Westell NPGMT1125 Technical Practice Download Page 2

____________________________________________________________________________________

  

 

 

 

 

 

 

 

 

 

 

  

 

 

 

2

1. GENERAL DESCRIPTION

 

1.1.  The Westell NPGMT1125 Fuse Panel 
provides up to 20 circuits for the distribution of 
DC power to equipment.  Each of the 20 circuits 
is individually protected by a GMT style 
telecommunication fuse (20A max) located on 
the panel's faceplate. Alarm circuits are 
provided to indicate and extend alarm 
conditions when faults occur.  Normal Operation 
LEDs are provided to indicate the status of each 
bus in the panel. 

 

1.2.  Input wiring is connected to a high current, 
2-hole lug input block located at the rear of the 
panel.  A 90 degree standard copper barrel 
compression lug is recommended for 
connecting power to the input block (see page 4 
for compatible lugs).  Each group of fuses or 
bus has its own completely isolated inputs, 
allowing the distribution of two battery voltages 
through the same panel.   

 

1.3.  The power is distributed to the load side 
equipment through GMT style fuses. There are 
10 fuses per fuse group and two groups per 
panel.  Each fuse position is available for 
installer connection at the rear of the panel.  A 
designation card is provided for keeping records 
of which position is connected to which 
equipment and what amperage is to be used. 

 

 

1.4. Alarm circuits are provided to alert service 
personnel of fault conditions. A fuse alarm is a 
blown fuse within a given bus. A red fuse alarm 
LED

!

on the faceplate will illuminate when 

a fuse alarm condition is present. As well, the 
green Normal Operation LED 

9

 will extinguish 

to signal a fuse alarm or input power failure.  If a 
fuse failure occurs, the alarm relay for that bus 
will change state. These fuse panels have 
common (C), normally open (NO) and normally 
closed (NC) terminals for alarms for each bus.  
Note, the use of the alarm contacts is optional, if 
you do not wish to extend the alarms, you don’t 
have to do anything with the alarm outputs. The 
“Normal” condition of the relay exists when 
there are no blown fuses in the panel.  

The local 

alarm LEDs are located on the front of the panel 
as shown in Figure 1.4.1. 

 

LED SYMBOL 

SIGNIFICANCE 

GREEN

 

9

 

NORMAL OPERATION 

RED

 

!

 

BLOWN FUSE

 

10

7

8

9

2

1

3

POS

9

!

Ì

9

!

Ì

 

Figure 1.4.1 

 

1.5. The NPGMT Fuse Panels are made from 
0.050" steel and painted off-white. The 
NPGMT1125 is designed to fit 19" wide racks 
and use only one 1.75" panel space.   
 

2.  APPLICATION

 

2.1.  The NPGMT1125 Fuse Panels are 
designed to be used in the distribution of DC 
power.  They are rack mount panels that can 
provide fused DC power to up to 20 individual 
circuits, or 10 pieces of equipment, providing 
redundant battery feeds to each.  

 

2.2  The NPGMT family fuse panels are suitable 
for installation as part of a Common Bonding 
Network (CBN) for electrically bonding the shelf 
type chassis of this fuse panel to its equipment 
rack (via mounting brackets or chassis bonding 
studs). Note that all power return inputs (RTNs) 
are electrically isolated from each other and from 
the fuse panel chassis.  As well, this family of fuse 
panels is suitable for restricted access locations in 
Network Telecommunications Facilities and OSP. 

 

3.  CIRCUIT DESCRIPTION

 

3.1.  Power is connected to the fuse panel via 
¼” studs on 5/8” centers located at the rear of 
the panel (torque 5.5 ft-lbs).  These inputs are 
high current stud blocks that supply current to 
the fuse panel. Connect the battery return cable 
to the stud input that is labeled “RTN” and the 
Battery supply cable to the terminals labeled 
“BAT”.  

Summary of Contents for NPGMT1125

Page 1: ...es in each 20Amps GMT position max Polarity insensitive 24 or 48 Vdc battery voltage This panel can operate at 200 Amps of output current per panel 100 Amps per Bus Barrier terminal strips for fused o...

Page 2: ...e alarm relay for that bus will change state These fuse panels have common C normally open NO and normally closed NC terminals for alarms for each bus Note the use of the alarm contacts is optional if...

Page 3: ...ided WARNING For safety reasons all wiring should be done with the power source removed when possible Rack Mount Instructions Elevated Operating Ambient For closed or multi unit rack assemblies the op...

Page 4: ...the panel should already be ground to the rack via the 12 24 thread forming rack screws and outside tooth lock washers In addition to grounding via the mounting brackets an appropriate cable size as...

Page 5: ...ut fuse rating Compatible lugs for Input Block 2 hole compression lugs for 1 4 studs on 5 8 centers torque 5 5ft lbs example Panduit LCD1 14A 1awg wire LCD2 14A 2awg wire LCD4 14A 4awg wire LCD6 14A 6...

Page 6: ...ipment by anyone other than an authorized Westell representative will void the warranty 7 2 Westell will repair or replace any defective Westell equipment without cost during the warranty period if th...

Page 7: ...____________________________________________________________________________________ 7 Westell...

Page 8: ...C NEG 24 VDC 9 9 Insert fuse flag down 20A MAX BUS B ACCEPTS C NC A A B B TRQ nuts to 5 5 ft lbs max TRQ nuts to 5 5 ft lbs max BAT RTN BUS B TRQ nuts to 3 ft lbs max BAT RTN BUS A NO is center alarm...

Page 9: ...____________________________________________________________________________________ 9...

Reviews: