background image

23

6651-22611

Hints

If the fibre distance is long it may be necessary to adjust the bus parameter Slot time, the 
monitoring time (tbit) of the sender of frame for acknowledgement of recipient and the 

TSDR Station Delay of Responders, at configuration of the PROFIBUS DP master.
If the time between transferred PROFIBUS DP frames is long, it may be necessary to 
allow a longer time of interruption in receiving frames, using DIP-switches.
If disturbances in the electrical PROFIBUS DP network result in missed frames, it may be 
necessary to allow a number of consecutive faulty frames before the bus is considered to 
be out of operation, using DIP-switches.

Summary of Contents for ODW-610-F1

Page 1: ...www westermo com ODW 610 F2 Fibre Optic Modem Industrial Converter PROFIBUS DP to Fibre Optic Link Repeater line and redundant ring...

Page 2: ...2 6651 22611...

Page 3: ...s for a particular purpose are made in relation to the accuracy and reliability or contents of this document Westermo reserves the right to revise this document or withdraw it at any time without prio...

Page 4: ...port or any connected fibre although this unit is designed to meet the Class 1 Laser regulations Care recommendations Follow the care recommendations below to maintain full operation of unit and to fu...

Page 5: ...special treatment It is very sensitive to dust and dirt If the fibre will be disconnected from the modem the protective hood on the transmitter receiver must be connected The protective hood must be...

Page 6: ...ent in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Type Approval Compliance EMC EN 61000 6 1 Immun...

Page 7: ...ion 200 ms 40 residual voltage 500 ms 70 residual voltage Mains freq 50 Hz EN 61000 4 16 Signal ports 100 V 50 Hz line to earth Mains freq 50 Hz SS 436 15 03 Signal ports 250 V 50 Hz line to line Radi...

Page 8: ...r or when isolation of the electrical network is needed The maximum optical fibre distance depends on selected fibre transceiver and fibre type Data rate up to 12 Mbit s ODW 610 F2 converts PROFIBUS D...

Page 9: ...he electrical port UnitS to which the addressed Slave is connected receives PROFIBUS DP data from the Slave UnitS converts slave data and transfers the slave frame via ring A The repeating of transfer...

Page 10: ...only one optical fibre link end unit converted data will be transmitted in one direction via CH 1 only Data received from one ODW 610 F2 optical fibre port will be repeated through the other optical...

Page 11: ...upplied with safety extra low voltage SELV It is designed to operate permanently over a wide input range and provided with two independent inputs allowing redundancy should either supply fail 9 positi...

Page 12: ...all system delay The Redundant ring and Multidrop application Overall system delays differ see below Redundant ring one data exchange The data exchange between PROFIBUS DP master and slave via ODW 610...

Page 13: ...s connected to PROFIBUS DP master and addressed slave Example Redundant ring one data exchange between master and one slave One PROFIBUS DP master and 11 slaves with data rate 1 5 Mbit s 12 ODW 610 F2...

Page 14: ...t 1 0 Apeak Polarity Reverse polarity protected Redundant power input Yes Isolation to PROFIBUS DP and Status port Connection Detachable screw terminal Connector size 0 2 2 5 mm2 AWG 24 12 Shielded ca...

Page 15: ...5 125 and 50 125 m Wavelength 1550 nm 1310 nm 1310 nm 1310 nm Transmitter Output optical power min max 5 0 dBm 5 0 dBm 15 8 dBm 20 14 dBm Receiver Input sensitivity 34 dBm max 34 dBm max 31 dBm max 31...

Page 16: ...rminal PROFIBUS DP RS 485 D sub 3 position Direction Description No 1 NO Contact with C when link is in operation No 2 C Common No 3 NC Open no con tact with C when fibre link is in operation 4 positi...

Page 17: ...2 out of opera tion CH 1 Channel ON Fibre link at port CH 1 in operation Data can be transmitted OFF Fibre link at port CH 1 out of opera tion DPR Receive PROFIBUS DP Flash Receive data on the electri...

Page 18: ...ne optical fibre port CH 1 ON 1 2 3 4 5 6 7 8 Multidrop application mid unit Both optical fibre ports CH 1 CH 2 ON 1 2 3 4 5 6 7 8 Redundant ring application ON 1 2 3 4 5 6 7 8 65535 tbit interruption...

Page 19: ...ON 1 2 3 4 5 6 7 8 6 faulty frame before data rate is seen as unidentified S1 No extended retry limit ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 7 faulty frame before data rate is seen as unidentified S1...

Page 20: ...cing is recommended for the use of unit in full operating temperature range and service life Removal Press down the black support at the top of the unit See figure Mounting This unit should be mounted...

Page 21: ...e the fibre optical network Redundant ring Set switch S2 3 set to ON and all others to OFF at all units Connect the fibre links between the units Connect the power supply to all units The Fibre links...

Page 22: ...twork Multidrop mid units CH 1 CH 2 Set switch S2 2 set to ON and all others to OFF Multidrop end units CH 1 only All switches should be set to OFF Connect the fibre links between the units Connect th...

Page 23: ...onders at configuration of the PROFIBUS DP master If the time between transferred PROFIBUS DP frames is long it may be necessary to allow a longer time of interruption in receiving frames using DIP sw...

Page 24: ...REV B 6651 22611 2019 01 Westermo Network Technologies AB Sweden Westermo SE 640 40 Stora Sundby Sweden Tel 46 16 42 80 00 Fax 46 16 42 80 01 E mail info westermo com www westermo com...

Reviews: