38
WHL-015 REV. 1.13.17
Figure 25
– DHW Priority with Outdoor Reset, Boiler Primary Pump, and Recirculation
NOTES:
1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local
codes.
2. All closely spaced tees shall be within 4 pipe diameters center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees.
4. The
minimum
pipe size of DHW piping should be ¾” diameter and CH piping should be 1” in diameter.
5. Circulators are shown with isolation flanges. The alternative is standard flanges with full port ball valves. Purge valves can be used
with circulator flanges as an alternative.
6. Piping shown is Primary/Secondary. System flow (sec
ondary loop) must be greater than the appliance’s primary loop flow.
7. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
8.
VERY IMPORTANT
– Minimum flow rates outlined in this manual must be maintained through the heat exchanger to minimize short
cycling.
9. Each heating zone of a pump-based system has its own circulator with turns on when a zone thermostat calls for heat.
10.
Unit is equipped with built-in primary pump for the heating loop.
This pump is sized to insure proper flow rate through the
appliance heat exchanger and related piping. On long pipe runs, it is recommended to keep the pump at maximum speed (setting 3).
DO NOT lower it from the factory default.
11. To achieve 199,000 BTU/hr, install a Boiler Primary Pump.
NOTE:
RECOMMENDED PUMP: TACO 0013 or equivalent.
Boiler Primary Pump Instructions:
a. Install pump. Connect the pump to boiler terminal (2A max).
b. Go into installer menu and change 19:cb from 70 (default) to 100.
Summary of Contents for WBRC 140F Series
Page 2: ...2 WHL 015 REV 1 13 17 ...
Page 43: ...43 WHL 015 REV 1 13 17 Figure 29 140F Model Electrical Wiring Diagram ...
Page 44: ...44 WHL 015 REV 1 13 17 Figure 30 140F Model Ladder Diagram ...
Page 45: ...45 WHL 015 REV 1 13 17 Figure 31 199F Model Electrical Wiring Diagram ...
Page 46: ...46 WHL 015 REV 1 13 17 Figure 32 199F Model Ladder Diagram ...