5.3 InSignal adaptation
5.3.1
SIGNAL (Type of input signal)
Command
Parameters
Unit
Group
SIGNAL:I X
i= W|X
x= OFF|U0-10|I4-20
-
EASY
This command can be used to change the type of input signal (voltages or current) and to define the direction
of the signal. This command is available for all analogue inputs (W and X).
OFF= Deactivation of the input
5.3.2
N_RANGE:X (Sensor nominal pressure)
Command
Parameter
Unit
Group
N_RANGE:X X
x= 1… 10000
%
EASY
This command defines the nominal working range of the feedback sensor. Wrong parameterization causes
wrong system settings. The control parameters cannot be calculated correctly in case of wrong values.
The N_RANGE:X value is set per cent in relation to the working range. Because this is a universal controller,
the working range of the system is defined to 100% as reference value. The N_RANGE should not be set
lower than 100% if possible-
5.3.3
OFFSET:X (Sensor offset)
Command
Parameter
Unit
Group
OFFSET:X X
x= -60000… 60000
0.01 %
EASY
Adjustment of the zero point of the sensor. Reference value is always the working range.