Installation and operating instruction
Dual fuel burner WGL30/1-C ZM
7 Commissioning
83260202 1/2019-02 La
62-144
7.2 Adjusting the burner
7.2.1 Adjusting gas side
DANGER
Risk of electric shock
Touching the ignition device can lead to electric shock.
Do not touch ignition device during the ignition process.
Set fuel selection switch to GAS.
Check mixing pressure during commissioning [ch. 7.1.1].
1. Preset combustion manager
Unplug bridging plug No. 7 on combustion manager.
Switch on voltage supply.
Combustion manager drives to Standby.
Press [G] and [L/A] keys simultaneously.
Combustion manager changes to access level.
Press [+] key.
Combustion manager changes into the setting level for step points.
Press [+] key.
Factory setting operating point P
9
(full load) is displayed.
Press and hold [L/A] key and set air damper setting determined using the [–] or
[+] key [ch. 7.1.7].
Press and hold [G] key using [–] or [+] key set gas butterfly valve to the same
value.