CONNECTION:
Warning. Danger of death through electric shock!
⚫
Must be installed by professional electrician.
⚫
Disconnect power source.
⚫
Cover or shied any adjacent live components.
⚫
Ensure device cannot be switched on.
⚫
Check power supply is disconnected.
➢
Unload the transparent vinyl cover which is at the bottom of the sensor.
➢
Loose the screws in the connection terminal, and then connect the power to connection terminal of
sensor according to connection-wire diagram.
➢
Install back the transparent vinyl cover into the original location.
➢
Fold the metal spring of the sensor upwards, until they are in “I” position with sensor, and then put the
sensor into the hole or installation box which is on the ceiling and has the similar size with the sensor.
Releasing the spring, the sensor will be set in this installation position.
➢
After finishing installing, turn on the power and then test it.
STEP1 STEP 2 STEP 3
CONNECTION-WIRE DIAGRAM:
(See the right figure)
TEST:
➢
Turn the TIME knob anti-clockwise on the minimum (10s). Turn the LUX knob clockwise on the
maximum (sun).
➢
Switch on the power; the sensor and its connected lamp will have no signal at the beginning.
➢
After Warm-up 30sec, the sensor will start working. If the sensor receives the induction signal, the lamp
will turn on. While there is no another induction signal any more, the load will stop working within
10sec±3sec and the lamp will turn off.
➢
Turn LUX knob anti-clockwise on the minimum (-). If the ambient light is more than 10LUX, the sensor
will not work and the lamp stops working too. If the ambient light is less than 10LUX (darkness), the
sensor will work. Under no signal condition, the sensor will stop working within 10sec±3sec.
Note: When testing in daylight, please turn LUX knob to (SUN) position, otherwise the sensor lamp
could not work!