background image

Stove Performance & testing

Westfire UNIQ 33 & 34 have been approved in accordance with EN 13240.

Preparatory work and safety checks
Important warning

This stove must not be installed into a chimney that serves any other heating appliance. There must not be an
extractor fan  itted in the same room as the stove as this can cause the stove to emit fumes into the room.

Chimney
chimney connection
Flue diameter 150mm (175cm2)

Important

: When installing the UNIQ 33 & 34 wood stoves remove steel retaining bar across flue exit. Remove bolts in

collar and remove bar, replace  cast collar  and bolt down securely.

In order for the stove to perform satisfactorily the chimney height must be sufficient to ensure an adequate
draught so as to clear the products of combustion and prevent smoke problems into the room.

Minimum draft: UNIQ 33, 34 stove has been tested with a draft of 12 Pa. Maximum draft 25 Pa.
Flue gas flow 6.0 g/sec.

Flue gas temperature 267°C. approximately 12 Pa.

NOTE: A chimney height of not less than 4.5 metres measured vertically from the outlet of the stove to the top of
the chimney should be satisfactory. Alternatively the calculation procedure given in BS 5854:1980 may be used as
the basis for deciding whether a particular chimney design will provide sufficient draught.

The outlet from the chimney should be above the roof of the building in accordance with the provisions of Building
Regulations Approved Document J.

If installation is into an existing chimney then it must be sound and have no cracks or other faults which might allow
fumes into the house. Older properties, especially, may have chimney faults or the cross section may be too large i.e.
more than 160 mm x 160 mm. Remedial action should be taken, if required, seeking expert advice, if necessary. If it is
found necessary to line the chimney then a flue liner suitable for solid fuel must be used in accordance with Building
Regulations Approved Document J.
Any existing chimney must be clear of obstruction and have been swept clean immediately before installation of the
stove. If the stove is fitted in place of an open fire then the chimney should be swept one month after installation to
clear any soot falls which may have occurred due to the difference in combustion between the stove and the open fire.

If there is no existing chimney then either a prefabricated block chimney in accordance with Building Regulations
Approved Document J or a twin walled insulated stainless steel flue to BS 4543 can be used. These chimneys must be
fitted in accordance with the manufacturer’s instructions and Building Regulations.

A single wall metal flue pipe is suitable for connecting the stove to the chimney but is not suitable for using for the
complete chimney. The chimney and connecting flue pipe must have a minimum diameter of 150 mm and its
dimension should be not less than the size of the outlet socket of the stove.

Stove model 

Weight 

Nominal heat output

Wood <20% 

smokeless fuels

UNIQ 33 

118 kg 

6.1 KW 

N/A

UNIQ 34 

124 kg 

6.1 KW 

N/A

Any bend in the chimney or connecting flue pipe should not exceed 45°. 90° bends should not be used.

If it is found that there is excessive draught in the chimney then either an adjustable flue damper or alternatively
a draught stabiliser should be fitted. The adjustable flue damper should not close off the flue entirely but should
in its closed position leave a minimum continuous opening free area of at least 20 % of the total cross sectional
area of the flue or flue pipe.

Adequate provision e.g. easily accessible soot door or doors must be provided for sweeping the chimney and
connecting flue pipe.

distance to combustible materials
Combustible materials should not be located where the heat dissipating through the walls of fireplaces or flues
could ignite it. Therefore when installing the stove in the presence of combustible materials due account must be
taken of the guidance on the separation of combustible material given in Building Regulations Approved Document J
and also in these stove instructions.

Hearth
The hearth should be able to accommodate the weight of the stove and its chimney if the chimney is not
independently supported.

The Westfire UNIQ 33, 34 wood stove has been tested and is suitable to be installed on a 12mm non combustible
plate such as Westfire 12mm glass plates or 20mm slate plates. Installation of all hearths should comply in size
and construction so that it is in accordance with the provisions of the current Building Regulations Approved
Document J.

The clearance distances to combustible material beneath, surrounding or upon the hearth and walls adjacent to
the hearth should comply with the guidance on the separation of combustible material given in Building Regulations
Approved Document J and also in these stove instructions.

If the stove is to be installed on a wooden floor, it must be covered with a non-combustible material at least
12mm thick, in accordance with Building Regulations Approved Document J, to a distance of 30 cm in front of the
stove and 15 cm to each side measuring from the door of the combustion chamber.

Combustion air supply
In order for the stove to perform efficiently and safely there should be an adequate air supply into the room in
which the stove is installed to provide combustion air. This is particularly necessary if the room is double-glazed
or a flue draught stabiliser is operating in the same room as the appliance. The provision of air supply to the
stove must be in accordance with current Building Regulations Approved Document J. An opening window is not
appropriate for this purpose. Air inlets must be positioned in such a way that they cannot be blocked. An air inlet
may be a vent (the vent must be open and the capacity of the vent sufficient when the stove is lit) or a fresh air
system linked to the stove.

The UNIQ 33 & 34 are available with a closed air supply collar (additional item) this enables the stove to take
combustion air directly from outside with a 100 mm pipe from the stove.

There are no European rules regarding the minimum distance to non-flammable walls, Westfire recommend leaving a
gap of at least 10 cm behind and to sides of stove.

UNIQ 33,34 side glass

Distances to flammable materials/furniture   

 

 

 

 

 

 

                     1000 mm

Distance to combustible materials side std/sideglass                                                       

               350/450 mm

Distance to combustible materials rear 

 

 

 

 

 

 

 

 

 

200 mm

Summary of Contents for WF UNIQ 33

Page 1: ......

Page 2: ......

Page 3: ...ns Special care must be taken when installing the stove such that the requirements of the Health and Safety at Work Act are met Handling Adequate facilities must be available for loading unloading and site handling Fire cement Some types of fire cement are caustic and should not be allowed to come into contact with the skin In case of contact wash immediately with plenty of water Asbestos This sto...

Page 4: ...xceed 45 90 bends should not be used If it is found that there is excessive draught in the chimney then either an adjustable flue damper or alternatively a draught stabiliser should be fitted The adjustable flue damper should not close off the flue entirely but should in its closed position leave a minimum continuous opening free area of at least 20 of the total cross sectional area of the flue or...

Page 5: ...ld be well ventilated During the process it is important to open and close the stove door periodically every 30mins during the first couple of firings therefore preventing the door seal cord around the door from sticking and coming away from the door Once the Heat resistant paint has hardened the stove door must be kept closed except when lighting the stove adding firewood or removing ash in order...

Page 6: ...mbers can remain hot for over 24 hours To clean the outside of the stove use a dry cloth annual service The inside of the stove should be serviced cleaned once a year To clean the inside remove all ash soot and tar residue from the combustion chamber Remove insulated chamber panels and baffle dirt and soot will collect be hind it and this must be cleaned out Insulated panels may crack if hit too h...

Page 7: ...installer may have fitted a permanent air supply vent into the room in which the stove is installed to provide combustion air This air vent should not under any circumstances be shut off or sealed Warning note Properly installed operated and maintained this stove will not emit fumes into the dwelling Occasional fumes from de ashing and re fuelling may occur However persistent fume emission is pote...

Page 8: ... of stove Hold baffle in place and push in two securing pins into side bricks Rest baffle on pins Place front and rear base bricks 05 in place Fit log retaining bars 12 Place one side brick 04 in place Sloping section to rear of stove While holding upper baffle brick in place fit second side brick 04 ensuring upper baffle is securely in place Place two base bricks 07 and grate support 10 on base o...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ......

Reviews: