10
6651-22631
Failure
Indications
Fibre interruption ring A, TX
On: FL R
Fibre interruption ring A, RX
On: FL L
Fibre interruption ring A, RX & TX
On FL L
Fibre interruption ring B, TX
On: FL R
Fibre interruption ring B, RX
On: FL L
Fibre interruption ring B, RX & TX
On: FL L
Fibre interruption ring A and B
(e.g. CH1 or CH2 both TX & RX)
On: FL L &/or FL R
Low power on the receiver (May indicate bad fibre)
FLL flicker
… Recovery from faulty status
• ODW-620-F2 will automatically recover to the previous operating status when a
failure disappears. This involves recovery from multi drop application to Redundant
ring A/B when ring is up and running and recovery from Ring B to Redundant ring A
when the ring is up and running.
• The time to recover from the failure status depends on total length of fibre ring.
This is typically 40–500 ms. During that time the transferred data frames should be
seen as corrupted or missed.
• When the “first” ODW-620-F2 unit receives the master frame (the same frame
that has been transmitted by this unit), or after a timeout, data conversion will be
allowed again. The received slave frame will be converted and transmitted at the
electrical port.
• When the ODW-620-F2 unit, connected to the PLC slave receives the slave frame
(the same frame that has been transmitted by this unit), or after a timeout, data
conversion at this unit will be allowed again.
… Behaviour under faulty conditions
• Elapsed time from any kind of failure at the fibre optic network until data exchange
after a corrective action depends on total length of fibre ring.
This is typically 40–500 ms (local unit). During that time, the transferred data frames
should be seen as corrupted or missed.
Note:
Be ware of that full duplex will not work in redundant ring.