Westinghouse HQS Installation, Operation & Maintenance Instructions Manual Download Page 2

TYPE  HQS  RELAY 

� 

T4REUY 

�:.S�AC� 

-

---

-

71/F�HS. 

FH4NT  VIEW 

SHt/ffTIItt$ SW/TDH 

WITH  /ff£i.IP71VE  INSTIPNTIPN44VS �(IJ.IIIHITY, 

THE 

H-.2() 

s.., 

S4 Go  HA�£  C:(IN:McTS  CU.(IS"£. 

Fig.  !-Internal  Schematic  of  the  Type  HQS  in  the  Type  FT 

Case. 

contacts. 

This  shunts 

the 

main 

relay 

con­

tacts, 

thereby 

relieving  them  of  the  duty  of 

carrying 

tripping 

current. 

These 

contacts 

remain 

closed 

until 

the 

trip 

circuit 

is 

opened  by  the  auxiliary  switch  on  the  breaker. 

Three  of 

these  contactor  switches  are  used, 

one 

in 

each 

of  the  three  trip 

circuits  to 

seal  in  the  trip  circuit. 

Operation  Indicator 

The  operation 

indicator  is  a  small  solenoid 

coil 

connected  in  the  trip  circuit. 

When  the 

coil 

is 

energized,  a  spring-restrained  arma­

ture  releases  the  white  target  which  falls  by 

gravity 

to 

indicate 

completion  of  the 

trip 

circuit.  The 

indicator  is  reset  from  outside 

of 

the 

case 

by 

push 

rod  in  the 

or  cover  stud. 

Three  Phase  Negative  Sequence  Filter 

cover 

The  filter  consists  of  three  mutual  reactors 

each 

with 

three 

windings  connected  as  shown 

in  Figure  2·.  With  unbalanced  three-phase  cur-

rents  flowing  in  the  input  terminals,  the  out­

put 

voltage  and  current 

will  be  proportional 

to  the  negative  sequence  components  of  the  un­

balanced 

input. 

The  detailed  explanation 

of 

the  filter  is  beyond  the  scope  of  this  leaflet 

and  is  covered 

in 

catalog 

section  41-287  on 

the  type  CRS  relay. 

CHARACTERISnCS 

The 

type 

HQS 

relay 

js  an  auxiliary  relay 

used 

in 

the  carrier  relaying  scheme  with  the 

types 

HZ ,  

HRK-P  and  RSN  relays.  There  are 

no 

settings  required. 

The 

minimum  pick-up 

of  the  type 

HQS  Relay 

and  the  filter  is  as  follows: 

Polarizing 

Winding 

Turns 

Amperes 

17 

1.0 

10 

1.3 

1.55 

2.37 

Maximum 

3Io 

Amperes 

15.0 

25.0 

32.0 

75-0 

Connection 

of  Links 

1  to  B,  2  to  3 

4  to 

1  to  B,  2  to 

3  to  B,  4  to 

2  to 

A, 

1  to  3 

to  B 

This  is  the  total 

phase  current  passed  thru 

the  filter  ana  relay  to  neutral  with  the  other 

two  phase  currer.ts  zero. 

The 

corresponsing 

negative  and  zero  sequence  values  are  each  one 

third  of  the  values  given  above. 

The 

negative  sequence  coils  of  the  type  HQS 

relay 

are 

normally  connected 

in 

star 

to 

terminals 

1, 

1, 

and  C 

of 

the 

sequence 

filter. 

The 

neutral 

of 

negative 

this  star 

should  not  be  grounded. 

The· terminals 

A", 

B", 

and  C"  should 

be 

connected 

together 

to  the 

neutral  of  the 

main  current  transformers. 

It 

is  important 

that 

no 

other  elements  be  con­

nected 

between 

A", 

B"  and  C" 

and 

the  star 

neutral  point. 

The  alternate  connection  is  used  where  other 

equipment  must  be  connected  between 

A 11, 

B"  and 

C"  and 

the 

neutral  point. 

In  this  case 

the 

negative  sequence  coils 

are  connected  between 

terminals 

A1A", 

B 1B11  and  C1C11• 

With  this  c·on-

nection 

zero 

sequence  current  must 

be 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for HQS

Page 1: ...ine current from an external SUPERSEDES I L 41 610 1B filter These zero and negative sequence elements are assembled at right angle to each other with the one turn loop in the air gaps of the negative...

Page 2: ...of the filter is beyond the scope of this leaflet and is covered in catalog section 41 287 on the type CRS relay CHARACTERISnCS The type HQS relay js an auxiliary relay used in the carrier relaying sc...

Page 3: ...remaining switches The order of opening the remaining switches is not opening the test switches important In they should be moved all the way back against the stops With all the switches fully opened...

Page 4: ...ull open position 4 the ten circuit test plug can be inserted in the contact jaws This connects the relay elements to a set of binding posts and com pletely isolates the relay circuits from the extern...

Page 5: ...the right and bridge sc the stationary contacts Reverse the connections to terminals 25 and 26 The left hand con tacts should now remain firmly closed Raise the current to 15 amperes and make sure tha...

Page 6: ...relay terminals 19 21 and 23 to 14 l I I gether With balanced three phase currents of 5 amperes 60 cycles phase rotation A B C applied to the filter input terminals A B C and the neutral made by conn...

Page 7: ...6 1 o l c 0 PANEL LOCIITION fOil PROJECTION TYPE KTQ 0 I I I PANEL LOCATION I Oit seMI F USII TVPE MTGo t l8 HTG STUD 2 Ri O Fig 4 0utline and Drilling Plan of the M20 Projection or Semi Flush Type F...

Page 8: ...WESTINGHOUSE ELECTRIC CORPORATION METER DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Reviews: