Installation and operating instruction
Dual fuel burner WGL30/1-C ZM
7 Commissioning
83260202 1/2019-02 La
51-144
7.1.1 Connect measuring devices
Pressure measuring device for mixing pressure
Open pressure test point for mixing pressure
1
and connect pressure measur-
ing device.
1
Guide values for mixing pressure
Partial load
Mixing pres-
sure
(1
Full load
Mixing pres-
sure
(1
70 … 170 kW
1 … 4 mbar
125 kW
3 … 4 mbar
140 kW
4 … 5 mbar
160 kW
6 … 7 mbar
180 kW
7 … 9 mbar
200 kW
8 … 10 mbar
220 kW
9 … 11 mbar
240 kW
9 … 11 mbar
260 kW
8 … 10 mbar
280 kW
8 … 9 mbar
300 kW
8 … 9 mbar
320 kW
8 … 9 mbar
340 kW
8 … 9 mbar
(1
Guide values, which could deviate depending on combustion chamber resist-
ance.