9.4.8.1 Parametrization Cross Muting (X)
• For general information on the cross muting function, see
• All settings under the muting function must be carried out in one go. If the cross muting menu item is called
up again, the parameter configurations must be set again for the desired options.
• The following selection options are available for cross muting:
a) Timeout / muting duration
OSSD
RES
SIG LOW
ERROR
300 sec:
• There is a time limit on the maximum duration of an active muting
sequence. There are two values to choose from.
– 300S: Muting duration max. 300 s
– 8H: Muting duration max. 8h
• For more information on the “muting duration” function, see
OSSD
RES
SIG LOW
ERROR
8 hours
OSSD
RES
SIG LOW
ERROR
Back
OSSD
RES
SIG LOW
ERROR
b) Belt stop
OSSD
RES
SIG LOW
ERROR
Switch on
• The “belt stop” function stops the monitored muting counter for
as long as a valid signal is present. This means that the muting
duration can be extended in the event of process-related mal-
functions.
– ON: Belt stop activated
– OFF belt stop deactivated
• For more information on the “belt stop” function, see
OSSD
RES
SIG LOW
ERROR
Switch off
OSSD
RES
SIG LOW
ERROR
Back
OSSD
RES
SIG LOW
ERROR
c) Muting enable