![Westermo ODW-631 User Manual Download Page 9](http://html1.mh-extra.com/html/westermo/odw-631/odw-631_user-manual_960407009.webp)
9
6650-2241
Point-to-point communication via fibre optical network
The serial data is transferred via a fibre optic network between two ODW-631s.
This application is useful e.g. for long distance communication, where electromagnetic
interference may occur or when isolation of the electrical network is needed. The maxi-
mum optical fibre distance between two units depends on selected fibre transceiver and
fibre type. Distance up to 80 km (50 miles) are available.
Note! The bi-di transceivers must always be used in pair, see example:
TX 1310 nm
RX 1310 nm
RX 1550 nm
TX 1550 nm
POWER
CH 1
COM +VA +VB COM
POWER
CH 1
COM +VA +VB COM
TX
RX
TX
RX
Fibre optical connection
at point-to-point communication
POWER
CH 1
COM +VA +VB COM
POWER
CH 1
COM +VA +VB COM
TX/
RX
TX/
RX
Fibre optical connection
at point-to-point communication (Bi-di transceiver)
Bi-di transceiver, TX 1310 nm,
RX 1550 nm.
Bi-di transceiver, TX 1550 nm,
RX 1310 nm.
Serial data transfer can be set in two modes:
Syncronous mode: Transfer special protocols such as Manchester coded protocol.
…
See special switch settings on page 19.
Asyncronous mode: Data will be sent over the fibre optic network when a start-
…
bit has been identified. The data rate and number of data bits should be set by
DIP-switches. The turning time (from sending serial RS-485 data until changing to
receive mode) is automatically calculated from the DIP-switch setting.