Westinghouse HKB Series Instructions Manual Download Page 4

CARRIER  RELAYING 

RESTRAINING VOLTAGE 

FROM  CARRIER 

.INTERNAL  FAULT 

I� 

WAVE  DIAGRAMS 

EXTERNAL FAULT 

LOCAL 

FILTER  OUTPUT 

LOCAL 

OPERATIN& 

VOLTA&£ 

--------- LOCAL 

CARRIER 

__.__.._. 

-------DISTANT CARRIER  _________._ 

RECTIFIED  CARRIER 

AT 

RECEIVER 

(RESTRAINING VOLTA&£> 

VOLTA&£ 

ON  &RID OF 

RELAY TUBE•(a>+<f) 

PLATE  CURRENT 

OF R

E

L

A

Y TUBE 

SEC. VOLTAGE 

,.: 

e' 

c' 

b' 
E' 

F' 

e: 

H' 

RELAY TRIP5 

RELAY 

CURRENT 

RELAY DOES NOT TRIP  I' 

Fig.  2-The  Relay  Tube  Circuit  and  Typical  Wave  Dia· 

grams  Of  The  Type  HKB  System. 

relay  tube  positive. 

The  rectified  output 

the  carrier  receiver  is  connected 

with 

of 

the 

opposite  polarity  and  i.s  sufficient  to  cancel 

the  effect  of  the  voltage  across  R'c  if  carri­

er  is  received  at  the  same  time  that  V2 

is 

conducting. 

The  voltage  drop  across  resistor 

RB 

provides  negative  grid  bias  for  the  thrya­

trons. 

The  carrier  transmitter  and  receiver 

are  conventional  carrier  relaying  units  whose 
construction 

and  principle  of  operation  are 

well  known. 

Response  To  Faults 

Figure  2  shows  in  detail  how  the  circuits 

just  described  determine·  whether  an  internal 

or  external  fault  exists. 

The 

relay-tube 

circuit  is  shown  at  the  top  of  Figure  2 

for 

convenience. 

The 

"operating  voltage 

from 

trigger  circuit"  is  the  voltage  drop  Eo  across 

"R''  RELAY 

CURRENT 

20 

180 

Fig.  3-Typical  Overall  Characteristics  of  the  Type  HKB 

System. 

R'c  of  Figure 

1. 

It  is  called  operating  volt­

age,  as  it  makes  the 

grid  of  the  relay  tube 

positive,  causing  the  flow  of  relay-tube  plate 
current. 

The  "restraining  voltage  from  carri­

er" 

is  the  d-e  output  ER  of  the  carrier  re-

ceiver  and  is  so  named  as  it 
operating  voltage  and  prevents 
plate 

current  in  the  relay  tube 

negative  potential  to  its  grid. 

opposes  the 

the  flow  of 
by  applying 

To  see  how  the  quantities 

shown  in  Figure  2 

are  utilized, consider  first  an  internal  fault. 
The  polarities  of  the  sequence-filter-output 
voltages  at  the  two  ends  of  the  line  are  such 
that,  when  the  fault  detectors  operate,  carri­
er  is  transmitted 

from  both  line  terminals  on 

the  same  half-cycles  (Figure  2,  C  and  D) . 

The 

received  and  rectified  c�rrier 

restraining 

voltage  (Figure  2,  E)  is  applied  to  the 

grid 

of  the 

relay  tube  in  series  with  the  opera­

ting  voltage  (Figure  2, 

B). 

The 

net  voltage 

on  the  grid  of  the  relay  tube  is  the 

sum  of 

these  two  voltages,  and  has  the  wave  form  in­
dicated  at  F  on  Figure  2. 

The  reference  axis  at  F  is  the  voltage 

Ec 

required  to  cut  off  the  plate  current  of  the 
relay  tube. 

Consequently, 

when  the  net  grid 

voltage  is  above  this  axis, 

plate  current 

flows. 

For  an  internal  fault, 

there  is  no 

rect�fied  carrier  voltage  during  the  half­
cycles  that  the  grid  of  the  relay  tube  is  made 

www . ElectricalPartManuals 

. com 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for HKB Series

Page 1: ...es place in the grid circuit of a vacu m tube which is NEW INFORMATION so biased that no plate current flows when there is no filter or carrier voltage on its control grid The polarity of the filter a...

Page 2: ...should trip the breaker 3 A coupling capacitor with carrier aux 4 iliary for introducing the carrier fre quency on to the transmission line This may be supplied with a potential device for obtaining...

Page 3: ...FD2 is set to trip 25 ercent above tap value and supervises the operation of the tripping relay element R through the relay tube This tripping of the line breaker cannot occur until FDl and FD2 have...

Page 4: ...age drop Eo across 4 R RELAY CURRENT 20 180 Fig 3 Typical Overall Characteristics of the Type HKB System R c of Figure 1 It is called operating volt age as it makes the grid of the relay tube positive...

Page 5: ...tivity the relay R can be set to operate when the angle between the currents at the two ends of the line becomes any desired value such as 35 degrees as shown The preceding explanation is based on sin...

Page 6: ...nnel can be used for other func tions such as telemetering load communication supervisory control tripping Fore these functions lead from the oscillator plate control and remote a separate circuit is...

Page 7: ...laying equipment This can be done by plugging a hand set at the carrier set at the relay switchboard or rrom a desk set permanently wired to the equipment The push to talk type or communication is emp...

Page 8: ...WESTINGHOUSE ELECTRIC CORPORATION METER DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Reviews: