Westinghouse DB-75 Instructions Manual Download Page 20

MAINTENANCE 

On  larger  overload  currents,  the  action  is 

essentially  the  same  as  above  except  that  the 
moving  armature  (B)  will  close  completely  as 
soon  as  the  overload  is  applied. 

When  the 

armature  closes,  it  compresses  spring  (C) 
which  applies  a  force  to  diaphragm  (D).  After 
a  time  delay  determined  by valve  (F),  the  dia­
phragm  movement  permits  the  spring  to  rotate 
the  trip  crank 

(J) 

f ar  enough  to  trip  the 

breaker  by  moving  the  trip  lever 

(K) . 

Large  fault  currents  cause  the  instantane­

ous  armature  (M)  to  close  immediately. 

This 

armature  lifts  the  trip  crank 

(J) 

without  any 

delaying  action  and  trips  the  breaker. 

Selective  Overcurrent  Tripping  Device 

(Refer  to  Figure  9A) 

For  small  and  intermediate  overloads,  the 

operation  of  this  device  is  the  same  as  for 
the  standard  overcurrent  tripping  device. 

However,  the  selective  o vercurrent  tripping 

device  operates  differently  when  large  fault 

currents  occur. 

When  the  fault  current  is  large  enough  to 

close  the  short  delay  armature  (M),  the  link­
age  attached  to  the  armature  opens  valve  (P) 

which  permits  air to enter  the  diaphragm  cham­
ber  at  a  much  faster  rate  than  through  the 
long  delay  valve  (F).  Tripping  is  then  accom­

plished  by  the  same  means  as  though  a  small 

overload  had  occurred. 

That  is;  the  main 

armature  (B)  has  closed,  pulling  on  the  com­

pression  spring  (C)  which  is  restrained  by 

diaphragm  (D)  until  sufficient  air has  entered 
valve  (P)  to  permit  the  spring  assembly  (C) 

to  lift  crank 

(J) 

and  trip  the  breaker  by  ro­

tating  the  trip  finger 

(K) . 

A  discriminator  arm  is used  on the selective 

overcurrent  trip  units  to make  the  unit  behave 

as  an  instantaneous  type  trip  unit  while  the 
breaker  is being  closed  and  for  a  short  inter­
val  of  time  after  closing. 

This  is  achieved 

b�  having  a  discriminator  latch  connection 
between  the  short  delay  armature  bracket  and 

the  trip  crank. 

When  this  latch  is  engaged, 

the  short  delay  armature  will  lift  the  trip 
crank  directly  if  the  current  is  greater  than 

20 

the  short  delay  pick-up  setting. 

If  the  cur­

rent  does  not  rise  above  this  value,  then  the 

breaker  remains  closed  and  the  discriminator 

arm  disengages the discriminator  latch  so  that 

the  trip  unit  will  then  revert  to  its  normal 
f unction  as  one  having  long  and  short  time 
d elay  characteristics. 

Instantaneous  Overcurrent  Tripping  Device 

(Single  Element) 

This  device  operates  in  an  instantaneous 

manner  to  trip  the  breaker  at  any  time  when 

the  current rises above the calibrated  setting. 
The  main  armature  (B),  of  Figure  7A,  is  modi­
fied  so  that  it  lifts  the  trip  crank-

(J) 

and 

trjps  the  breaker  directly. 

The  operation  is 

similar  to the  instantaneous  trip  of the  stand­
ard  overcurrent  tripping  device. 

FIG.  lOA - SCHEM ATIC  DIAGRAM  OF 

OVER CURRENT TRIPPING  DEV ICE  WITH 

INSTANTANEOUS  ELEMENT  ONLY 

I.B. 

35-240-1 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for DB-75

Page 1: ...s A C 250 Volts D C INTERRUPTING RATING 75 000 Amperes 600 Volts A C 100 000 Amperes 250 Volts A C November 1956 I B 35 240 1 I WESTINGHOUSE ELECTRIC CORPORATION i 11 Switchgear Division East PittSburgh Plant eel East Pittsbu gh a Jil Ji w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 2: ...tion 4 Time current Characteristics 5 Adjustment of Calibration Settings 6 Maintenance Control Relay Shunt Trip Attachment Undervoltage Trip Attachment Undervoltage Time Delay Attachment Auxiliary Switch Alarm Switch Attachment Electric Lockout Attachment Key Lock Attachment Key Interlock Attachment Rectifier Unit for A C Undervoltage and A C Electric Lockout Attachments 7 11 11 12 12 12 12 15 15 ...

Page 3: ... lOA lOB 11 12 13 14 15 16 17 18 19 Overcurrent Tripping Device with Long Delay and Short Delay Elements Schematic Diagram of Overcurrent Tripping Device with Instantaneous Element Only Typical Time Current Characteristics of overcurrent Tripping Device with Instantaneous Element Only Control Relay Construction Details Shunt Trip Attachment Construction Details Undervoltage Trip Attachment Constru...

Page 4: ...I B 35 240 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 5: ...mounted in an enclosure suitable to local operating conditions A selection of standard enclosures is available for various applications IMPORTANT To assure proper functioning inspect each breaker at regular intervals in accordance with a systematic maintenance schedule The frequency and character of the inspections will for the most part be determined by the severity of the duty performed The mini...

Page 6: ...ns for proper operation should therefore be made with the breaker in this position Final inspection should preferably b e made with the breaker in its permanent mounting 6 2 Remove anyforeign particles from the hinge end of the moving contacts 3 Insert the maintenance operating handle and slowly close the breaker a Observe whether all parts are in proper alignment and move freely b Be sure that th...

Page 7: ...s and 3 completing any secondary control w iring that may be necessary CAUT ION DUR ING INSTALLAT ION THE C IRCU IT BREAKER SHOULD BE IN THE OPEN POS IT ION Be sure to de energize the load and control leads to be connected and also the section of the switchboard where installation is being made Mounting dimensions and details of the front enclosure cutouts are shown in Figure 1 To prevent distorti...

Page 8: ... BUILDER 1 J l I li 10 II I I riJ POSITION INDICATOR ADDITIONAL 4 POLE AUXILI ARY SWITCH 4 POLE AUXILIARY SWITCH Z4 DIA 6 MOUNTING HOLES f J 2 LIFTING BRACKET DOOR OR FRONT COVER SUPPLIED BY SWITCHBOARD BUILDER BOUNDARY SURFACES OF THE CIRCUIT BREAKER ARE TO BE CONSIDERED GROUND POTENTIAL PROVISION FOR PADLOCKING BREAKER L IN TRIPPED POSITION PADLOCKS FURNISHED BY CUSTOMER FIG 1 DB 75 OUTLINE AND ...

Page 9: ... O OI 2J x coNTROL RE LAY 1 0 G 1 1 460 VAG 1 810317 o 03J cc cLOSING COIL I J FUSES TC TRIP COIL 125VDC X I T GONT V RATING cs coNTROL SWITCH 250VDC c I 2oe VAC R RED LAMP CLOSED 208VAC X l 230 VAG 4 0A 600V G GREEN LAMP OPEN g 4 TC 460 VAG U V UNDER V OLTAGE 125 VAG 30A 250V LO LOCKOUT l 1 250 VAG 15A 250V AS ALARM SWITCH o o MAKE CONTAC _r _yg _ bZ b BREAK CONT _ b __ CONTROL VOLTAGE SCHEMATIC ...

Page 10: ...00 VOLTS A C CLOSING SOLENOID POLE UNIT MECHANISM CLOSED ARC CHUTE ALUMINUM PANEL TRIPPED OVERCURRENT TRIPPING DEVICE OPEN RESET FIG 3 CROSS SECTIONAL VIEW OF DB 75 CIRCUIT BREAKER 10 I B 35 240 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 11: ...lowing order 1 Turn adjusting n uts A on insulating links to vary main contact pressure Use 005 feeler gauge 1 4 inch wide by 6 inches long inserted as shown in Figure 4A to check clearance Feeler X above contact fingers insures that they have all been deflected Feeler Y inserted below fingers insures that they have not gone solid 2 Check clearance between cam B and roller C located between insula...

Page 12: ... up and then drive the pin to the right just far enough to clear the moving core rod Lower the moving core until it hits its stop Drive the pin to the left into its original posi tion 5 Remove the four mounting bolts a CAUTION THESE BOLTS ARE ALSO THE MOUNT ING BOLTS FOR THE CLOSING SOLENOID THEREFORE SUPPORT THE SOLENOID WHILE REMOVING THE BOLTS n Remove the Mechanism The mechanism is factory 1 u...

Page 13: ... I I I I I I Jl_ I I I II I I 1 I I II 1 I I II I I I II I I I 1 II I 1 I II I I 1 I II I 11 I I II I I II II I I I I II II II I I II I r I I II I I I I I II I I I I II I 1 I II I I I l i I i i I l11 u l II II o II C I i l II II I I 0 l t til I II Jt I I I II I 0 z 0 n 0 n c l til 0 i l i l 0 w E l e c t r i c a l P a r t M a n u a l s c o ...

Page 14: ...INSTA NTANEOUS PICK UP CAL IBRATION SPRING INSTANTANEOUS STAT IONARY MAGNE T t LONG DELAY STAT IONARY MAGNET t r I L L 7 v rT I t I L _ J l j h r _ __ __ LOW I r ER BREAKER STUDS I I j i L r J k _POLE UNI T BASE CJ 1 1 I i DIAPHRAGM AIR FILTER LONG DELAY VALVE AND DIAL FIG 6 CROSS SECTIONAL VIEW OF OVERCURRENT TRIP PING DEVICE WITH LONG DELAY AND INSTANTANEOUS ELEMENTS a z tzl z z tzl w E l e c t ...

Page 15: ...ly equal when the main armature is closed Then tighten all four mounting bolts securely Adjustment of Trip Screw The trip screw mounted on the trip finger must be adjusted properly to obtain proper tripping CAUTION SINCE THIS ADJUSTMENT INVOLVES TRIPPING THE BREAKER CARE MUST BE TAKEN TO KEEP FINGERS AND FACE AWAY FROM ALL CONTACT ARMS AND OPERATING LINKAGE To proceed with the adjustment turn the ...

Page 16: ...ANEOUS PICK UP CALIBRATION SPRING R BREAKER MOVING CONTACT ARM W SHAFT 11 LONG DELAY PICK UP ADJUSTMENT RESETTABLE DELAY f LONG DELAY TIME ADJUSTMENT GUIDE BEARING _j_ SOLID JOINT PINNED JOINT I 1 NO JOINT mJm_ STOP SURFACE Q ADJUSTABLE SCHEMATIC DIAGRAM 16 CURRENT MAGNITUDE TYPICAL TRIPPING CHARACTERISTICS FIGURE 7B FIGURE 7A FIG 7 SCHEMATIC AND TYPICAL TIME CURRENT CHARACTE RISTICS OF OVE RCURRE...

Page 17: ...ER LONG DELAY ARMATURE T DELAY ARMATURE PART S WHICH DISCRIMINATE BETWEEN A BREAKER IN CLOSED POSITION B BREAKER OUR lNG PERIOD OF C LOSING L ARRANGED FOR LONG DELAY AND SHORT DE LAY TRIPPING ARRA NGED FOR LONG DELAY AND INSTA NTANEOUS TRIPPING o 0 t l t l o l t l t l 0 z a n a n c o l a t l t l a w E l e c t r i c a l P a r t M a n u a l s c o ...

Page 18: ...OR T DEL A Y OVER TRAVEL SPRING LONG DELAY FORCE LIM ITING SPRING LONG DELAY PICK UP CALIBRATION SPRING SHORT DELAY PICK UP CALIBRATION SPRING _ __ j j __L WE BREAKER t I STUDS I ME J j I DISCRI PISTON MINATOR Tl I DELAY L_ _ f POL E UNIT BASE r 1 w N J DIAPHRAGM AIR FILTER SHORT DELAY VALVE __ LONG DELAY VALVE AND DIAL FIG 8 CROSS SECTION AL VIEW OF OVERCURRENT TRIP PING DEVICE WITH LONG DELAY AN...

Page 19: ... A BREAKER MOVING CONTACT ARM S DISCRIMINATOR ROLLER T DISCRIMINATOR TIME DELAY PISTON U DISCRIMINATOR LEVER V DISCRIMINATOR LATCH W SHAFT I I t 1 LONG DELAY PICK UP ADJUSTMENT RESETTABLE DELAY I I I I I I I I I I I TOTAL CLEARING TIME f t LONG DELAY TIME ADJUSTMENT DELAY PICK UP ADJUSTMENT GUIDE BEARING _j_ SOLID JOINT PINNED JOINT NO JOINT 1 STOP SURFACE ADJUSTABLE SCHEMATIC DIAGRAM CURRENT MAGN...

Page 20: ...ring C which is restrained by diaphragm D until sufficient air has entered valve P to permit the spring assembly C to lift crank J and trip the breaker by ro tating the trip finger K A discriminator arm is used on the selective overcurrent trip units to make the unit behave as an instantaneous type trip unit while the breaker is being closed and for a short inter val of time after closing This is ...

Page 21: ...resents the minimum time for the breaker to clear when fault currents exceed ten times the trip unit rating S ELECTIVE OVERCURRENT TRIPPING DEVICE Refer to Figure 9B The time current characteristic of this trip unit is the same as the standard device except that the position of the flat portion of the curve can be shifted as indicated by the number 3 This adjustment can be made b y changing the se...

Page 22: ... dl_____ l fF r ll 4 I u _ I RELAY TOGGLE _ Lt ARC j RELEASE CHAMBER RElAY TRIP J CLOSING SOlENOID BRACKET MOVING CORE A C OPERATING SOLENOID C8J l STATIONARY CONTACT D C OPERATING SOLENOID RELAY TRIP PIN BLOWOUT COIL FIG 1 1 CONTROL RELAY CONSTRUCTION DETAILS J z z z n E l e c t r i c a l P a r t M a n u a l s c ...

Page 23: ...igure 12 mounts on top of the platform immediately to the right of I I I I I I I 0 I I I the operating mechanism It is non adjustable and is intended for intermittent duty only The shunt trip circuit must always be open by an auxiliary switch contact Inspecti on With the breaker in the open position m anually pull the shunt trip moving core against the stationary core and manually at tempt to clos...

Page 24: ...rotates the pin pushes against the latch to release it from its latch plate When the latch releases the trip spring rotates the trip lever to trip the breaker The linkage is reset by the c ross bar as the breaker opens Always connect the coil to the line side o f the breaker unless the attachment is equipped with time delay device In this case the time delay will delay the tripping of the breaker ...

Page 25: ...D C 2 1 75 115 v A C 75 15 450 v A C 25 5 Inspection Hold the U V trip lever down and close the breaker manually Release the trip lever slowly allowing the undervoltage trip spring to rotate the trip rod and trip the breaker after a time delay CAUTION DO NOT USE YOUR FINGERS TO HOLD AND RELEASE THE U V RESET LEVER Maintenance Check for loose bolts and faulty coils The switch is a shaft operated 4 ...

Page 26: ...Note that the alarm contacts do make contact Maintenance Clean the alarm contacts when necessary Check for loose bolts 26 ELECTR IC LOCKOUT ATTACHMENT The electric lockout Figure 17 mounts on the top of the platform on the extreme left side and behind the auxiliary switches Its function is to hold the breaker open trip free until the lockout coil is energized The lockout coil can be de energized a...

Page 27: ...35 240 1 TYPE DB 75 DE ION AIR CIRCUIT BREAKER I I r I C _ lli____ _ 1 w Q z 0 i u l et f z 0 u 1 z w z u I z u 1 V et J ci u 27 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 28: ...MAINTENANCE rr I ll_ 28 H M1 T IT V J 1 w Cl z 1 L V l z 0 Ul 1 z w e c u 1 5 I u 0 l l C u e 1 u w l w _ ci LL B 35 240 1 I w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 29: ... B 35 240 1 TYPE DB 75 DE ION AIR CIRCUIT BREAKER ln I I I I I J LRfl I I V J 1 w 0 z 0 1 u 0 I V z 0 u 1 z w 1 u 1 u 0 J 0 w 1 z w 0 0 u 0 J w u 29 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 30: ...key interlock attachment the key cannot be removed unless the breaker is locked in the open position Inspection Push the trip button and turn key to the locked position The key is then removable and the breaker is locked in the trip free position Replace the key and rotate to the 30 RECTIFIER UNIT FOR A C UNOERVOLTAGE AND A C ELECTRIC LOCKOUT ATTACHMENTS When an a c undervoltage attachment or an a...

Page 31: ..._ _ iEf4 i I II II u TERMINAL BLOCK RECTIFIER TO UV AND OR LO TRANSFORMER TO AC VOLTAGE SOURCE SCHEMATIC FIG 19 FIG 19 RECTIFIER UNIT FOR A C UNDERVOLT AG E AND ELECTRICAL L OCKOUT ATT ACHMENTS _ _ _ ________ _ ____ ___ _ ___ o o i CC l l t 1 til t 1 l l 0 z a a c o i til a l l l l a E l e c t r i c a l P a r t M a n u a l s c ...

Page 32: ...t l J f f w m _ r W Cfttz 7 jHS R u w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Reviews: