- 14 -
Installation manual
M-WRG-M/MB-FK1 / FK2
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L AT I O N & H E AT R E C O V E R Y
Fig. 8:
Wall breakthrough for installation kit
without
filler piece, dimensions in millimetres
Fig. 9:
Wall breakthrough for installation kit
with
filler piece, dimensions in millimetres
9.2.2
Breaking through an existing wall
WARNING
Danger due to damaging supply lines and changing the stress loadings
►
Make sure that there are no supply lines in the vicinity of the wall breakthrough (e.g. gas,
water or power).
►
Make sure that the wall breakthrough does not affect the local static loading requirements.
►
Fit a lintel if necessary.
►
Break through the wall. There are two possible versions of the wall breakthrough:
— Wall breakthrough with recess (see Fig. 8) for installation kit
without
filler piece
M-WRG-M/Fü
— Full-width wall breakthrough (see Fig. 9) for installation kit
with
filler piece
M-WRG-M/Fü