Installation and Maintenance
9
●
Select the installation location as shown in Fig 3.2:
(A) Minimum Clearance
(B) Down Slope Pitch of Drain Piping:1/25
~
1/100
●
Consider the air distribution from the indoor unit to the space of the room, and select a suitable location so that
uniform air distribution can be achieved in the room. It is recommended that the indoor unit is installed
8 ft. (2.5m) to 10 ft. (3m) from the floor level.
●
Do not install flammable items in the service space for the indoor unit.
●
Avoid obstacles which may obstruct the air intake or the air discharge flow.
3
●
Do not install the indoor unit in a machine shop or kitchen where oil vapor or mist flows through the indoor unit.
The oil will deposit on the heat exchanger, thereby reducing the indoor unit performance, and in severe cases,
damaging the indoor unit.
●
Pay attention to the following points when the indoor unit is installed in a hospital or other facilities with
electromagnetic waves from medical equipment:
(A) Do not install the indoor unit where the electromagnetic wave is directly radiated to the electrical box,
remote control cable or remote control switch.
(B) Install the indoor unit and components at least 10 ft. (3m) from the electromagnetic wave source.
(C) Instal the remote controller within a field provided and installed steel box. Prepare a steel case and install
the remote control switch in it. Install remote controller wire with a steel electric conduit. Connect a ground
wire to both the box and the tube.
(D) Install a noise filter when the power supply emits harmful noises.
●
To avoid any corrosive chemical reaction at the heat exchanger, do not install the indoor unit in an acid or alkaline
environment. If the indoor unit has to be installed in such environments, use corrosion-proof type unit.
Ensure that the below calculated number is within a concentration of refrigerant gas higher that
0.3kg/m3 in an enclosed space is harmful and can cause injury.
the
Model Capacity
(Btu/h)
H
in. (mm)
9K~12K
9-5/8
(245)
18K~24K
9-3/4
(248)
36K
11-3/4
(298)
3/8 in. to 3/4 in. (10mm to 20mm)
H
0.3 kg/m³
≤
WARNING
Summary of Contents for 18K-24K
Page 1: ......
Page 20: ......
Page 21: ... ...
Page 22: ...7 7 8 8 13 16 16 ...
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ...7 ...
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ...Fig 4 2 Apriete de la tuerca c nica ...
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ...6 4 7 ...
Page 40: ......
Page 41: ......
Page 42: ...7 7 8 8 13 16 16 ...
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ...6 4 7 ...