14
6620-2200
RS-232
Electrical specification
EIA/TIA-232
Data rate
1 200 bit/s – 115.2 kbit/s
Data format
7 or 8 data bits, Odd, even or none parity, 1 or 2 stop bits;
Σ
9 – 12 bits
Protocol
Transparent
Retiming
Yes
Transmission range
Cable length
≤
15 m
Isolation to
Power port 3 kV
rms
50 Hz 1 min
ISDN line 2 kV
rms
50 Hz 1 min
I/O 1.5 kV
rms
50 Hz 1 min
Galvanic connection to
RS-485
Connection
9-pin D-sub female (DCE)
Shielded cable
Not required*
Miscellaneous
Do not connect RS-232 and RS-422/485 simultaneously
Generic I/O Input
Electrical specification
Opto isolated input
Input voltage range
0 – 60 VDC
Input current
5mA @ 60 VDC
Input inactive
Input active
U
in
<2.5 V
U
in
>5.0 V
Transmission range
Cable Length
≤
15 m
Connection
Detachable screw terminal (DCE)
Connector size
0.2 – 2.5 mm
2
(AWG 24 – 12)
Isolation to
Power port 3 kV
rms
50 Hz 1 min
ISDN line 2 k
Vrms
50 Hz 1 min
RS-232 2 kV
rms
50 Hz 1 min
RS-485 2 kV
rms
50 Hz 1 min
I/O output 2 kV
rms
50 Hz 1 min
Shielded cable
Not required*
* To minimise the risk of interference, a shielded cable is recommended when the cable is located inside 3 m
boundary to the rails and connected to this port.
The cable shield should be properly connected (360°) to an earthing point within 1 m from this port.
This earthing point should have a low impedance connection to the conductive enclosure of the apparatus
cabinet, or similar, where the unit is built-in. This conductive enclosure should be connected to the earthing
system of an installation and may be directly connected to the protective earth.