Welotec OWLF 4007 Fa S1 User Manual Download Page 8

Seite / Page 29 

Delay between teach signal and response on alarm output: 

t11 

alarm output 

external teach input 

Seite / Page 30 

Time 

Description of timing functions 

Value 

Comment 

t1 

Minimum button hold time to enter 
teach mode 

5 s 

Using the button, this feature can 
only be used within 5 minutes 
after power-up. Using the external 
teach input, it may be used at any 
time. 

t2 

Maximum waiting time after 
teaching the first position. 

< 20 s 

If the button has not been pushed 
during this interval, the sensor will 
leave the teach mode without any 
changes.  

t3 

LED on as response for the first 
position. 

approx 3 s 

t4 

Maximum waiting time after 
teaching the second position. 

< 20 s 

If the button has not been pushed 
during this interval, the sensor will 
leave the teach mode without any 
changes. 

t5 

LED on and “OK response” after 
the second position. 

approx 3 s 

t6 

LED Blinking for “NOT OK 
response” after teaching the 
second position. 

approx  5 s 

t7 

Minimal time between high/low 
transition of alarm output high/low 
transition of the external teach 
input at the beginning of the teach. 

1 ms 

Seite / Page 31 

t8 

Pulse lengths on external teach 
input for first position. 

30 .. 2000 ms 

t9 

Pulse lengths on external teach 
input for second position. 

30 .. 2000 ms 

t10 

Delays between teach signal and 
response on alarm output at the 
rising edge of the signal. 

< 20 ms 

t11 

Delay between teach signal and 
response on alarm output at the 
falling edge of the signal 

< 10 ms 

t12 

Minimum blinking time for the 
reset to factory settings with 
button. 

10 s 

t13 

Blinking time after reset to factory 
settings 

> 0.2 s 

As long as the button is down or 
the external teach input is high. 

t14 

Minimum blinking time for the 
reset to factory settings with 
external teach input. 

10 s 

 

t15 

Minimum high time of the external 
teach input after the alarm output 
has been set at the end of the 
setting of the factory settings. 

0.2 s 

 

Seite / Page 32 

Alarm output 

The alarm output indicates when an object is outside the measuring range or when the received 
signal cannot be used for measuring distance. In this case, the output shows 0 V (4 mA). 

The sensor has no internal hold function if measured values are missing. It provides  real time 
measuring. 
In some critical applications (poorly reflective objects),  the sensor sometimes loses the signal and 
the output signal drops down to 0 V (4 mA). For such applications, we recommend to use the alarm 
output.  Before reading the analog signal, observe the alarm output; if it is active, the analog signal 
must be  invalid. 

Summary of Contents for OWLF 4007 Fa S1

Page 1: ...the sales documentation apply at all times Seite Page 4 2 Introduction The latest generation of laser distance sensors are setting new standards in terms of speed and performance The short response ti...

Page 2: ...urface has to be flat Be aware of the max tightening torque In case of EMC the sensor has to be grounded and a shielded cable has to be used The 90 rotating connecter allows wiring the sensor from the...

Page 3: ...justed and linearized on a reference object The object is a white ceramic sheet with an absolutely flat surface Many objects have a surface structure that is within the resolution of the sensor or rou...

Page 4: ...s larger than the real distance Transparent objects The light passes the object without a diffuse reflection No measurment is possible Highly reflective objects Only direct reflection No measurmentis...

Page 5: ...a c i p y T e g n a r g n i r u s a e m t h g u a t R M e g n a r g n i r u s a e m t h g u a t R M Seite Page 19 OWLF 4030 FA S1 L r o r r e y t i r a e n i l l a c i p y T n o i t u l o s e r l a c...

Page 6: ...nge This is the position that will later produce 0 V or 4 mA 5 Briefly press the button again The LED will stop blinking and will stay on for about 3 sec to indicate that the first position has been s...

Page 7: ...eaching the sensor via the external teach input is equivalent to the teaching procedure via the button There is no 5 min time limit The sensor may be taught at any time In addition to the LED the alar...

Page 8: ...30 2000 ms t9 Pulse lengths on external teach input for second position 30 2000 ms t10 Delays between teach signal and response on alarm output at the rising edge of the signal 20 ms t11 Delay between...

Page 9: ...ce It may range from T3 White or gray objects reflect well enough to enable a less than half the sampling of interval T3 Only very dark objects actually need the maximum sampling interval T1 T2 12 28V...

Page 10: ...0 1 x a m P N P t u p t u o m r a l A Voltage supply range 12 28 VDC A m 0 4 V 4 2 i e b A m 0 2 1 t n e r r u c y l p p u S Seite Page 38 OWLF Reverse polarity protection yes voltage supply only Shor...

Page 11: ...ction The sync input or the teach in wire is connected to Vs Connect sync input or the teach in wire to 0 V The receiving beam is covered by an object edge step Make sure that no object is in the rece...

Reviews: