using our products.

 

273 Branchport Avenue   
Long 

Branch, 

N.J. 

 

07740          

 

 

INSTALLATION 

INSTRUCTIONS 

(800) 

 

631-2148      SERIES 

E70-24MCC 

AND 

E90-24MCC

 

MULTI-CANDELA SPEAKER STROBE 

www.wheelockinc.com 

           (CEILING 

MOUNT 

VERSION)

 

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 

GENERAL: 

Wheelock’s Series E70-24MCC and E90-24MCC Multi-Candela Speaker Strobe is UL Listed under Standard 1971 for (Signaling Devices for the Hearing Impaired) for 
indoor fire protection service.  The Series E70-24MCC and E90-24MCC is designed for multiple power requirements with high dBA output at each power tap and 
offers a choice of field selectable taps, 1/8W to 2W, for either 25.0VRMS or 70.0VRMS audio systems.  The low profile design incorporates a high efficiency speaker 
for maximum output at minimum power across a frequency range of 400Hz to 4000Hz, and features a sealed back construction for extra protection and improved 
audibility.  The Series E70-24MCC and E90-24MCC Multi-Candela provides four selectable light output intensities in one unit and incorporates a speaker mounting 
plate attached to the speaker for ease of installation.  the low profile speaker strobe can provide a non-synchronized strobe appliance when connected directly to a fire 
alarm control panel (FACP), or provide a synchronized strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or Wheelock 
power supplies.  The Strobes use a xenon flashtube with solid state circuitry enclosed in a polycarbonate

 lens to provide maximum visibility and reliability for 

effective visible signaling.  The Series E70-24MCC and E90-24MCC is Listed for 

indoor use, ceiling mount only

 with the backboxes specified in these instructions 

(see wiring and mounting information). 

 

WARNING:  PLEASE READ THESE INSTRUCTIONS CAREFULLY.  FAILURE TO COMPLY WITH ANY OF THE FOLLOWING 

INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, CANDELA SETTING, INSTALLATION AND/OR 
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS 
INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

SPECIFICATIONS: 
 

Table 1:  UL Listed Models and Ratings 

 Speaker 

Strobe 

 

 

dBA at 10 Feet 

Regulated 

Voltage 

 

Models Voltage 

(Rated 

Watts) 

Voltage  Range 

Candela 

 (VRMS) 

1/8 

1/4 

1/2 

(VDC/VRMS) 

(VDC/VRMS)  

E70-24MCC 

 

25/70 

76  80  82 85 88 

24 

16.0-33.0 

15/30/75/95 

E90-24MCC 

25/70 

76  80  82 85 88 

24 

16.0-33.0 

15/30/75/95 

 

NOTES: 

1.

 

The strobe will produce 1 flash per second over the "Regulated Voltage" range.  

2.

 

Strobes meet the required light distribution patterns defined in UL 1971. 

3.

 

The E70/90-24MCC is UL Listed for indoor use with a temperature range of +32

°

F  to +120

°

F  (0

°

C to +49

°

C) and maximum humidity of 85% RH.  The effect of 

shipping and storage temperatures shall not adversely affect the performance of the appliance when  it is stored in the original cartons and is not subjected to 
misuse or abuse.   

4.

 

The maximum supervision voltage is 33 volts DC. 

5.

 

Frequency range of speakers is 400-4000Hz. 

 

CAUTION:  

Always operate audio amplifiers and speakers within their specified ratings.  Excessive input may distort sound quality and may damage audio 

equipment.  Do not exceed 100% of speaker input voltage per UL 1480.  Improper input voltage can damage speaker.  If distortion is heard, check for clipping of the 
audio appliance with an oscilloscope and reduce the amplifier input level or gain level to eliminate any clipping. 

 

WARNING:  CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT. 

 

Table 2:  UL Current Ratings with Strobe Only 

Maximum RMS Current (AMPS) 

UL Voltage 

15cd 

30cd 

75cd 

95cd 

DC 16-33VDC 

0.065 

0.105 

0.189 

0.249 

FWR 16-33VRMS 

0.110 

0.170 

0.280 

0.375 

 

When calculating the total currents use Table 2 to determine the highest value of RMS current for an individual strobe, then multiply these values by the total number of 
strobes.  Be sure to add the currents for any other appliances, including audible signaling appliances powered by the same source, and to include any required safety 
factors. 

NOTE:  

The maximum number of strobes on a single notification appliance circuit shall not exceed 50. 

 

 

 

CAUTION:  

These strobes are UL Listed as “Regulated”.  They are intended to be used with FACPs whose notification circuits are UL Listed as “Regulated.”  

These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the installation 
instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual. 

 

WARNING:  THESE STROBES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING 

FILTERED DC OR UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE.  DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.  

 

 

WARNING:  CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE 

VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPPLIED VOLTAGE TO THE STROBES.  THE MAXIMUM 
WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.  

 

 