Westinghouse CN-33P Instructions Manual Download Page 8

Curve 

471108 

Fig.  7  Typical  Trip  Phase  Angle  Curve  for  the  CN33P  Relay- Low  Current  Values. 

zero,  the  moving  contact  will  move  away  from  the 

stationary  CLOSE  contact  and  take  up  a  position 
somewhere  between  it  and  the  stationary  TRIP 

contact. 

When  the  feeder  breaker  opens,  the  transformer 

will  be  magnetized  from  the  network. 

This  flow  of 

exciting  current  from  the  network  to  the  transformer 
bank  will  cause  enough  current  to  flow  in  the  current 

coils  in  the  type  CN33P  relay  to  produce  a  tripping 

torque  sufficient  to  close  the  TRIP  contacts.  This 

energizes  the  BN  relay  which  will  trip  the  breaker 

when  its  timer  contacts  have  closed. 

The  timer 

contacts  are  shunted  by  the  instantaneous  triP  con­

tacts  which  close  when  the  reverse  current  exceeds 
their  setting. 

Fig.  4  shows  the  phasing  coils  short  circuited 

through  a  resistance  by 

52ri 

contacts  when  the 

breaker  is  closed. 

This  circuit  is  used  to  obtain 

the  desired  tripping  phase  angle  characteristic. 

CHARACTER ISTICS 

Figures  5,  6  &  7  show  the  operating  character­

istics  of  the  type  CN33P  primary  network  relay  for 

balanced  3  phase  conditions. 

Fig. 

shows  the 

closing  characteristics  of  the  relay.  For  curve  #lA, 

lines  drawn  from  the  origin  at  various  angles  with 

respect  to  the·  network  voltage  represent  both  in 

magnitude  and  phase  position  the  transformer  voltage 
which  will  produce  a  torque  in  the  relay  just  suffi­

cient  to  cause  its  CLOSE  contacts  to  make. 

Any 

transformer  voltage  which  does  not  terminate  on  or 

above  the  closing  curve  will  produce  a  relay  torque 

in  the  tripping  direction.  Curve  #lA  in  fig. 

shows 

a  small  section  of  the  closing  curve  plotted  to  a 

much  larger  scale  so  as  to  show  the  characteristics 

of  the relay  for  the values  of  phasing  voltage  at  which 
it  normally  operates. 

Lines  drawn  from  the  origin 

to  this  curve  represent  in  magnitude  and  phase  po­

sition  the  phasing  voltage  (the  voltage  across  the 
open  breaker)  necessary  to  produce  a  torque  in  the 

relay  just  sufficient  to  make  its  CLOSE  contacts. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for CN-33P

Page 1: ...n knife edge bearings Since this type of bearing is placed at the center of the shaft friction is reduced to a minimum Phosphor bronze retaining rings encircle the ends of the drum shaft End thrust is...

Page 2: ...CONTACT STATIONARY MOVING C ONTACTS TRIP CONTACT STATIONARY SPIRA L SPRING ADJUSTER FRONT BEARING TRIP CURR ENT ADJUST ING PINION COUNTER WE IGHTS CLOSING VOLTAGE ADJUSTING SPRING CLOS ING VOLTAGE AD...

Page 3: ...1 TERMINAL SCREW Fig 2 Type CN33P Relay Rear Cutaway View DAMPING M AGNE T VOLTAGE COIL ASSEMBLY REAR B EA RING CURRENT 8 PHASING COIL ASSE MBLY MOV ING E LEMENT STOP D R UM 3 w w w E l e c t r i c a...

Page 4: ...mly into engagement with their associated jaws These jaw assemblies are free to move in their molded insulation blocks so as to be self aligning The heads of all terminal screws are accessible from th...

Page 5: ...VICE NUMBER CHARTS FOR FT TEST SWITC H DEVICE FOR RELAY NUMBER TS T THERMAL TS NI NETWORK TS N2 NETWORK TS P PHASING r f ill 52Z 52Z 57 52Z 52Z 52Z 57 9 9 5 7 57 T T l 12 l 2K 3 1K 1 2K f I S T N2 G H...

Page 6: ...330 340 380 0 10 2 0 30 320 310 290 280 260 100 2 50 130 140 210 200 190 180 170 160 150 Curve 471102 Fig 5 Typical Closing Phase Angle Curve lor the CN33P Relay 6 w w w E l e c t r i c a l P a r t M...

Page 7: ...sing voltage will be zero In this case there will be no electrical torque produced except the voltage only torque produced by the potential coils This torque is suf ficient to overcome the tension of...

Page 8: ...circuit is used to obtain the desired tripping phase angle characteristic 8 CHARACTER ISTICS Figures 5 6 7 show the operating character istics of the type CN33P primary network relay for balanced 3 ph...

Page 9: ...nly torque is overcome and the TRIP contacts close when 2 4 rna in phase current flows toward the transformer SETTINGS Set the voltage closing adjusting screw for the desired value Adjustment range is...

Page 10: ...Mechanical Adjustment A Set contacts See Settings The moving contacts 10 are adjusted such that the contact springs are just touching their support Just touching is determined as follows With the rel...

Page 11: ...milliamp three phase If the trip cur rent is not within this range the following re adjustments should be made a If the trip current is high change the spiral spring setting by turning the pinion one...

Page 12: ...WESTINGHOUSE ELECTRIC CORPORATION RELAY DEPARTMENT NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Reviews: