background image

030-101868 Rev A 

Section A90-DCP10X10

 

 

 

________________________________________________________________________________

 

 

Page 3 of 6 

1509IARA 

 

 

Figure 4.2.1

 

4.3. 

Mount the panel on the equipment rack using the thread 

forming  #12-24  rack  mounting  screws  and  tooth  lock  washers 
provided.  If you want the cables to exit the top of the panel, use 
standard lugs and discard the top protective shield.  If you want 
the cabling to exit the back of the panel, use right angle lugs and 
discard the back protective shield.  

 

 
 
 
Rack Mount Instructions: 
 

Elevated  Operating  Ambient

  -  For  closed  or  multi-unit  rack 

assemblies,  the  operating  ambient  may  be  greater  than  room 
ambient.  Take care to install  the equipment  in an environment 
compatible  with  the  maximum  ambient  temperature  (Tma) 
specified by the manufacturer. 
 

Reduced air flow

 - Installation of the equipment in a rack should 

be such that the amount of air flow required for safe operation is 
not compromised. 
 

Mechanical  Loading

  -  Mounting  of  the  equipment  in  the  rack 

should be such that a hazardous condition is not achieved due to 
uneven mechanical loading. 
 

Circuit  Overloading

  -  Consideration  should  be  given  to  the 

connection of the equipment to the supply circuit and the effect 
that  overloading  of  the  circuits  might  have  on  overcurrent 
protection  and  supply  wiring.    Appropriate  consideration  of 
equipment  nameplate  ratings  should  be  used  when  addressing 
this concern. 
 

Reliable earthing

 - Reliable earthing of rack-mounted equipment 

should  be  maintained.    Particular  attention  should  be  given  to 
supply  connections  other  than  direct  connections  to  the  branch 
circuit. 

 

WARNING:

 For safety reasons all wiring should be done with all 

power sources removed (when possible).  
 

Note:

  A  readily  accessible  disconnect  device  shall  be 

incorporated in the building installation wiring. 
 
4.4. 

Remove  the  distribution  fuse  feeding  the  input  cables 

that are to be connected to the new panel.  Remove the 2 outer 
nuts on each side and slide the return bar assembly off the unit 
to access the input terminals.  Attach the input cables to the input 

terminals  in  accordance  to  the  National  Electrical  Code, 
ANSI/NFPA,  and  Canadian  Electrical  code.    Hook  up  the  input 
cables to the input terminals (“BAT” & “RTN” for each bus).  Each 
high current input terminal can accept 2 - two-hole compression 
lug    (3/8”  on  1”,  torque  to  20  ft-lbs).  Once  the  inputs  are 
connected, re-install the ground bar assembly, and the 4 nuts that 
hold it in place.  

 

    

 

Figure 4.4.1 

 

4.5. 

The battery outputs (BAT) and ground returns (RTN) are 

also located on the back of the panel.  Each fuse/breaker position 
and terminal position is numbered 1-10.  Connect your load side 
equipment  to  the  panel,  and  record  which  equipment  is 
connected to which input on the designation card (supplied).   
 
4.6. 

All  battery  return  (“RTN”)  connections  are  also 

terminated using two-

hole lugs (1/4” on 5/8” centers).  Note, these 

returns are isolated from the chassis frame.   
 
4.7. 

This panel has Bus A, and Bus B alarm contacts.  Each 

alarm  has  a  common  (C),  normally  open  (NO)  and  normally 
closed (NC) alarm contact. In an alarm the “C” contact will short 
to the “NO” contact, and the “NC” will open.  Wire-wrap the alarm 
connections as per your alarm system requirements.  The alarm 
contacts are limited to 1A through an auto resettable fuse within 
the  panel.    The  panel  comes  preconfigured  to  work  with  fuse 
alarms  and  mid-trip  style  breaker  alarms.    If  you  wish  to  use 
standard non mid-trip breakers, adjust the shunt on the pluggable 
alarm card to the “NON MID-TRIP” position. 
 
4.8. 

Chassis  Ground:    For  safety  reasons,  and  as 

recommended  by  NEBS,  the  chassis  should  be  electrically 
connected to the rack ground.  From step 4.3. the panel should 
already be ground to the rack via the #12-24 thread forming rack 
screws and outside tooth lock washers.  In addition to grounding 
via  the  mounting  brackets,  it  is  recommended  you  ground  the 
chassis using a ground cable and the two ¼” bolts on the inner 
sidewall  of  the  chassis  (1/4”  bolt  torque;  5.5ft-lbs  or  7.5Nm). 
Consult  the  National Electric  Code,  ANSI/NFPA,  and Canadian 
Electrical code for AWG sizes. 
 
4.9. 

The input wiring feeding this panel should be protected 

by a Listed fuse/breaker rated for at least 60Vdc, with a trip rating 
of 750 Amps Max.  With input wiring connected and this input fuse 
installed, the panel should power up with the Normal Operation 

LED 

 illuminated and without any red LEDs

!

 illuminated, 

and the relays should be in the “Normal” state (“C” connected to 
“NC”).   

Reviews: